Sie sind auf Seite 1von 115

DC INVERTER AIR CONDITIONER

SERVICE MANUAL

V:3.0

UNIT:
AUD-18UX4SGKL
AUD-24UX4SZLH
AUD-36UX4SAMH
AUD-48UX6SPHH
AUD-60UX6SPHH

AUC-18UX4SGAA
AUC-24UX4SZEA
AUC-36UX4SAEA
AUC-48UX6SPFA
AUC-60UX6SPFA

AUD-18UX4SZKL1
AUD-24UX4SALH1
AUD-36UX4SAMH1

AUC-18UR4SZAA1
AUC-24UR4SAEA1
AUC-36UR4SAEA1

AUV-18UR4SZA1
AUV-24UR4SAA1
AUV-36UR4SAB1
AUV-48UR6SPC
AUV-60UR6SPC

Hisense Corporation

Table of Contents
Page
1GENERAL

2SPECIFICATION

15

3OUTLINES AND DIMENSIONS

24

3-1 INDOOR

24

3-2 OUTDOOR

29

4 DIAGRAM&DATA

33

4-1 Refrigerant Flow Diagram

33

4-2MAX. Refrigerant Pipe Length and Height Difference

36

4-3 Electric Diagrams

37

4-4Air flow and ESP Chart Diagrams(for duct type)

39

5ELECTRICAL DATA

44

5-1 Electric Wiring Diagrams

44

5-2. Electric Control

57

5-3. Dip Switch Setting of Outdoor

66

5-4. Digital Display Switch of Outdoor

67

5-5. Static Pressure Setting(only for duct type)

69

5-6. Ambient Temperature Revise(INDOOR)


5-7 Sensor Parameter
6CONTROL MODE
6-1 Indoor Control Mode
6-2 Outdoor Control Mode
7TROUBLE SHOOTING
7-1 Error Codes
8CHECKING COMPONENTS

71
72
80
80
83
86
81
97

8-1 Check Refrigerant System

97

8-2 Check Parts Unit

99

1.GE
ENERAL

1.1 Featuress
Duct Type Aiir Conditioner

Features

Save Insttallation Spa


ace
The indoor unit can
c be installled inside the
e ceiling con
nveniently.

Optional Static Pressure

18
8k: optional 10Pa
1
/30Pa, 24K/36K 50Pa/80Pa(For AUD-24UX44SALH1&AUD
D-36UX4SAMH
H1freely
chhanged between1-80Pa), 48
8K/60K: 80P
Pa/120Pa sta
atic Pressure
e.
One unit, mute optional
o
insta
allation metho
od.

High Efficciency and Environment


E
Friendly New
w Refrigerant-R410A
R410
0A can prote
ect the enviro
onment and do
d not harm to the ozone
e layer.

24-hour Timer
T
ON an
nd OFF
This Timer can be
b set to auto
omatically turn the unit on
n or off within
n a 24-hour period.
p

Mute Ope
eration
The excellent fan
n design ena
able the airflo
ow to be quie
et and smootth with minim
mum
e.
noise

Meeting Various
V
Insta
allation Requ
uirements
The back-air-inle
et type is usu
ually to be ad
dopted accorrding to the a
actual installa
ation
spacce.

1.GENERAL

The unit is also installed with down-air-inlet type and the noise will increase about 5-6
dB.

Self Recovery of Power Break


When the power supply is recovered after break, all preset are still effective and the
air-conditioner can run according to the original setting.

Fault Self-diagnose Function


When there is something wrong with the air-conditionerthe micro computer could
diagnose the faults, which can be read from the display and is convenient for
maintenance.

1.GE
ENERAL

C
Cassette
T
Type
Air Condition
ner

Fe
eatures

Save Insttallation Spa


ace
The indoo
or unit can be
b installed in
nside the ceilling convenie
ently.

High Efficciency and Environment


E
Friendly New
w Refrigerant-R410A
R410A ca
an protect the environme
ent and do no
ot harm to the ozone laye
er.

24-hour Timer
T
ON an
nd OFF
This Time
er can be sett to automatiically turn the
e unit on or off
o within a 24
4-hour period.

Mute Ope
eration
The exce
ellent fan dessign enable the airflow to be quiet and
d smooth witth minimum noise.
n

Self Reco
overy of Pow
wer Break
When the
e power supp
ply is recovered after bre
eak, all prese
et are still effe
ective and th
he
air-condittioner can run according to the origina
al setting.

Fault Selff-diagnose Function


F
When the
ere is someth
hing wrong with
w the air-co
onditioner, the micro com
mputer could diagnose
d
the faults, which can
n be read from
m the display
y and is convvenient for m
maintenance.

1.GENERAL

Ceiling &Floor Air Conditioner

Features

Save Installation Space

The indoor units thickness is only 230mm,can be installed inside the ceiling conveniently.

Flexible Installation Options

According to the actual installation space,The indoor unit can be installed in the ceiling
or on the floor. One unit, Two installation method.

High Efficiency and Environment Friendly

New Refrigerant-R410A
R410A can protect the environment and do not harm to the ozone layer.

24-hour Timer ON and OFF

This Timer can be set to automatically turn the unit on or off within a 24-hour period.

Mute Operation

The excellent fan design enable the airflow to be quiet and smooth with minimum noise.

Various Refrigerant Pipe Connect Methods

The refrigerant pipe can be connect from 3 different directions(rear,right or top) .More methods,
more conveniently.

Self Recovery of Power Break

When the power supply is recovered after break, all preset are still effective and the
air-conditioner can run according to the original setting.
4

1.GENERAL

Fault Self-diagnose Function

When there is something wrong with the air-conditioner, the micro computer could diagnose the
faults, which can be read from the display and is convenient for maintenance.

1.GENERAL

1.2 Product Lineup


Type

Model

18

24

36

48

Duct Type

AUD-

Cassette Type

AUC-

Ceiling&Floor
type

AUV-

60

1.GENERAL

1.3 MODEL IDENTIFICATION

A U C -18 U R 4 S Z A A 1

serial number
K:Outdoor Unit Indetification
G:Indoor Unit Indetification
S:Refrigement R410A F:Refrigement R22
4:220V-240V/50HZ/1P

6:380V-415V/50HZ/3P

X: Wire Romote Controller R:Wireless Romote Controller


U:DC-Invert Heat Pump Type H:Heat Pump Type C:Cooling Only
Cool Capacity:18x10 3Btu/h
Type:D-Duct Type,C-Cassette Type,V-Ceiling&Floor Type,W-Outdoor Unit
Unit
Air Conditioner

1.GE
ENERAL

1.4 Produuct Pictture


Duct Type
M
Model

AUD-18UX44SGKL

AUD-24UX4S
SZLH

Indoor

Ouutdoor

M
Model

AUD-48UX6S
SPHH

AUD-36UX44SAMH

AUD-48UX6S
SPHH

Indoor

Ouutdoor

1.GE
ENERAL

M
Model

AUD-18UX44SZKL1

AUD-24UX4S
SALH1

AUD-36UX44SAMH1

Indoor

Ouutdoor

M
Model

Indoor

Ouutdoor

1.GE
ENERAL

Caassette Type

M
Model

AUC-18UX44SGAA

AUC-24UX4S
SZEA

Indoor

Ouutdoor

AUC-48UX6S
SPFA
M
Model

AUC-36UX44SAEA

AUC-60UX6S
SPFA

Indoor

Ouutdoor

10

1.GE
ENERAL

M
Model

AUC-24UR4S
SAEA1
AUC-36UR4S
SAEA1

AUC-18UR44SZAA1

Indoor

Ouutdoor

11

1.GENERAL

Ceiling &Floor Type


Model

AUV-18UR4SZA1

AUV-24UR4SAA1

Indoor

Outdoo
r

Model

AUV-48UR6SPC

AUV-36UR4SAB1

AUV-60UR6SPC

Indoor

Outdoo
r

12

1.GENERAL

DISPLAY PANEL:
Cassette Type
18k

24K36K48K60K

13

1.GENERAL

Ceiling&Floor type

14

2.SPECIFICATIONS

2.Specifications
DuctType
Model

AUD-18UX4SZKL1

AUD-24UX4SALH1

AUD-36UX4SAMH1

AUD-18UX4SGKL

AUD-24UX4SZLH

AUD-36UX4SAMH

AUD-48UX6SPHH

AUD-60UX6SPHH

Indoor model

AUD-18UX4SKL1

AUD-24UX4SLH1

AUD-36UX4SMH1

AUD-18UX4SKL

AUD-24UX4SLH

AUD-36UX4SMH

AUD-48UX4SHH

AUD-60UX4SHH

Outdoor model

AUW-18U4SZ1

AUW-24U4SA1

AUW-36U4SA1

AUW-18U4SG

AUW-24U4SZ

AUW-36W4SA

AUW-48U6SP

AUW-60U6SP

Ph-V-H

Power supply

9.2

6.4

10

12.6

17

Btu/h

17,000

23,900

31,400

17,000

21,800

34,100

43,000

58,000

kW

5.6

8.1

11

5.6

7.25

11.5

15

20.5

Btu/h

19,100

27,600

37,500

19,100

24,700

39,200

51,200

70,000

L/h

1.4

1.8

2.4

1.4

1.8

2.4

3.3

4.5

Cooling

kW

1.5

2.3

3.05

1.552

1.99

3.11

3.92

5.295

Heating

kW

1.6

2.65

3.25

1.55

3.19

4.15

5.65

Cooling

6.8

10.2

13.9

6.9

8.9

13.5

7.5

10.8

Heating

7.3

11.5

13.1

6.9

8.9

13.9

11.3

Max. input

kW

2.5

3.6

5.1

2.58

5.23

6.2

9.38

Max.Current

12

15.9

22.5

11.5

13.5

22.78

13

17.7

EER/COP

3.33/3.5

3.04/3.06

3.04/3.06

3.22/3.61

3.22/3.63

3.22/3.61

3.21/3.61

3.21/3.63

SEER/SCOP

5.6/3.8

5.6/3.8

5.1/3.8

Cooling Energy Class

A+

A+

Heating Energy Class

DA131S1B-28F

DA230S2C-31M

DA130S1C-20F

ATL165SD-C9A

DA250S2C-30M

TNB306FPNMC

LNB42FSAMC

0.59

0.9520

U-V:

U-V:

Capacity
Heating
Dehumidification
Rated input

Rated Current

Model

DA250S2C-30MT

Type
Winding resistance

Rotary

0.5520

0.73 (at20)

05520

15

380V-415V3N~/50Hz

kW

Cooling

Compressor

20V-240V ~/50Hz

0.9520

2.SPECIFICATIONS
Model

AUD-18UX4SZKL1

AUD-24UX4SALH1

AUD-36UX4SAMH1

AUD-18UX4SGKL

AUD-24UX4SZLH

AUD-36UX4SAMH

AUD-48UX6SPHH

AUD-60UX6SPHH

Indoor model

AUD-18UX4SKL1

AUD-24UX4SLH1

AUD-36UX4SMH1

AUD-18UX4SKL

AUD-24UX4SLH

AUD-36UX4SMH

AUD-48UX4SHH

AUD-60UX4SHH

Outdoor model

AUW-18U4SZ1

AUW-24U4SA1

AUW-36U4SA1

AUW-18U4SG

AUW-24U4SZ

AUW-36W4SA

AUW-48U6SP

AUW-60U6SP

2433;U-W :2433;

