CONCRETE QUALITY CONTROL DURING CONSTRUCTION


By
1) KAUSHAL KISHORE
Materials Engineer
Roorkee
Kaushal Kishore is retired from IIT, Roorkee and now a Consulting Materials Engineer. He has over 50 years of
experience in all types of Concrete Mix Design.
2) RAKESH SHARMA
Vice President Project
Supertech Limited
Rakesh Sharma is Vice President Project of M/s Supertech Limited. He has 28 years of experience in Construction.
I.T. Park, Doon Square Mall at Dehradun, Uttarakhand is being constructed by M/s Supertech Ltd. For this site M-30
grade of concrete suitable for pumped concrete is required. Aggregates for construction was stored at site. Its
analysis report is given in Table 2.
For laboratory trial 5 brands of PPC cement bags were taken from local market. They were identified as cement
brand, 1, 2, 3, 4 and 5. Two reputed brands of normal superplasticizers based on sulphonated naphthalene
formaldehyde (SNF) were taken for trials. They were identified as SP (A) and SP (B) to find their compatibility with
the given 5 brands of PPC cement identified as cement brand 1, 2, 3, 4 and 5.
COMPATIBILITY
The behavior of concrete in the presence of superplasticizers is related to the amount and type of sulfate added to
the clinker. The rheological and setting Behavior are changed depending on whether the sulfate is added as
anhydrite, hemihydrates, or gypsum. The difference are explained by the different rates of dissolution of these
sulfates.
It is also important to note that all admixtures belonging to the same generic type may not behave similarly in
concrete because of the variations in the molecular weight, cautions associated with them, chain length, etc.
Similarly the same type of cement generically may be different in mineral, alkali and sulfate contents, and fineness.
As per IS: 456-2000 Admixture should not impair durability of concrete nor combine with the constituent to form
harmful compounds nor increase the risk of corrosion of reinforcement. The workability, compressive strength and
the slump loss of concrete with an without the use of admixtures shall be established during the trial mixes before
use of admixtures. If two or more admixtures are used simultaneously in the same concrete mix, data should be
obtained to assess their interaction and to ensure their compatibility.
The performance of concrete admixtures including superplasticizers depend upon the admixtures and concrete
making materials and their compatibility. It is necessary to evaluate concrete admixtures for specific use with the
concrete making materials and mix proportions to be used on the work under actual field conditions.
Cement is composed of four major compounds, namely, C 3s, C2s, C3A and C 4AF. In additions, a number of minor
oxide such as K2O and Na2O, MgO and SO3 which is contributed by gypsum, which is added in the final stages
of cement manufacture as a set regulator. When there is less C3A available, superplasticizer would tend to get
absorbed in higher amount on C3S and C2S, resulting in a reduction in the strength development.
Table 1 : Superplasticing chemicals

Ref.: 1
S.No.

Class

Origin

Relative
cost

1.

Lignosulphonates

Derived from neutralization, precipitation, and fermentation processes of


the waste liquor obtained during production of paper-making pulp from
wood

2.

Sulphonated
melamine
formaldehyde
(SMF)

Manufactured by normal resinification of melamine formaldehyde

3.

Sulphonated
naphthalene
formaldehyde
(SNF)

Produced from naphthalene by oleum or SO3 sulphonation; subsequent


reaction with formaldehyde leads to polymerization and the sulphonic acid
neutralized with sodium hydroxide or lime

4.

Polycarboxylic
ether (PCE)

Free radical mechanism using peroxide initiators is used for


polymerization process in these systems

MIX DESIGN DETAILS


1. As per IS: 456-2000, M-30 grade of concrete design for a mean target strength of
30 + 1.65 x 5 = 38.3 N/mm 2
at 28 days age
2. Workability (a) Mix with NO admixture, only for comparison
Slump + 40 mm
(b) Mix with superplasticizer for pumped concrete slump +90 mm.
Pouring time with in 40 minutes.
3. From many laboratory trials, the following mix design identified for final trials.
M-30 grade of concrete quantity of materials per cu.m of concrete on the basis of saturated and surface dry
aggregates.
1. Water =

180 kg/m3

2. Cement, PPC =
3. Sand =

410 kg/m3

750 kg/m3

4. 5 mm crushed aggregate =
5. 20 mm crushed aggregate =
6. Normal superplasticizer =
-