2433;U-W :2433;

V-W: 2.304at

V-W: 2.304at

25

25

MITSUBISHI

MITSUBISHI

ELECTRIC

ELECTRIC

Y7S423C032

Y7S423C032

YDK65-6-9024

YDK65-6-9024

YDK65-6-9061

YDK65-6-9061

Brand

GMCC

Indoor

Model

Outdoor

Model

Fan motor

GMCC

GMCC

GMCC

YSK110-40-4-A(

SIC-70CW-F195

SIC-101CW-F1246

YSK110-40-4-A(

HS16)

-1

-1

HS16)

SIC-71FW-D812

SIC-71FW-D8121-

1-1

ARW4401QH

YDK29-6I-22

Indoor

Speed
Hi/Med/Low
type

Fan speed

Outdoor

Speed
Hi/Med/Low

Air circulation

r.p.m

Weight

YDK70-6H-3

YDK95-6-9043

1000/910/810(30

1060/980/900(30P

1130/850/950(10

1070/990/860(50

1150/1070/1020(

1250/1200/1100(

1250/1200/1100(

Pa)

Pa)

a)

Pa)

Pa)

50Pa)

120Pa)

120Pa)

tube-axial

r.p.m
r.p.m

0-810

0-810

0-810

900/750/500

840/780/560

800/640/540

700/600/500

700/600/500

Hi/Med/Low

m/h

850

1100

1800

850

1100

1700

2000

2000

Outdoor

Hi/Med/Low

m/h

--

--

--

--

--

--

--

--

Pa

10*/30

30*/(1~80

30*/(1~80

optional)

optional))

10*/30

50*/80

50*/80

80*/120

80*/120

Wireless Remote control-J1-05(E)

Indoor

LWH

mm

1170447190

900720270

1300720270

1170447190

900720270

1300720270

1300800350

1300800350

Outdoor

LWH

mm

900300640

950340840

950340840

800260570

900300640

940340840

9503401386

9503401386

Indoor

LWH

mm

1340580236

1170X340X870

1570X340X870

1340580236

1170X340X870

1570X340X870

1550X940X410

1550X940X410

Outdoor

LWH

mm

1050400700

1110460980

1110460980

950365645

1050700400

1110460980

11104601530

11104601530

Indoor

Net/Gross

kg

24/28

32/37

43/51

24/28

32/37

38/43

50/58

50/58

16

Y7S423C024

1130/850/950(10

Operating control

Packing

Y6S419C56

Indoor

Static Pressure(*Default Setting)

Dimensions

GMCC

centrifugal fan

type
Fan

HIGHLY

2.SPECIFICATIONS
Model

AUD-18UX4SZKL1

AUD-24UX4SALH1

AUD-36UX4SAMH1

AUD-18UX4SGKL

AUD-24UX4SZLH

AUD-36UX4SAMH

AUD-48UX6SPHH

AUD-60UX6SPHH

Indoor model

AUD-18UX4SKL1

AUD-24UX4SLH1

AUD-36UX4SMH1

AUD-18UX4SKL

AUD-24UX4SLH

AUD-36UX4SMH

AUD-48UX4SHH

AUD-60UX4SHH

Outdoor model

AUW-18U4SZ1

AUW-24U4SA1

AUW-36U4SA1

AUW-18U4SG

AUW-24U4SZ

AUW-36W4SA

AUW-48U6SP

AUW-60U6SP

45/51

69/73

70/74

35.5/39

50/56

70/74

101/107

108/112

--/54(SOUND

--/61(SOUND

--/56(SOUND

POWER)

POWER)

POWER)

--/41

43/49

43/51

49/53

49/53

--/62(SOUND

--/65(SOUND

--/70(SOUND

POWER)

POWER)

POWER)

--/56

53/58

--/58

--/60

--/60

mm

12.7/6.35

15.88/9.52

15.88/9.52

12.7/6.35

15.88/9.52

15.88/9.52

19.05/9.52

19.05/9.52

20

30

30

20

30

30

50

50

10

20

20

10

15

15

30

30

Outdoor

Net/Gross

kg

Indoor

Hi/Med/Low

dB(A)

Outdoor

Hi/Med/Low

dB(A)

Noise lever

Gas/Liquid
Max. refrigerant pipe
length

Refrigerant piping

Max. difference in level


Connection method

Flare

Connection

Power wiring

mm2

3 core x1.5

3 core x2.5

3 core x2.5

3 core x1.5

3 core x2.5

3 core x2.5

5 core x2.5

5 core x2.5

wiring

Signal wiring

mm2

4core x0.75

4core x0.75

4core x0.75

4core x0.75

4core x0.75

4core x0.75

4core x0.75

4core x0.75

kg

1.4

1.68

2.1

1.27

1.5

2.1

3.5

EEV

EEV

EEV

EEV

EEV

EEV

EEV

EEV

Refrigerant charge(R410a)
Throttle Type
Ambient temp

Cooling -1548

Heating -1024

17

2.SPECIFICATIONS

Cassettetype
Model

AUC-18UR4SZAA1

AUC-24UR4SAEA1

AUC-36UR4SAEA1

AUC-18UX4SGAA

AUC-24UX4SZEA

AUC-36UX4SAEA

AUC-48UX6SPFA

AUC-60UX6SPFA

Indoor model

AUC-18UR4SAA1

AUC-24UR4SEA1

AUC-36UR4SEA1

AUC-18UX4SAA

AUC-24UX4SEA

AUC-36UX4SEA

AUC-48UX4SFA

AUC-60UX4SFA

Outdoor model

AUW-18U4SZ1

AUW-24U4SA1

AUW-36U4SA1

AUW-18U4SG

AUW-24U4SZ

AUW-36W4SA

AUW-48U6SP

AUW-60U6SP

Power supply

Ph-V-Hz
kW

Cooling

Capacity

Btu/h

kW
Heating

Dehumidification

Btu/h

L/h

20V-240V ~/50Hz
51.2-6.5

7.02.2-8.0

17,100(4,100-22

23,900

,200)

7,500-27,300

5.6(1.8-7.2

8.22.5-10

19,100(6,100-24

28,000

,600)

8,500-34,100

1.490.40

9.53.610.5

6.4

10

12

17

17000

21800

34100

41000

58000

5.6

11.5

15

20

19100

23900

39200

51200

68200

2.30.403.6

3.07(0.44.2)

1.552

1.91

3.07

3.72

5.095

32,400
12,300-35,800

11.0(3.0513.8)
37,500
10,400-47,100

Cooling

kW

Heating

kW

1.75(0.382.15)

2.73(0.383.6)

3.10(0.384.2)

1.55

1.92

3.15

3.95

5.45

Rated

Cooling

6.6

10.1

13.4

6.9

8.5

13.36

6.5

6.5

Current

Heating

7.8

12.2

13.5

6.89

8.5

13.76

Cooling

kW

2.5

3.6

4.25

2.421

2.92

4.55

5.32

8.5

Heating

kW

2.5

3.6

4.25

2.581

2.72

4.85

5.92

9.1

Cooling

12

15.5

20

9.9

13.1

19.83

10.7

10.7

Heating

12

15.5

20

11.47

12.1

21.13

11.7

11.7

EER/COP

3.36/3.20

3.04/3.0

3.09/3.55

3.22/3.61

3.35/3.64

3.26/3.65

3.39/3.8

3.34/3.67

SEER/SCOP

5.6/3.8

5.6/3.8

5.1/3.8

Cooling Energy Class

A+

A+

Heating Energy Class

Rated input

Max. input

Max.Current

2.25

18

380V-415V3N~/50Hz

2.SPECIFICATIONS
Model

AUC-18UR4SZAA1

AUC-24UR4SAEA1

AUC-36UR4SAEA1

AUC-18UX4SGAA

AUC-24UX4SZEA

AUC-36UX4SAEA

AUC-48UX6SPFA

AUC-60UX6SPFA

Indoor model

AUC-18UR4SAA1

AUC-24UR4SEA1

AUC-36UR4SEA1

AUC-18UX4SAA

AUC-24UX4SEA

AUC-36UX4SEA

AUC-48UX4SFA

AUC-60UX4SFA

Outdoor model

AUW-18U4SZ1

AUW-24U4SA1

AUW-36U4SA1

AUW-18U4SG

AUW-24U4SZ

AUW-36W4SA

AUW-48U6SP

AUW-60U6SP

DA131S1B-28F

DA230S2C-31M

DA250S2C-30M

DA130S1C-20F

ATL165SD-C9A

DA250S2C-30MT

TNB306FPNMC

LNB42FSAMC

U-V:

U-V:

2433;U-W :2433;

2433;U-W :2433;

Model
Type

Compressor

Rotary

Winding resistance

0.5520

0.73 (at20)

05520

0.9520

0.59

0.9520

V-W: 2.304at 25

Brand
Mode

Indoor

Fan motor

Mode

Outdoor

GMCC

GMCC

GMCC

GMCC

HIGHLY

GMCC

EHDS50AQ

ARW5901QH

EHDS50AQH

YDK95-28-4-B

ARW5901QH

EHDS50AQH

SIC-71FW-D812

SIC-71FW-D812

1-1

1-1

YDK29-6I-22

YDK70-6H-3

YDK95-6-9043

ARW4401QH

Indoor

Speed
Hi/Med/Low
type

Fan speed

Outdoor

Speed
Hi/Med/Low

MITSUBISHI

MITSUBISHI

ELECTRIC

ELECTRIC

SIC72FW-D8124-2B

SIC72FW-D8124-2
B

YDK65-6-9024

YDK65-6-9024

YDK65-6-9061

YDK65-6-9061

r.p.m

980/840/720

440/380/370

630/520/460

980/840/720

r.p.m

440/370/280

630/520/460

630/520/460

630/520/460

tube-axial

r.p.m

0-810

0-810

0-810

900/750/500

840/780/560

800/640/540

700/600/500

700/600/500

Air

Indoor

Hi/Med/Low

m/h

850

1100

1600

850

1100

1600

2000

2400

circulation

Outdoor

Hi/Med/Low

m/h

--

--

--

--

--

--

--

--

Pa

Static Pressure(*Default Setting)


Operating control
Dimensions

Wireless Remote controlJ1-05)

Indoor

LWH

mm

650570270

840840248

840840248

650570270

840840248

840840248

840840298

840840298

Outdoor

LWH

mm

900300640

950340840

950340840

800260570

900300640

940340840

9503401386

9503401386

19

25

centrifugal fan

type
Fan

V-W: 2.304at

2.SPECIFICATIONS
Model

AUC-18UR4SZAA1

AUC-24UR4SAEA1

AUC-36UR4SAEA1

AUC-18UX4SGAA

AUC-24UX4SZEA

AUC-36UX4SAEA

AUC-48UX6SPFA

AUC-60UX6SPFA

Indoor model

AUC-18UR4SAA1

AUC-24UR4SEA1

AUC-36UR4SEA1

AUC-18UX4SAA

AUC-24UX4SEA

AUC-36UX4SEA

AUC-48UX4SFA

AUC-60UX4SFA

Outdoor model

AUW-18U4SZ1

AUW-24U4SA1

AUW-36U4SA1

AUW-18U4SG

AUW-24U4SZ

AUW-36W4SA

AUW-48U6SP

AUW-60U6SP

Panel

LWH

mm

65065030

95095037

95095037

65065030

95095037

95095037

95095037

95095037

Indoor

LWH

mm

770750310

930930290

930930290

770750310

930930290

930930290

930930340

930930340

Outdoor

LWH

mm

1050400700

1110460980

1110460980

940360640

1050700400

1110460980

11104601530

11104601530

Panel

LWH

mm

730730130

101099095

1010990115

730730130

101099095

101099095

101099095

101099095

Indoor

Net/Gross

kg

21/25.5

24/30

26/32

21/25.5

24/30

26/32

29/35

29/35

Outdoor

Net/Gross

kg

45/51

69/73

70/74

35.5/39

50/56

70/74

101/107

108/112

Panel

Net/Gross

kg

2.4/5

6/7.5

6/7.5

2.4/5

6/7.5

6/7.5

6/7.5

6/7.5

Db

--/48/58

36/42/53

--/50/61

--/48

36/42

--/50

43/49

43/49

Db

45/50/62

--/58/70

--/58/70

--/56

53/58

--/58

--/60

--/60

Gas/Liquid

mm

12.7/6.35

15.88/9.52

15.88/9.52

12.7/6.35

15.88/9.52

15.88/9.52

19.05/9.52

19.05/9.52

Refrigerant

Max. refrigerant pipe length

20

30

30

20

30

30

50

50

piping

Max. difference in level

10

20

20

10

15

15

30

30

3 core x1.5

3 core x2.5

3 core x2.5

5 core x2.5

5 core x2.5

4core x0.75

4core x0.75

4core x0.75

4core x0.75

4core x0.75

Packing

Weight

Low/Hi/sound

Indoor

power

Noise lever

Low/Hi/sound

Outdoor

power

Connection method

Flare

Connection

Power wiring

mm2

wiring

Signal wiring

mm2

Refrigerant charge(R410a)

kg

Throttle Type
Ambient temp

3 core x1.5

3 core x2.5

3 core x2.5

4 core shielded wire x 0.75


1.4

1.68

2.1

1.27

1.5

2.1

3.5

EEV

EEV

EEV

EEV

EEV

EEV

EEV

EEV

Cooling -1548

Heating -1024

20

2.SPECIFICATIONS

Ceiling&Floortype
Model

AUV-18UR4SZA1

Power supply

Ph-V-Hz

AUV-24UR4SAA1

AUV-36UR4SAB1

AUV-48UR6SPC

1N,220V-240V/50Hz

AUV-60UR6SPC

3N~,380V-415V/50Hz

kW

5.0

7.0

9.2

12.6

17.0

Btu/h

17,000

23,900

31,400

43,000

58,000

kW

5.8

8.6

11.0

15.3

20.5

Btu/h

19,800

29,000

37,500

52,200

70,000

L/h

1.4

1.8

2.4

3.3

4.5

Cooling

kW

1.55

2.3

3.05

3.92

5.295

Heating

kW

1.75

2.77

3.3

4.2

5.65

Cooling

7.0

10.1

13.9

7.5

10.8

Heating

8.0

13.0

15.0

8.0

11.3

Max. input

kW

2.5

3.6

5.1

6.2

9.38

Max.Current

12.0

15.9

22.5

13.0

17.7

EER/COP

3.33/3.31

3.04/3.10

3.02/3.33

3.21/3.64

3.21/3.61

SEER/SCOP

5.6/3.8

5.6/3.8

5.1/3.8

DA131S1B-28FZ

DA230S2C-31MT

DA250S2C-30MT

TNB306FPNMC

LNB42FSAMC

U-V: 2433;U-W :2433;

U-V: 2433;U-W :2433;

V-W: 2.304at 25

V-W: 2.304at 25

Cooling
Capacity
Heating
Dehumidification
Rated input

Rated Current

Model
Type

Rotary
U-V:

Compressor

Winding resistance

2.806;U-W :2.806;
M:2.1A:2.81

M:1.37A:1.7

V-W: 2.651 at
25

MITSUBISHI

Brand

GMCC

GMCC

GMCC

MITSUBISHI ELECTRIC
ELECTRIC

Fan motor

Indoor

Model

YSK110-22-4-A( HS24)

SIC-70CW-F1100-6

21

SIC-70CW-F1140-3

Y7S423C032

Y7S423C032

2.SPECIFICATIONS
Model

AUV-18UR4SZA1

AUV-24UR4SAA1

AUV-36UR4SAB1

AUV-48UR6SPC

M:187A:245,60,33,143

M:209.4;A:245,60,33,143

M:75;A:97.5

M:79.7;A:59.4,20.2,108

AUV-60UR6SPC

Winding
resistance

M:79.7;A:59.4,20.2,10
8

(at20)
Model
Outdoor

ARW4401QH

SIC-71FW-D8121-1

YDK65-6-9024

YDK65-6-9024

YDK65-6-9061

YDK65-6-9061

M:83;A1:23.4A2:14A1:6

M:83;A1:23.4A2:14A1:

3.5

63.5

1000/1100/1200

1000/1100/1200

SIC-71FW-D8121-1

Winding
resistance

M:231.5;A:168

M:78;A:36.2,51.5,109.2

M:59.1;A:85.8

(at20)
type
Fan

Indoor

Speed
Hi/Med/Low
type

Fan speed

Outdoor

Speed
Hi/Med/Low

Air circulation

centrifugal
r.p.m

630/720/850

910/1030/1150

r.p.m

tube-axial

r.p.m

0-810

0-810

0-810

500/600/700

500/600/700

Hi/Med/Low

m/h

800

1100

1600

2000

2000

Outdoor

Hi/Med/Low

m/h

--

--

--

--

--

Pa

Operating control

Packing

Weight

Noise lever

Wireless Remote control-J1-05(E)

Indoor

LWH

mm

990680230

990680230

1290680230

1580680230

1580680230

Outdoor

LWH

mm

900300640

950340840

950340840

9503401386

9503401386

Indoor

LWH

mm

1100820350

1100820350

1400820350

1690820350

1690820350

Outdoor

LWH

mm

1050700400

1110460980

1110460980

11104601530

11104601530

Indoor

Net/Gross

kg

27/33

30/35

37/44

47/54

47/54

Outdoor

Net/Gross

kg

45/51

69/73

70/74

101/107

108/112

Indoor

Hi/Med/Low

dB(A)

--/54(SOUND POWER)

--/63(SOUND POWER)

48/50/53

48/50/53

--/60

--/60

--/64(SOUND
POWER)

Outdoor

Hi/Med/Low

dB(A)

--/62(SOUND POWER)

--/65(SOUND POWER)

22

1080/1160/1220

Indoor

Static Pressure(*Default Setting)

Dimensions

fan

--/70(SOUND

2.SPECIFICATIONS
Model

AUV-18UR4SZA1

AUV-24UR4SAA1

AUV-36UR4SAB1

AUV-48UR6SPC

AUV-60UR6SPC

POWER)
Gas/Liquid
Refrigerant
piping

Max. refrigerant pipe


length
Max. difference in level

mm

12.7/6.35

15.88/9.52

15.88/9.52

19.05/9.52

19.05/9.52

15

30

30

50

50

7.5

15

15

20outdoor blow15

20outdoor blow15

Connection method
Connection
wiring

Power wiring
Signal wiring

Refrigerant charge(R410a)

Flare
2

mm

3 core x1.5

3 core x2.5

3 core x2.5

5 core x2.5

5 core x2.5

mm

4core x0.75

4core x0.75

4core x0.75

4core x0.75

4core x0.75

kg

1.4

1.68

2.1

3.5

EEV

EEV

EEV

EEV

EEV

Throttle Type
Ambient temp

Cooling -1548

Heating -1024

23

3. OUTLINES AND DIMENSION


3.OUTLINES AND DIMENSIONS
3-1 INDOOR
Duct type

24

3. OUTLINES AND DIMENSION

25

3. OUTLINES AND DIMENSION


Cassette type
18K

24K,36K

26

3. OUTLINES AND DIMENSION


48K,60K

27

3. OUTLINES AND DIMENSION


Ceiling&Floor Type

28

3. OUTLINES AND DIMENSION


3-2.OUTDOOR
18K(AUW-18U4SG)

29

3. OUTLINES AND DIMENSION


18KMODEL: AUW-18U4SZ1
24K(MODEL: AUW-24U4SZ)

30

3. OUTLINES AND DIMENSION


24&36K
MODEL: AUW-24U4SA1, AUW-36U4SA1, AUW-36W4SA

31

3. OUTLINES AND DIMENSION


48K&60K
MODEL: AUW-48U6SPAUW-60U6SP

32

4 DIAGRAM&DATA

4. Diagrams&DATA
4.1 Piping Diagrams
18k type

33

4 DIAGRAM&DATA
24k &36K type
Stop Valve

Ambient
temperature
sensor

Ambient
temperature
sensor

Discharge
temperature
sensor
4-Way Valve

Coil
temperature
sensor

Discharge
Pressure
Switch

Outdoor
heat
exchanger

Coil
temperature
sensor
Suction
temperature
sensor

Indoor heat exchanger

Defrost
temperature
sensor

Compressor

Stop Valve

strainer

Electronic expansion valve

Indoor

Outdoor

34

Accumulator

strainer

4 DIAGRAM&DATA
48K&60K
Stop Valve

Ambient
temperature
sensor

Discharge
temperature
sensor

Suction
Pressure
Switch

4-Way Valve
Coil
temperature
sensor

Ambient
temperature
sensor

Discharge
Pressure
Switch

Outdoor
heat
exchanger

Coil
temperature
sensor
Suction
temperature
sensor

Indoor heat exchanger

Defrost
temperature
sensor

Compressor

Stop Valve

strainer

Electronic expansion valve

Indoor

Outdoor

35

Accumulator

strainer

4 DIAGRAM&DATA

4-2MAX. Refrigerant pipe length and height difference

*Doyourbesttoreducethepipelength.Longpipemaycausecapacityoftheindoorunitincline.