500 kg/m3
540 kg/m 3
5.800 kg/m3

Total =

2385.8 kg/m3

Note: With cement brand No. 3 and SP (B) 28 days laboratory cubes average density found to be 2394 kg/m 3.
4. All the 150 mm cube samples are the average of 3 cubes and they are with in + 15% of the average value.
5. For conclusion of Lab trials the cubes compressive strength is given in Table 3.
6. The mix design is carried out from references 2 and 3.
7. The above given design mix is used in all the Lab trial mixes. The same design mix along with cement brand
3 with superplasticizer (B) is followed in the construction. Site cube results are given in Table 4.
CONCLUSION
1. If we are producing concrete into superplasticizer, then we can achieved 11% more strength compare to normal
concrete with respect to about 4% increments in cost per cubic meter. This is very important superplasticizer must
be compatiable with the cement proposed to be used in the construction.
2. On the basis of laboratory experimental investigations and studies carried out in the present work, it is concluded
that though the concrete mix proportion is the same in all the trial mixes, the workability, compressive strength and
setting times of cement concrete are considerably different depending on the brand of the cement and brand of
superplasticizer.
3. If superplasticizer is not compatiable with the cement lower strength will be obtained. This can be seen in Table 3.
4. The results given in this paper are our findings other researchers/sites should draw conclusions by testing with
their own site materials, and not depend upon the test results of this paper.
5. In the mix design cement is 410 kg/m3. With the present set of materials this cannot be reduce, as per reasons
given below:
(a) Water = 180 kg + 3.654 kg water in the superplasticizer total water = 183.654 kg/m3. Free W/c ratio =
183.654/410 = 0.45.
(b) For workability consideration water cannot be reduce. For durability requirements free W/c ratio also cannot be
increase from 0.45.
(c) The dosage of superplasticizer cannot be increase due to retardation of setting time of concrete.
REFERENCES
1. R. Rixom and N. Mailvaganam, Chemical Admixture for Concrete, E & FN Spon, London 1999.
2. Kishore Kaushal, Mix Design for Pumped Concrete, Journal of Central Board of Irrigation and Power, Vol. 49.
No.2, Apr. 1992, pp. 81-92.
3. Kishore Kaushal, Mix Design for Pumped Concrete, NBM & CW Sept. 2010, pp. 204-217.
4. IS: 456-2000, Plan and Reinforced Concrete Code of Practice (Fourth Revision) BIS, New Delhi.
5. IS: 1489, Specifications for Portland Pozzolana Cement, BIS, New Delhi.
6. IS: 9103-1999, Specification for Admixtures for Concrete (First revision) BIS, New Delhi.
Table 2. Test report of site aggregates
Percentage passing by mass
I.S. Sieve size

Sand
(crushers)

Crushed Agg

Combine grading of
mix

Suitable combine grading for pumped


concrete

42%

12.5
m

20
mm

28%

30%

40 mm

100

100

100

100

100

20 mm

100

100

94

98

100

12.5 mm

85

10 mm

100

58

60

60-73

4.75 mm

92

40

40-58

2.36 mm

80

34

28-46

1.18 mm

50

21

18-35

600 Micron

36

15

12-25

300 Micron

21

7-15

150 Micron

10

2-06

Specific gravity

2.65

2.65

2.65

Water
absorption %

0.9

0.6

0.5

Bulk density
kg/lit

1.67

1.40

1.39

Table 3 : Cube compressive strength (N/mm 2) Laboratory results


Cement Brand Numbers

Mix without Admixture

Mix with SP (A)

Mix with SP (B)

3 days

7 days

28 days

3 days

7 days

28 days

3 days

7 days

28 days

23.8

27.3

39.9

23.9

24.5

32.9

24.9

25.2

35.1

27.2

32.5

40.7

22.1

30.0

42.5

25.9

30.8

41.8

19.3

25.9

35.7

16.0

21.6

35.3

23.6

26.0

39.7

15.9

19.7

29.6

17.7

21.2

27.7

18.9

23.6

30.0

20.0

23.5

34.0

18.9

23.9

33.2

23.3

26.9

33.0

Note:
1. Cement brand 2 and 3 found to be achieving the designed target strength of 38.3 N/mm2 with superplasticizer
brand (B). As cement brand 3 is found to be available in bulk at site. Hence cement brand 3 and superplasticizer
brand (B) is allowed in the construction.
2. Manufacturer of all the 5 brands of PP cement claims, cement conforms to IS: 1489 Manufacturer of 2 brands of
superplasticizer claims, their product conforms to IS: 9103-1999.
Table 4 : Cube compressive strength construction site results with cement brand number 3 and

superplasticizer brand SP (B). All the samples are of M-30 grade concrete of the same site.
Sample Number 28 days compressive strength in N/mm 2
1

39.5

31.0

39.9

39.7

41.7

34.4

39.1

35.6

37.1

10

37.8

11

39.5

12

40.1

REMARKS
1. Characteristic compressive strength compliance requirements IS: 456-2000 with amendments Table 11 (clause
16.1 and 16.3)
Specified
grade

Mean of group of 4
N/mm2 Mi

Non-overlapping consecutive Test results in

Individual test results in


N/mm2 Min

1)

2)

3)

M15 and
above

fck + 0.825 x establishe standard deviation (round off to nearest

> fck 3 N/mm 2

0.5 N/mm 2)
or
> fck + 3 N/mm2
whichever is greater

RESULT : The site concrete have the compliance of M-30 grade of concrete.
2. With the present sets of material further economy in cement cannot be obtained. See item 5 of conclusion of this
paper.