Outdoorunitprecharged

Totalrefrigerantpipelength
0m~5m

AUW18U4SG

1270g

0g

AUW24U4SZ

1500g

0g

AUW-36U4SA
AUW-18U4SZ1
AUW-24U4SA1
AUW-36U4SA1
AUW-48U6SP
AUW-60U6SP

2100g

0g

1400g

0g

1680g

0g

2100g

0g

3000g

0g

3500g

0g

Xg=15g/m (Totalpipelength(m)5)

Xg=35g/m (Totalpipelength(m)5)

36

5m60m

4 DIAGRAM&DATA

4-3ELECTRIC Diagrams

Recommend Wire Size

Model

POWER SUPPLY

Power Source

Transmitting Cable

Cable Size

Size

mm2

mm2

18K

220-240V,50Hz

31.5

40.75

24K/36K

220-240V,50Hz

32.5

40.75

48K/60K

380~415V,3N~,50Hz

52.5

40.75

Use an ELB (Electric Leakage Breaker). If not used, it will cause an electric shock or a
fire.
Do not operate the system until all the check points have been cleared.
(A) Check to ensure that the insulution resistance is more than 1 megohm, by measuring
the resistance between ground and the terminal of the electrical parts. If not, do not
operate the system until the electrical leakage is found and repaired.
37

4 DIAGRAM&DATA
(B) Check to ensure that the stop valves of the outdoor unit are fully opened and then start
the system.
Pay attention to the following items while the system is running.
(A) Do not touch any of the parts by hand at the discharge gas side, since the compressor
chamber and the pipes at the discharge side are heated higher than 90.
(B) DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES). It will cause a
serious Accident.

NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked in the table are selected at the maxim current of the
unit according to the European Standard ,En60 335-1. Use the wires which are
not lighter than the ordinary tough rubber sheathed flexible cord (code
designation H07RN-F) or ordinary polychloroprene sheathed flexible
cord (code designation H07RN-F) .
3) Use a shielded cable for the transmitting circuit and connect it to ground .
4) In the case that power cables are connected in series, add each unit
maximum current and select wires below.

* in the case that current exceeds 63A, do not connect cables in series.

38

4 DIAGRAM&DATA

4-4Air flow and ESP Chart Diagrams(for duct type)

18K
18KCurvefor10PaESP
35

30

25

ESP

20
15
10
5
0
500

600

700

800

900

1000

Airflowm3/h

18KCurvefor30PaESP
50
45
40

ESP

35
30
25
20
15
10
500

600

700

800
Airflowm3/h

39

900

1000

1100

4 DIAGRAM&DATA

24K
24KCurvefor50PaESP
90
80

800

900

70

ESP

60
50
40
30
20
10
700

1000

1100

1200

1300

1400

Airflowm3/h

24KCurvefor80PaESP
130
120

110

ESP

100
90
80
70
60
50
40
600

700

800

900

1000

1100

Airflowm3/h

40

1200

1300

1400

1500

4 DIAGRAM&DATA

36K(ACMOTOR)
36KCurvefor50PaESP
90
80

ESP

70

60
50
40
30
900

1100

1300

1500

1700

1900

Airflowm3/h

36KCurvefor80PaESP
130

120

110

ESP

100
90
80
70
60
50
800

1000

1200

1400
Airflowm3/h

41

1600

1800

2000

4 DIAGRAM&DATA

48K
48KCurvefor80PaESP
120

110

100

ESP

90
80
70
60
50
1500

1700

1900

2100

2300

2500

Airflowm/h

48KCurvefor120PaESP
160
150

140

ESP

130
120
110
100
90
1500

1700

1900

2100

Airflowm/h

42

2300

2500

4 DIAGRAM&DATA

60K
60KCurvefor80PaESP
120

110

100

ESP

90
80
70
60
50
1500

1700

1900

2100

2300

2500

Airflowm/h

60KCurvefor120PaESP
160
150

140

ESP

130
120
110
100
90
1500

1700

1900

2100

Airflowm/h

43

2300

2500

5. ELECTRICAL DATA
5-1.Electrical wiring diagrams
INDOOR UNIT
Duct type
AUD-18UX4SKL,AUD-18UX4SKL1

44

5. ELECTRICAL DATA
AUD-24UX4SLH,AUD-36UX4SMH

45

5. ELECTRICAL DATA
AUD-24U4SLH1,AUD-36U4SMH1

46

5. ELECTRICAL DATA
AUD-48UX4SHH,AUD-60UX4SHH

47

5. ELECTRICAL DATA
Cassette type
18k

24K ,36K,48K,60K

48

5. ELECTRICAL DATA
Ceiling&Floor type
18K,48K,60K

24K,36K

49

5. ELECTRICAL DATA
OUTDOOR UNIT
18K
AUW-18U4SG

50

5. ELECTRICAL DATA
AUW-18U4SZ1

51

5. ELECTRICAL DATA
24K
AUW-24U4SZ

52

5. ELECTRICAL DATA

AUW-24U4SA1

53

5. ELECTRICAL DATA
36K
AUW-36U4SA

54

5. ELECTRICAL DATA
AUW-36U4SA1

55

5. ELECTRICAL DATA
AUW-48U6SP
AUW-60U6SP

56

5. ELECTRICAL DATA

5-2. Electric control Board


1. Indoor control board
Duct type
18K,48K,60K
&AUD-24UX4SLH, AUD-36UX4SMH

AUD-24UX4SLH1, AUD-36UX4SMH1

57

5. ELECTRICAL DATA

CASETTE Type
18K

24K,36K,48K,60K

58

5. ELECTRICAL DATA

Ceiling & Floor type


18k,48k,60k

24k,36k

59

5. ELECTRICAL DATA

2.Control board for outdoor unit


1) OUTDOOR CONTROL BOARD
AUW-18U4SG
1) CONTROL BOARDAUW-18U4SG

CONTROL BOARDAUW-24U4SZ

60

5. ELECTRICAL DATA
AC fan motor

Heater N

N OUT

Earth
AC N IN

4-way valve
AC L IN

Heater L
Communication SI

IPM-SI

Communication N

IPM power

High pressure switch


DC+

Liquid and Gas Sensor


Electric expansion valve
DCOutdoor/suction/coil Sensor
Overload protection switch

Discharge Sensor

CONTROL BOARDAUW-36U4SA

61

5. ELECTRICAL DATA
4-way valve
Heater N
4-way valve

N OUT
Heater L

AC N IN

AC fan motor
Earth

AC L IN

Electric expansion valve


Communication SI
IPM power
IPM-SI
Communication N

AC L OUT

DC+

DC-

Suction Sensor
High pressure switch

Outdoor Sensor

Discharge Sensor

Low pressure switch

coil/defrost Sensor

CONTROL BOARDAUW-48U6SPAUW-60U6SP
Heater N

POWER IN

Transformer

Down fan motor


62

Up fan motor

5. ELECTRICAL DATA

AUW-18U4SZ1AUW-24U4SA1AUW-36U4SA1
63

5. ELECTRICAL DATA

Heater N
4-way valve

N OUT
Heater L

AC N IN

Earth

AC L IN

Electric expansion valve


Communication SI
IPM power
IPM-SI
Communication N

AC L OUT

DC+

DC-

Suction Sensor
High pressure switch

Outdoor Sensor

Discharge Sensor

Low pressure switch

coil/defrost Sensor

IPM Board
IPM BoardAUW-18U4SG
64

5. ELECTRICAL DATA

To Electrolytic
Capacitor +
To PFC Inductor-2
AC L IN
To PFC Inductor-1
To Electrolytic
Capacitor AC N IN

IPM Power
To Compressor W
To Compressor V
To Compressor U

To Main Control
Board

To Electrolytic
Capacitor +

(AUW-24U4SZ / AUW-36U4SA)

To PFC
Inductor-2

To PFC
Inductor-1

To Electrolytic
Capacitor +

ac L in
ac N in

To Electrolytic
Capacitor IPM Power

To Compressor W
To Compressor V
To Compressor U
To Electrolytic
Capacitor +
To Main Control
Board

AUW-18U4SZ1AUW-24U4SA1AUW-36U4SA1

65

5. ELECTRICAL DATA

(AUW-48U6SPAUW-60U6SP)

AC IN-V

AC IN-W

Compressor

Contacto

Compressor

AC IN-U
Inductor
Compressor
AC IN
Contact

Inductor L1

IPM-SI

66

5. ELECTRICAL DATA
5-3. DIP SWITCH SETTING OF OUTDOOR
AUW-18U4SZ1,AUW-24U4SA1,AUW-36U4SA1,AUW-36W4SA

48K&60K

67

5. ELECTRICAL DATA
5-4. Digital Display Switch of Outdoor

Digital Display Switch Introduction


It can be used to check outdoor running parameters.

There are 3 buttons on the digital display board


1SWITH buttonIndoor parameters and outdoor parameters can be select in turn by press it.
P--outdoor unit,H--indoor unit
2INCREASE buttonEach time it is pressed,the number rises by 1,hold down it,the number will be
rapidly rises
3DECREASE buttonEach time it is pressed,the number lowers by 1,hold down it,the number will be
68

5. ELECTRICAL DATA
rapidly lowers.
Parameters can be checked as following table below.
Parameter
code
0

Descriptions
Protect Code or Error Code

P.1

Target Frequency

P.2

Driver Frequency

P.4

Outdoor Electronic expansion valve Opening

P.5

Outdoor Electronic expansion valve Target Opening

P.6

Upper DC Motor Revolving Speed

P.8

AC Input Voltage

P.9

Current

P.10

Modular Temperature

P.11

Capacity needed

P.12

Modular Trouble

P.20

Outdoor Ambient Temperature

P.21

Outdoor Coil Temperature

P.22

Outdoor Defrost Temperature

P.23

Suction Temperature

P.24

Discharge Temperature

H.1

Indoor Unit Error

H.2

Indoor Ambient Temperature

H.3

Indoor Coil Temperature

H.4

Indoor Setting Temperature

69

5. ELECTRICAL DATA
5-5. Static Pressure Setting(only for duct type)
CHANGE OF STATIC PRESSURE
The static pressure outside the indoor unit can be chosen .
Models except AUD-24UX4SALH1 & AUD-36UX4SAMH1 :
You can change the static pressure by changing the fan motor terminal which refer to following
Fig.below:

AUD-24UX4SALH1 & AUD-36UX4SAMH1 :


Default static pressure is 30 Pa.
The static pressure can be freely adjusted from 1 Pa to 80 Pa by using specific wire remote
controller(YXE-C01U).
Operation details, please refer to wire remote controller manuals .
If you still have any trouble, please contact local technical service center of our company for
further information.

70

5. ELECTRICAL DATA

71

5. ELECTRICAL DATA
5-6.AMBIENT TEMPERATURE REVISE(INDOOR)
when indoor unit highly mounted,because of hot air floatation,cold air sinks,so the ambient
temperature sensed by indoor unit is higher than the actual.Then the ambient temperature need
to be revised.
It can be changed by using specific wire remote controller(YXE-C01U).
Operation details, please refer to wire remote controller manuals .

72

5. ELECTRICAL DATA
5-7. Sensor parameter
1. THE PARAMETER OF OUTDOOR COMPRESSOR DISCHARGE TEMPERATURE SENSOR:
R0=187.25K6.3%R100=3.77K2.5KB0/100=3979K1%

T[ ]
-30
-29
-28
-27
-26
-25
-24
-23
-22
-21
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9

Rmin [ K ]
908.2603
855.3955
805.9244
759.6097
716.2320
675.5881
637.4902
601.7645
568.2499
536.7970
507.2676
497.5332
453.4748
428.9819
405.9517
384.2888
363.9047
344.7169
326.6497
309.6286
293.5903
278.4719
264.2156
250.7678
238.0783
226.1003
214.7903
204.1073
194.0135
184.4732
175.4533
166.8952
158.8023
151.1467
143.9026
137.0455
130.5528
124.4033
118.5769
113.0550

Rnom [ K ]
985.5274
927.6043
873.4324
822.7471
775.3041
730.8775
689.2583
650.2533
613.6835
579.3832
547.1989
516.9882
488.6192
461.9693
436.9251
413.3808
391.2386
370.4072
350.8019
332.3441
314.9620
298.5822
283.1464
268.5936
254.8686
241.9200
229.6997
218.1630
207.2681
196.9759
187.2500
178.0255
169.3067
161.0633
153.2667
145.8905
138.9097
132.3011
126.0429
120.1146

Rmax [ K ]
1065.1210
1001.9150
924.8368
887.5944
835.9165
787.5529
742.2720
699.8601
660.1191
622.8658
587.9307
555.1565
524.3977
495.5191
486.3954
442.9105
418.9563
396.4325
375.2461
355.3104
336.5448
318.3744
302.2294
286.5448
271.7603
257.8193
244.6593
232.2612
220.5495
209.4913
199.0468
189.1529
179.8058
170.9724
162.6216
154.7246
147.2544
140.1856
133.4946
127.1591
73

DR(MIN)%
-7.84
-7.78
-7.73
-7.67
-7.62
-7.56
-7.51
-7.46
-7.40
-7.35
-7.30
-3.76
-7.19
-7.14
-7.09
-7.04
-6.99
-6.94
-6.88
-6.83
-6.79
-6.74
-6.69
-6.64
-6.59
-6.54
-6.49
-6.44
-6.39
-6.35
-6.30
-6.25
-6.20
-6.16
-6.11
-6.06
-6.02
-5.97
-5.92
-5.88

DR(MAX)%
7.47
7.42
5.56
7.31
7.25
7.20
7.14
7.09
7.03
6.98
6.93
6.88
6.82
6.77
10.17
6.67
6.62
6.56
6.51
6.46
6.41
6.22
6.31
6.26
6.22
6.17
6.11
6.07
6.02
5.97
5.93
5.88
5.84
5.80
5.75
5.71
5.67
5.62
5.58
5.54

5. ELECTRICAL DATA
T[ ]
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52

Rmin [ K ]
107.8202
102.8560
98.1470
93.6787
89.4378
85.4114
81.5875
77.9551
74.5034
71.2227
68.1036
65.1373
62.3155
59.6306
57.0752
54.6424
52.3258
50.1192
48.0168
46.0133
44.1034
42.2825
40.5458
38.8891
37.3084
35.7998
34.3596
32.9844
31.6710
30.4164
29.2176
28.0718
26.9765
25.9293
24.9277
23.9697
23.0530
22.1757
21.3360
20.5321
19.7623
19.0261
18.3211

Rnom [ K ]
114.4973
109.1728
104.1246
99.3367
94.7946
90.4842
86.3926
82.5076
78.8177
75.3122
71.9808
68.8141
65.8032
62.9395
60.2152
57.6227
55.1551
52.8058
50.5684
48.4371
46.4046
44.4711
42.6261
40.8668
39.1890
37.5883
36.0609
34.6030
33.2113
31.8823
30.6130
29.4004
28.2417
27.1342
26.0755
25.0632
24.0950
23.1688
22.2826
21.4345
20.6226
19.8468
19.1040

Rmax [ K ]
121.1586
115.4734
110.0855
104.9778
100.1342
95.5398
91.1805
87.0430
83.1150
79.3848
75.8414
72.4746
69.2746
66.2324
63.3395
60.5877
57.9695
55.4778
53.1058
50.8472
48.6960
46.6466
44.6937
42.8323
41.0576
39.3653
37.7511
36.2109
34.7412
33.3383
31.9988
30.7197
29.4979
28.3306
27.2150
26.1488
25.1293
24.1545
23.2221
22.3301
21.4766
20.6612
19.8808
74

DR(MIN)%
-5.83
-5.79
-5.74
-5.70
-5.65
-5.61
-5.56
-5.52
-5.47
-5.43
-5.39
-5.34
-5.30
-5.26
-5.21
-5.17
-5.13
-5.09
-5.05
-5.00
-4.96
-4.92
-4.88
-4.84
-4.80
-4.76
-4.72
-4.68
-4.64
-4.60
-4.56
-4.52
-4.48
-4.44
-4.40
-4.36
-4.32
-4.29
-4.25
-4.21
-4.17
-4.14
-4.10

DR(MAX)%
5.50
5.46
5.41
5.37
5.33
5.29
5.25
5.21
5.17
5.13
5.09
5.05
5.01
4.97
4.93
4.89
4.85
4.82
4.78
4.74
4.71
4.66
4.63
4.59
4.55
4.51
4.48
4.44
4.40
4.37
4.33
4.29
4.26
4.22
4.19
4.15
4.12
4.08
4.05
4.01
3.98
3.94
3.91

5. ELECTRICAL DATA
T[ ]
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95

Rmin [ K ]
17.6458
16.9986
16.3784
15.7839
15.2139
14.6673
14.1430
13.6400
13.1573
12.6941
12.2494
11.8224
11.4124
11.0185
10.6401
10.2765
9.9271
9.5912
9.2682
8.9576
8.6589
8.3716
8.0951
7.8290
7.5730
7.3264
7.0891
6.8605
6.6403
6.4282
6.2239
6.0269
5.8371
5.6542
5.4777
5.3076
5.1435
4.9853
4.8326
4.6852
4.5430
4.4058
4.2733

Rnom [ K ]
18.3926
17.7113
17.0537
16.4332
15.8338
15.2592
14.7083
14.1799
13.6730
13.1868
12.7202
12.2723
11.8424
11.4295
11.0331
10.6522
10.2863
9.9348
9.5968
9.2720
8.9597
8.6594
8.3705
8.0926
7.8252
7.5679
7.3202
7.0818
6.8522
6.6311
6.4182
6.2131
6.0154
5.8249
5.6413
5.4644
5.2937
5.1292
4.9705
4.8174
4.6697
4.5272
4.3896

Rmax [ K ]
19.1338
18.4185
17.7335
17.0774
16.4488
15.8464
15.2690
14.7154
14.1846
13.6756
13.1872
12.7186
12.2690
11.8373
11.4230
11.0251
10.6429
10.2756
9.9231
9.5841
9.2583
8.9451
8.6440
8.3544
8.0758
7.8078
7.5499
7.3018
7.0629
6.8329
6.6115
6.3982
6.1928
5.9949
5.8042
5.6205
5.4433
5.2726
5.1079
4.9492
4.7960
4.6483
4.5058
75

DR(MIN)%
-4.06
-4.02
-3.96
-3.95
-3.92
-3.88
-3.84
-3.81
-3.77
-3.74
-3.70
-3.67
-3.63
-3.60
-3.56
-3.53
-3.49
-3.46
-3.42
-3.39
-3.36
-3.32
-3.29
-3.26
-3.22
-3.19
-3.16
-3.12
-3.09
-3.06
-3.03
-3.00
-2.96
-2.93
-2.90
-2.87
-2.84
-2.81
-2.77
-2.74
-2.71
-2.68
-2.65

DR(MAX)%
3.87
3.84
3.83
3.77
3.74
3.71
3.67
3.64
3.61
3.57
3.54
3.51
3.48
3.45
3.41
3.38
3.35
3.32
3.29
3.26
3.23
3.19
3.16
3.13
3.10
3.07
3.04
3.01
2.98
2.95
2.92
2.89
2.86
2.84
2.81
2.78
2.75
2.72
2.69
2.66
2.63
2.61
2.58

5. ELECTRICAL DATA
T[ ]
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130

Rmin [ K ]
4.1453
4.0218
3.9024
3.7872
3.6758
3.5661
3.4601
3.3577
3.2588
3.1632
3.0708
2.9816
2.8953
2.8118
2.7311
2.6531
2.5776
2.5046
2.4340
2.3656
2.2995
2.2354
2.1734
2.1134
2.0553
1.9991
1.9446
1.8918
1.8406
1.7911
1.7430
1.6965
1.6514
1.6076
1.5652

Rnom [ K ]
4.2568
4.1287
4.0049
3.8854
3.7700
3.6585
3.5509
3.4468
3.3463
3.2491
3.1551
3.0643
2.9765
2.8915
2.8093
2.7299
2.6530
2.5785
2.5065
2.4368
2.3693
2.3040
2.2407
2.1795
2.1201
2.0626
2.0070
1.9530
1.9007
1.8500
1.8009
1.7533
1.7071
1.6623
1.6189

Rmax [ K ]
4.3683
4.2355
4.1074
3.9837
3.8643
3.7512
3.6419
3.5362
3.4341
3.3353
3.2398
3.1475
3.0582
2.9717
2.8881
2.8072
2.7289
2.6531
2.5798
2.5087
2.4400
2.3733
2.3088
2.2463
2.1858
2.1271
2.0702
2.0151
1.9617
1.9099
1.8597
1.8110
1.7638
1.7180
1.6736

76

DR(MIN)%
-2.62
-2.59
-2.56
-2.53
-2.50
-2.53
-2.56
-2.59
-2.61
-2.64
-2.67
-2.70
-2.73
-2.76
-2.78
-2.81
-2.84
-2.87
-2.89
-2.92
-2.95
-2.98
-3.00
-3.03
-3.06
-3.08
-3.11
-3.13
-3.16
-3.18
-3.22
-3.24
-3.26
-3.29
-3.32

DR(MAX)%
2.55
2.52
2.50
2.47
2.44
2.47
2.50
2.53
2.56
2.58
2.61
2.64
2.67
2.70
2.73
2.75
2.78
2.81
2.84
2.87
2.90
2.92
2.95
2.97
3.01
3.03
3.05
3.08
3.11
3.14
3.16
3.19
3.21
3.24
3.27

5. ELECTRICAL DATA
2. THE PARAMETER OF THE OTHER SENSOR IN INDOOR AND OUTDOOR UNIT
R0=15K2%
B0/100=3450K2%

T []
-30
-29
-28
-27
-26
-25
-24
-23
-22
-21
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10

Rmin [ K ]
60.78
57.75
54.89
52.19
49.63
47.21
44.92
42.76
40.71
38.77
36.93
35.18
33.53
31.96
30.48
29.07
27.73
26.46
25.26
24.11
23.03
21.99
21.01
20.08
19.19
18.35
17.55
16.78
16.06
15.36
14.70
14.08
13.48
12.91
12.36
11.85
11.35
10.88
10.43
9.999
9.590

Rnom [ K ]
64.77
61.36
58.15
55.14
52.30
49.62
47.10
44.73
42.49
40.38
38.39
36.51
34.74
33.06
31.47
29.97
28.56
27.22
25.95
24.75
23.61
22.53
21.51
20.54
19.62
18.74
17.92
17.13
16.38
15.67
15.00
14.36
13.75
13.17
12.62
12.09
11.59
11.11
10.66
10.230
9.816

Rmax [ K ]
68.99
65.16
61.58
58.23
55.08
52.13
49.37
46.78
44.34
42.05
39.90
37.87
35.97
34.17
32.49
30.89
29.39
27.98
26.64
25.38
24.19
23.06
22.00
20.99
20.04
19.14
18.29
17.48
16.71
15.98
15.29
14.64
14.02
13.43
12.87
12.34
11.83
11.35
10.89
10.450
10.040
77

DR(MIN)%
-6.16
-5.88
-5.61
-5.35
-5.11
-4.86
-4.63
-4.40
-4.19
-3.99
-3.80
-3.64
-3.48
-3.33
-3.15
-3.00
-2.91
-2.79
-2.66
-2.59
-2.46
-2.40
-2.32
-2.24
-2.19
-2.08
-2.06
-2.04
-1.95
-1.98
-2.00
-1.95
-1.96
-1.97
-2.06
-1.99
-2.07
-2.07
-2.16
-2.26
-2.30

DR(MAX)%
6.12
5.83
5.57
5.31
5.05
4.81
4.60
4.38
4.17
3.97
3.78
3.59
3.42
3.25
3.14
2.98
2.82
2.72
2.59
2.48
2.40
2.30
2.23
2.14
2.10
2.09
2.02
2.00
1.97
1.94
1.90
1.91
1.93
1.94
1.94
2.03
2.03
2.11
2.11
2.11
2.23

5. ELECTRICAL DATA
T []
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53

Rmin [ K ]
9.199
8.826
8.470
8.129
7.804
7.493
7.196
6.912
6.640
6.381
6.132
5.894
5.667
5.449
5.240
5.048
4.864
4.687
4.517
4.355
4.198
4.048
3.904
3.766
3.663
3.506
3.383
3.265
3.152
3.043
2.938
2.838
2.741
2.648
2.558
2.472
2.389
2.309
2.232
2.158
2.087
2.018
1.952

Rnom [ K ]
9.422
9.047
8.689
8.347
8.021
7.709
7.412
7.127
6.855
6.595
6.347
6.109
5.882
5.664
5.456
5.260
5.072
4.891
4.717
4.550
4.390
4.236
4.089
3.946
3.810
3.679
3.552
3.431
3.314
3.202
3.094
2.990
2.890
2.793
2.701
2.611
2.525
2.443
2.363
2.286
2.212
2.140
2.072

Rmax [ K ]
9.647
9.269
8.910
8.567
8.240
7.928
7.630
7.346
7.074
6.815
6.567
6.330
6.103
5.886
5.678
5.478
5.286
5.101
4.924
4.753
4.589
4.431
4.280
4.134
3.994
3.859
3.729
3.604
3.484
3.368
3.257
3.149
3.046
2.946
2.850
2.758
2.669
2.583
2.500
2.421
2.344
2.269
2.198
78

DR(MIN)%
-2.37
-2.44
-2.52
-2.61
-2.71
-2.80
-2.91
-3.02
-3.14
-3.24
-3.39
-3.52
-3.66
-3.80
-3.96
-4.03
-4.10
-4.17
-4.24
-4.29
-4.37
-4.44
-4.52
-4.56
-3.86
-4.70
-4.76
-4.84
-4.89
-4.97
-5.04
-5.08
-5.16
-5.19
-5.29
-5.32
-5.39
-5.49
-5.54
-5.60
-5.65
-5.70
-5.79

DR(MAX)%
2.33
2.40
2.48
2.57
2.66
2.76
2.86
2.98
3.10
3.23
3.35
3.49
3.62
3.77
3.91
3.98
4.05
4.12
4.20
4.27
4.34
4.40
4.46
4.55
4.61
4.66
4.75
4.80
4.88
4.93
5.00
5.05
5.12
5.19
5.23
5.33
5.40
5.42
5.48
5.58
5.63
5.69
5.73

5. ELECTRICAL DATA
T []
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96

Rmin [ K ]
1.888
1.827
1.767
1.710
1.655
1.602
1.551
1.502
1.452
1.409
1.364
1.322
1.280
1.241
1.202
1.165
1.129
1.095
1.061
1.029
0.9977
0.9676
0.9385
0.9104
0.8833
0.8570
0.8316
0.8071
0.7834
0.7604
0.7382
0.7167
0.6958
0.6755
0.6560
0.6371
0.6188
0.6011
0.5840
0.5674
0.5514
0.5359
0.5209

Rnom [ K ]
2.005
1.941
1.880
1.820
1.763
1.707
1.654
1.602
1.553
1.505
1.458
1.413
1.370
1.328
1.288
1.249
1.211
1.175
1.140
1.106
1.073
1.041
1.011
0.9810
0.9523
0.9246
0.8977
0.8717
0.8466
0.8223
0.7987
0.7759
0.7537
0.7322
0.7114
0.6913
0.6718
0.6530
0.6348
0.6171
0.6000
0.5835
0.5675

Rmax [ K ]
2.129
2.062
1.998
1.936
1.876
1.818
1.762
1.709
1.657
1.606
1.558
1.511
1.466
1.422
1.379
1.339
1.299
1.261
1.224
1.188
1.153
1.120
1.088
1.056
1.026
0.9971
0.9687
0.9412
0.9146
0.8888
0.8639
0.8397
0.8161
0.7933
0.7712
0.7498
0.7291
0.7051
0.6897
0.6709
0.6527
0.6350
0.6179
79

DR(MIN)%
-5.84
-5.87
-6.01
-6.04
-6.13
-6.15
-6.23
-6.24
-6.50
-6.38
-6.45
-6.44
-6.57
-6.55
-6.68
-6.73
-6.77
-6.81
-6.93
-6.96
-7.02
-7.05
-7.17
-7.20
-7.25
-7.31
-7.36
-7.41
-7.47
-7.53
-7.57
-7.63
-7.68
-7.74
-7.79
-7.84
-7.89
-7.95
-8.00
-8.05
-8.10
-8.16
-8.21

DR(MAX)%
5.82
5.87
5.91
5.99
6.02
6.11
6.13
6.26
6.28
6.29
6.42
6.49
6.55
6.61
6.60
6.72
6.77
6.82
6.86
6.90
6.94
7.05
7.08
7.10
7.18
7.27
7.33
7.38
7.43
7.48
7.55
7.60
7.65
7.70
7.75
7.80
7.86
7.39
7.96
8.02
8.07
8.11
8.16

5. ELECTRICAL DATA
T []
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120

Rmin [ K ]
0.5064
0.4923
0.4787
0.4655
0.4528
0.4404
0.4284
0.4168
0.4056
0.3947
0.3841
0.3739
0.3640
0.3544
0.3450
0.3360
0.3272
0.3187
0.3104
0.3024
0.2947
0.2871
0.2798
0.2727

Rnom [ K ]
0.5519
0.5369
0.5224
0.5083
0.4946
0.4814
0.4685
0.4561
0.4440
0.4323
0.4210
0.4100
0.3993
0.3890
0.3789
0.3692
0.3597
0.3505
0.3416
0.3330
0.3246
0.3164
0.3085
0.3008

Rmax [ K ]
0.6014
0.5853
0.5698
0.5547
0.5401
0.5259
0.5121
0.4988
0.4859
0.4733
0.4611
0.4493
0.4379
0.4267
0.4159
0.4055
0.3953
0.3854
0.3758
0.3665
0.3574
0.3468
0.3401
0.33

80

DR(MIN)%
-8.24
-8.31
-8.37
-8.42
-8.45
-8.52
-8.56
-8.62
-8.65
-8.70
-8.76
-8.80
-8.84
-8.89
-8.95
-8.99
-9.04
-9.07
-9.13
-9.19
-9.21
-9.26
-9.30
-9.34

DR(MAX)%
8.23
8.27
8.32
8.36
8.42
8.46
8.51
8.56
8.62
8.66
8.70
8.75
8.81
8.84
8.90
8.95
9.01
9.06
9.10
9.14
9.18
8.77
9.29
9.34

6. CONTROL MODEL
6-1 Indoor control mode
1.Major general technical parameters
1 Conditionings for operation: Ambient temperatures: (-15 - +45 ),
relative humidity

(45 - 85%).

2 Remote receiver distance: 8 m.


3 Remote receiver angle: Less than 80 degrees.
4 Temperature control accuracy: 1.
5 Time error: Less than 1%.
6 The power supply for the air conditioner
18k&24k&36K:
a.c 220V240V, 50Hz, with its fluctuation in the range of (198V 253 V).
48K&60K:
AC 380V-415V 3N/50Hz, with its fluctuation in the range of (305V-438V).
2. Functions of the controller
Control function
3.1 Emergency switch
Press the emergency button can realize the starting or closing Machine, starting up
according to the automatic mode of operation.
3.2 Operator-machine communication
Air conditioning and remote controller is provided with a temperature sensor. The
remote controller on the temperature sensor to detect the default settings of room
temperature at room temperature. If the indoor control unit for long time have not received
remote control signal, will automatically switch to the air conditioner body temperature
sensor.
3.3 Timer function
1. Timer on: When set to start in a time by the remote controller, the air conditioner starts
in the timer on condition. When the set time is up, the air conditioner will turn on and
operates in the preset conditions after receiving a signal from the remote controller. If the air
80

6. CONTROL MODEL
conditioner has not received a signal from the remote controller when the set time is up, it
will automatically start and operate in the preset conditions.
2. Timer off: When set to stop in a set time by the remote controller, the air conditioner
will start in the timer off condition. When the set time is up, the air conditioner will turn off
after receiving a signal from the remote controller. If the air conditioner has not received a
signal from the remote controller when the set time is up, it will turn off automatically.
3. Neither the turning on nor turning off operation will cancel the timer function

3.4 Sleep
1. In the heating, cooling or dehumidifying mode, press the Sleep button on the remote
controller to start or cancel the sleep function in turn, and at the same time the sleep icon on
the display screen will be on or off accordingly.
2. In the heating mode, the set temperature will decrease automatically after the sleep
function is started.
3. In the cooling mode, the set temperature will rise automatically after the sleep function
is started.
4. In default, the setting is to cancel the sleep function. Turning off the unit will also
cancel the sleep function.
3.5 High efficient run function
In Cool, Dehumidification, Fan mode, press the "SUPER " to enter the refrigeration mode,
set the temperature automatically adjust to 18; the Fan speed is powerful speed;
frequency of high frequency operation.
In the heating mode, powerful function is invalid for H1 wireless remote controller.
3.6 mute function (only for H1 wireless remote controller)
In the indoor machine operation modeYou may turn on mute function and turn off mute
function by mute key, The air conditioner will run by mute fan speed in mute mode
3.7 prevent cooling wind mode
81

6. CONTROL MODEL
In the heating-run, to prevent the indoor fan from blowing cold air, the indoor fan will stop
or run slowly until the coil is warmth.
3.8 blow waste heating and waste cooling function
The heating mode, remote shutdown, such as indoor heat exchanger temperature is
higher, the wind blowing out opportunities continue to run the waste heat.
Cool and dehumidification mode , after the compressor close, indoor machine will
continue to set the speed of operation for a period of time.
3.9 automatically model
This model does not automatically model function, emergency button cannot set the
automatic mode of operation, can use the emergency switch shutdown, remote setting the
automatic mode of indoor machine with remote signal.
3.10 Dehumidifying method:
Remote control setting dehumidifying mode, indoor machine forced to run at low
speedhigh power key or a strong bond also maintain a low wind speed, the outdoor
machine according to the refrigeration mode operation.

3.11

Fault display

If the product operation failure, outdoor and indoor display control panel lights will quote
fault.

82

6. CONTROL MODEL
6-2 Outdoor mode control
Summarization
1.1
18k24k36K

1. Voltage scale: 176V253V50Hz

2. Storage temperature scale: -4085

3. Storage humidity scale: PH30PH95

4. Working temperature:-2085

5. accuracy for temperature control 0.5


1.2
48 k60k

1. Voltage scale: 305V438V50Hz

2. Storage temperature scale: -4085

3. Storage humidity scale: PH30PH95

4. Working temperature:-2085

5. accuracy for temperature control 0.5

2Control function
83

6. CONTROL MODEL
2.1Cooling Anti-freeze Protection
To prevent indoor air conditioner evaporator temperature is too low, the indoor coil
sensor for real time detection of evaporator. If the indoor coil temperature is too low, the
compressor will protect.
2.2 Overload Protection
Air can heat exchanger temperature sensor for monitoring, when the sensor when
the temperature is too high, the compressor will be automatic protection
2.3 Exhaust temperature protection
To prevent deterioration due to high exhaust temperature of compressor, the
machine will realize the real-time detection of the temperature of exhaust gas. If the
temperature is too high compressor automatic protection
2.4 Oil-return Control
When the compressor runs for a long time low frequencies, control system will start
the return oil program. The system in the oil return to the compressor.
2.5Operation Mode
Air conditioning mode is the operation mode set by users through remote controller,
four modes are available: cooling, heating, dehumidification, as well as fan mode.
2.6 Four-way Valve Control
Four-way valve of the outdoor machine shuts down when cooling and defrosting
but starts when heating. During the heating process, the four way valve to stop working for a
period of time after compressor disconnect.
2.7 Start-up Protection:
84

6. CONTROL MODEL
To prevent compressor from restart frequently in the condition that system
pressure has not been completely balanced, it cant be restarted within 3 minutes.
2.8 Pressure Protection:
When the pressure increases to a preset value, the pressure switch will
automatically protect. Compressor will stop and report the fault code protection.

85

7. TROUBLE SHOOTING
7-1- Error code
When the air conditioner failure occurs, the fault code will displays on outdoor control
board , wire remote controller or display panel.
1. INDOOR UNINT FAULT CODE DISPLAY
WALL MOUNTED TYPE
Run the air-conditioner by wireless remote controller , continue pressing
theSLEEP button for 4 times, fault codes will flashing rapidly on the LCD . If no fault ,"00"
will display.
ERshows indoor display panel Communication fault with indoor unit control board .
FLOOR STANDING TYPE
In the case of no button-locked,continue pressing CLOCKbutton for 8 times ,fault
codes will display on the LCD for 10 seconds,automatically disappears after 10seconds.
Continue pressing SLEEPbutton of wireless remote controller for 8 times ,fault codes
will display on the LCD for 10 seconds,automatically disappears after 10seconds.
Check indoor unit control board---FAILURE LAMP
LED3 and LED2 indicates fault codes: LED2 indicate ten fault code, LED3 indicate bits
fault code (as shown fig. below).

LED2 and LED3 are failure indicate


lamps
LED2 indicate fault code ten digit
number, LED3 indicate single digit
number code

ERshows indoor display panel Communication fault with indoor unit control board

86

7. TROUBLE SHOOTING
DUCT TYPE AND CASSETTE TYPE
(1) ERROR CODES INDICATED BY WIRE REMOTE CONTROLLER(see fig. below)
When displayFE ,shows that the wire controller
cant receive the signals of indoor unit control
board ,please check communication wires.

When failure occurs, this lamp light ON.

This number shows ERROR CODE.

FIG.2 ERROR CODE DISPLAY ON WIRE REMOT CONTROLLER

2WITH DISPLAY PANEL(CASSETTE type and CEILING &FLOOR type)


Lamp RUN(LED2 ,red) and Lamp DEFROSTLED5 ,greenflashingLamp RUN display
fault code ten digit number, lamp DEFROST display fault code single digit number

(as

shown fig. below).


For examplefault code 36 led RUN & defrost flash 3 times at the same time, and led
DEFROST continue flash 3 times, reports No. 36 fault.

87

7. TROUBLE SHOOTING

88

7. TROUBLE SHOOTING

LED FALSH CONTROLflash 300mS(T1)off 300mS(T2)after 2000mS(T3)fault code


repeat displays. (as shown below)

T1 T2

T3

Fig.2 LED FALSH CONTROL

3.Duct type indoor units of VRF---FAULT CODE DISPLAY BY INDOOR BOARD

LED2 and LED5 are failure indicate


lamps
LED2(RED) indicate fault code ten
digit number, LED5(GREEN)
indicate single digit number code

89

7. TROUBLE SHOOTING
2.OUTDOOR UNINT FAULT CODE DISPLAY
1 ON/OFF UNITARY TYPEequipped with outdoor control box
Fault code display by indicate lamps of outdoor control board.

LED2-fault code lamp

LED FALSH CONTROLflash 300mS(T1)off 300mS(T2)after 900mS(T3)fault


code repeat displays. (as shown below)

T1 T2

T3

2 INVERTER UNITARY AIR CONDITONER , MULTI-SPLIT


CONDITONER&VRF
Fault code will display on digital indication board.

TYPE

AIR

VRF
Indoor unit can indicate both indoor failure and outdoor failure ,but outdoor only
indicate outdoors.

90

7. TROUBLE SHOOTING

3.Fault code display ( Driver Board )


Fault code display by indicate lamps of outdoor driver board.
LED FALSH CONTROLflash 200mS(T1)off 200mS(T2)after 900mS(T3)fault
code repeat displays. (as shown below)

T1 T2

T3

91

7. TROUBLE SHOOTING
The following is the fault code table of outdoor.

Fault

Fault description

Fault description

REMARKS

code

Outdoor environment temperature


sensor fault

The outdoor coil sensor fault

Current protective device

EEprom Data error

Refrigeration and freezing or thermal overload


protection

Outdoor environment
temperature sensor short
circuit or open circuit
The outdoor coil temperature
sensor short circuit or open circuit

EEprom Data error or EE chip fault


Refrigeration indoor coil
temperature is too low or heating
the indoor coil temperature too high

AC motor fault
Outdoor continuously for 2 minutes

Indoor and outdoor communication fault

without receipt of indoor


communication data

Application of three-phase

Phase current imbalance

power supply models


9

10

Application of three-phase

Current U phase

power supply models


Application of three-phase

Current V phase

power supply models


Application of

11

Sequence error

Three phase power supply wiring


line sequence error

three-phase power
supply models
Application of

12

three-phase power

Phase detection phase

supply models
13

Compressor overheat protection device

Compressor overheating protector


tripping
Too high system pressure leads to

14

High voltage switch motor protection/Pressure


shutdown protection

high pressure switch tripping or

Were applied to have high

pressure sensors to detect the

pressure switch or a

pressure too high to achieve

pressure sensor type

shutdown protection pressure


System low pressure causing low
15

Low voltage switch protection/Low pressure

pressure switch tripping or pressure

protection shutdown

sensors to detect the pressure is too


low to achieve the shutdown

92

Were applied to the low


pressure switch or a
pressure sensor type

7. TROUBLE SHOOTING
Fault

Fault description

Fault description

REMARKS

code
protection pressure
The outdoor coil temperature is too
16

Refrigeration overload protection

high to reach refrigeration


temperature shutdown protection

17

Exhaust temperature sensor fault

Exhaust temperature sensor short


circuit or open circuit
MUTI-SPLIT TYPE

18

19

20

21

AC voltage of high and low voltage protection

Power input AC voltage is too low or

/ fault

too high

Intake air temperature sensor fault

Condenser entrance temperature sensor fault

The outlet of the condenser temperature


sensor fault

ONLY

Exhaust temperature sensor short


circuit or open circuit
Condenser entrance temperature
sensor short circuit or open circuit
The outlet of the condenser
temperature sensor short circuit or
open circuit
The outlet of the condenser

22

The defrosting sensor fault

temperature sensor short circuit or


open circuit
FOR

23

24

25

26

Expansion valve A tube sensor fault

Expansion valve B tube sensor fault

Expansion valve C tube sensor fault

Expansion valve D tube sensor fault

Expansion valve A tube sensor


short circuit or open circuit

MUTI-SPLIT&Inverter
unitary types

Expansion valve B tube sensor

FOR MUTI-SPLIT

short circuit or open circuit

outdoor

Expansion valve C tube sensor

FOR MUTI-SPLIT

short circuit or open circuit

outdoor

Expansion valve D tube sensor

FOR MUTI-SPLIT

short circuit or open circuit

outdoor
FOR MUTI-SPLIT

27

28

29

Expansion valve A thick pipe sensor fault

Expansion valve B thick pipe sensor fault

Expansion valve C thick pipe sensor fault

Expansion valve A thick pipe sensor


short circuit or open circuit

&inverter unitary
types

Expansion valve B thick pipe sensor

FOR MUTI-SPLIT

short circuit or open circuit

outdoor

Expansion valve C thick pipe sensor

FOR MUTI-SPLIT

short circuit or open circuit

outdoor

93

7. TROUBLE SHOOTING
Fault

Fault description

Fault description

REMARKS

code
30

Expansion valve D thick pipe sensor fault

Expansion valve D thick pipe sensor

FOR MUTI-SPLIT

short circuit or open circuit

outdoor

31

High discharge pressure fault

VRF outdoor

32

Low suction pressure fault

VRF outdoor
Application of

41

three-phase power

Current sensor fault

supply ON/OFF
TYPES

42

Voltage sensor fault

43

H Pressure sensor fault

44

L Pressure sensor fault

45

IPM fault

46

IPM Communication fault

47

Too high exhaust temperature shutdown

48

Outdoor DC fan fault

49

Outdoor DC fan fault

90

Forced expansion valve

91

IPM Temperature rise too high downtime

92
93

VRF

Compression ratio is too large to stop

VRF TYPES

The machine number and set the


VRF

number of inconsistencies fault

94

outdoor address conflict

VRF

95

Refrigerant serious excessive downtime

VRF

96

Refrigerant shortage downtime

VRF
FOR VRF&inverter

97

unitary types

Four way valve fault

94

7. TROUBLE SHOOTING
The following is the fault code table of indoor.
FAULT
CODE
31

FAULT DISCRIPTION

REMARKS

Panel key ADfault

Only for MUTI-SPLIT

The front panel fault is not in place


32

(two upper and lower position detecting switch and also put in

Only for MUTI-SPLIT

place or not in place)


33
34

Room

Temperature Sensor Fault

Only for MUTI-SPLIT

Coil Temperature Sensor Fault

Only for MUTI-SPLIT

Panel drive fault


35

(two upper and lower panel position detection switch is not in

Only for MUTI-SPLIT

accordance with thereservation timing action)


36

Communication between Indoor and Outdoor

Fault

Only for MUTI-SPLIT

37

humidity sensor failure

Only for MUTI-SPLIT

38

EEprom Data error

Only for MUTI-SPLIT

39

Indoor Fan Motor Fault

Only for MUTI-SPLIT

40

Grid protection

Only for MUTI-SPLIT

51
52

Drainage

Fault

Grid protection
The front panel fault is not in place

53

(two upper and lower position detecting switch and also put in
place or not in place)
ONLY FOR MUTI-SPLIT & VRF

55

Conflict Model Fault

56

Freeze Protection

57

Overload Protection

61

Indoor address duplication

For VRF

62

Remote address duplication

For VRF

64

Communication between Indoor & Outdoor unit Fault

65

Communication between Indoor &Wiring remote controller Fault

71

The indoor zero crossing detection fault

72

Indoor Fan Motor Fault

73

EEPROM Data Error

TYPES

Panel drive fault


74

(two upper and lower panel position detection switch is not in


accordance with there servation timing action)

80

Panel key fault

81

Ambient Temperature Sensor Fault

82

Evaporator Inlet Temperature Sensor Fault

83

Evaporator Middle TemperatureSensor Fault

84

Evaporator outlet Temperature Sensor Fault

85

Wiring Remote Controller Sensor Fault

95

For VRF

7. TROUBLE SHOOTING
86

Outlet temperature sensor fault

87

The water side entrance temperature sensor fault

88

The water side entrance temperature sensor fault

89

Humidity sensor failure

FE

ER

Communication between main control board &Wiring remote controller


Faultdisplay on wiring remote

controller

Communication between main control board &display board Fault


displays on display board

96

8. CHECKING COMPONENTS
8-1. Check refrigerant system
TEST SYSTEM FLOW
Conditions: Compressor is running.
The air condition should be installed in good ventilation.
Tool: Pressure Gauge
Technique: see
feel test
SEE
----- Tube defrost.
FEEL ----- The difference between tubes temperature.
TEST ----- Test pressure.

97

8. CHECKING COMPONENTS
Test system flow
Cooling mode
NO

Test system
pressure.Does the low
pressure normal at
service part ?

The pressure on the


high side.

Recharge refrigerant
after air purging with
the vacuum
pump.Does the low
pressure nomal over
again?

The pressure on the


low side.

The system wants


refrigerant.The service
people must be ration
refrigerant(about 100g/
per)in the cooling
mode fixed
frequency.Is the low
pressure rise ?

If the pressure is
close to static
pressure?

NO

yes
yes

Air remaining at the


refrigerant system.

4-way valve collude or


compressor exhaust very
ebb.

yes

NO

Recharge refrigerant .
The refrigerant system
blocked.Please check
the Capillary Tube( or
electronic expansion
valve)Is it blocked?

NO

yes

Unsolder the capillary tube


ASS'Y(or electronic expansion
valve).The capillary tube1 is blown
by N2 .

Check check valve and 4way valve.

Heating mode

Test system
pressure.Does the
high pressure normal
at service part ?

The pressure on the


high side.

The pressure on the


low side.

NO

The system wants


refrigerant.The service
people must be ration
refrigerant(about 100g/
per)in cooling mode fixed
frequency state .Is the
high pressure rise in
heating mode?

NO

Recharge refrigerant
after air purging with
the vacuum
pump.Does the high
pressure normal over
again?

Remove the back


panel."see"the
capillary tube1 and
capillary tube2.Is it
defrosting?
yes

yes

The capillary tube


blocked.Unsolder the
NO
capillary tube ASS'Y.The
capillary tube1 and capillary
tube2 is blown by N2 .

Air remaining at the


refrigerant system.
yes

NO

Recharge refrigerant
If the pressure is close
to static pressure?

Check heat exchanger and


4-way valve.

yes

4-way valve collude or


compressor exhaust every
ebb.

98

8. CHECKING COMPONENTS
8-2.Check parts unit
1. INDOOR FAN MOTOR

Duct type
18K
YSK110-40-4-A (HS16)

M1:14615%
M2: 3315%
M3: 4315%
A1: 6315%
A2: 2315%
A3: 11915%

99

8. CHECKING COMPONENTS
AUD-24UX4SLH
Y6S419C56

AUD-24UX4SLH1
DC MOTOR
AUD-36UX4SMH1
DC MOTOR

100

8. CHECKING COMPONENTS
AUD-36UX4SMH
Y7S423C024

101

8. CHECKING COMPONENTS
48K,60K

102

8. CHECKING COMPONENTS
Cassette
18k

25

24K,36K,48K,60K
DC-MOTOR

103

8. CHECKING COMPONENTS
Ceiling & Floor type
18K
YSK110-22-4-A

M: 187 A137.5

A227.8

A3146

24K-- DC MOTOR
SIC-70CW-F1100-6
36K-- DC MOTOR
SIC-70CW-F1140-3

48K,60K
Y7S423C032

WHITE-BLACK:42.69
RED-BLACK:36.41

BLACK-BLUE:9.19

BLUE-YELLOW:9.09

104

8. CHECKING COMPONENTS
Test in resistance.
TOOL: Multimeter.
Test the resistance of the main winding. The indoor fan motor is fault if the resistance of
main winding 0(short circuit)oropen circuit.
Test in voltage
TOOL: Multimeter.
Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure
voltage YELLOW and GND on motor. The voltage repeat 0V DC and 5V DC.
Notes:
1) Please dont hold motor by lead wires.
2) Please dont plug IN/OUT the motor connecter while power ON.
3) Please dont drop hurl or dump motor against hard material. Malfunction may not be observed at
early stage after such shock. But it may be found later, this type of mishandling void our
warranty.

105

8. CHECKING COMPONENTS
2. OUTDOOR FAN MOTOR
MOTOR EXAMINE AND REPAIR
Circuit diagram
AUW-18U4SZ1, AUW-24U4SA1&AUW-36U4SA1DC MOTOR
18K-- MOTOR MODEL:ARW4401QH
24K-- MOTOR MODEL:SIC-71FW-D8121-1
36K-- MOTOR MODEL:SIC-71FW-D8121-1
Circuit diagram
AUW-18U4SG
YDK29-6I-22:

Winding
"M"-The Main Winding
"A"-The Auxiliary Winding

BROWN

Capacitor

TP
A1

A2

A3

Hot Protector 130

WHITE
PINK
PURPLE

YELLOW

Winding resistance ( at 20)


M: 283.5
A: 180
AUW-24U4SZ
YDK70-6H-3:
WINDING
BROWN

BLACK
M
A
WHITE

YELLOW

BLUE RED

Winding resistance ( at 20)


M: 78
A: 80
Winding resistance ( at 20)
M: 283.5
A: 180
AUW-36U4SA
YDK95-6-9043

106

" M " The main winding


" A " The auxiliary winding
Capacitor
Hot protector 130

8. CHECKING COMPONENTS
BROWN

YELLOW
WINDING
A
M1

M: Main winding
M2

A: Auxiliary winding

M3

Capacitor
P
P

WHITE

BLACK

BLUE

Winding resistance ( at 20)


M1:59.1
M2:20.3
M3:15.3

Hot protector

RED

A: 85.8

48K,60K
YDK65-6-9024YDK65-6-9061

Winding resistance ( at 20)


M:83.0 A1:23.4
A2:14.0

A3: 63.5

Test in resistance.
TOOL: Multimeter.
Test the resistance of the main winding. The outdoor fan motor is fault if the
main winding 0(short circuit)oropen circuit.
Notes:
1) Please dont hold motor by lead wires.

resistance of

2 Please dont plug IN/OUT the motor connecter while power ON.
3 Please dont drop hurl or dump motor against hard material. Malfunction may not be observed at
early stage after such shock. But it may be found later, this type of mishandling void our
warranty.
107

8. CHECKING COMPONENTS
3. COMPRESSOR
COMPRESSOR EXAMINE AND REPAIR
AUW-18U4SGDA130S1C-20FZ

AUW-18U4SZ1
DA131S1B-28FZ

AUW-24U4SZ

108

8. CHECKING COMPONENTS
AUW-24U4SA1
DA230S2C-31MT

AUW-36U4SA / AUW-36U4SA1
DA250S2C-30MT

AUW-48U6SPTNB306FPNMC

109

8. CHECKING COMPONENTS
AUW-60U6SPLNB42FSAMC

Test in resistance.
TOOL: Multimeter.
Test the resistance of the winding. The compressor is fault if the resistance of winding
0(short circuit)oropen circuit
Familiar error:
1Compressor motor lock.
2Discharge pressure value approaches static pressure value .
3Compressor motor winding abnormality.
Notes
1Dont put a compressor on its side or turn over.
2) Please assembly the compressor in your air conditioner rapidly after removing the plugs.
Dont place the comp. In air for along time.
3Avoiding compressor running in reverse caused by connecting electrical wire incorrectly.
4Warning! In case AC voltage is impressed to compressor, the compressor performance will
below because of its rotor magnetic force decreasing.
110

8. CHECKING COMPONENTS
4. INDUCTANCE
Familiar error:
1Sound abnormality
2Insulation resistance disqualification.
5. STEP MOTOR
5

Test in resistance.
TOOL: Multimeter.
Test the resistance of winding. The stepper motor is fault if the resistance of winding 0(short
circuit)oropen circuit.
6. FUSE
Checking continuity of fuse on PCB ASSY.
1) Remove the PCB ASSY from the electrical component box. Then pull out the fuse from the
PCB ASSY (Fig.1)
Fuse

PCB Ass'Y

Fig.1

2) Check for continuity by a multimeter as shown in Fig.2.

Fuse

Fig.2

7.CAPACITOR
1) Remove the lead wires from the capacitor terminals, and then place a probe on the
capacitor terminals as shown in Fig.3.
2) Observe the deflection of the pointer, setting the resistance measuring range of the
multimeter to the maximum value.
111

8. CHECKING COMPONENTS
*
*

The capacitor is good if the pointer bounces to a great extent and then gradually returns to
its original position.
The range of deflection and deflection time differ according to the capacity of the capacitor.

Multimeter

Compressor motor
capacitor

Fan motor
capacitor