Sie sind auf Seite 1von 17

www.cimon.

com

PLC-S Analog modules


CM3-SP04EAO
CM3-SP04EAA
CM3-SP04EAM

CM3-SP04EOAI
CM3-SP04EOAV

MEMO

Caution
To use this product safely please read the following
instructions
1. The power must be off whenever you are in contact with the product.
2. Read and understand the following technical information about the
product.
3. For your safety only a qualified electrician should work on this product.

General Specifications
Items

PLC-S Analog Output (Specifications)

Specification

Standards

Ambient Temp.

-10C~70C

Storage Temp.

-25C~80C

Ambient Humidity

5~95%RH, (Non-condensing)

Storage Humidity

5~95%RH, (Non-condensing)

Items

SP04EAA

Analog Output point

2 points

Analog Output

Voltage: 0V~+5V, 1V~+5V,


0V~+10V, -10V~+10V
Current : 0~20mA,
4~20mA

0V ~ +10V.
-10V ~ 10V
(switch mode)

4~20mA

Output setting method

Setting by CICON

Switch OFF : 0V~10V


Switch ON :-10~10V
CICON setting

Not possible

Digital Input

14bit, 0~16000
16bit, 0~64000
Setting by CICON

For discontinuous vibration

Vibration

Frequency

Acceleration

Amplitude

10f<57Hz

0.075mm

57f150Hz

9.8m/s2{1G}

Contionuous vibration
Frequency

Acceleration

Amplitude

10f<57Hz

0.035mm

57f150Hz

Shocks

4.9m/s {1G}

Times

X,Y,Z
Each direction,
10 times

IEC 61131-2

IEC 61131-2

Square wave
impulse noise

2,000V

CIMON standard

Electrostatic
discharge

Voltage : 4kV (contact discharging)

IEC 61131-2
IEC 1000-2

Radiated
electromagnetic
field noise

27~500 MHz,10V/m

IEC 61131-2
IEC 1000-4-3

Noise
Fast Transient
Burst noise

Digital I/O
(24V or more)

Power
module

2 kV
Voltage

Digital I/O(less
than 24V)
Analog I/O
Comm. interface

2 kV
2 kV/1min

Accuracy

0.1% (Full Scale)


10ms
12V
24mA

12V

No corrosive gas or dust


Natural air cooling

24mA

Insulation method

Photo Coupler between Input terminal and PLC

Power supply

External DC 24V

I/O occupation
I/O Terminal
Consumption
current
(mA)

16 points
12points Terminal

8points Terminal

Internal

@DC3.3V, 15mA

@DC3.3V, 15mA

@DC3.3V, 15mA

External

@DC24V, 70mA

@DC24V, 60mA

@DC24V, 70mA

IEC 61131-2
IEC 1000-4-4

0.25 kV

Cooling type

14bit, 0~16000

0.5 kV/1min

Ambient
conditions

SP04EOAI
4 points

Conversion velocity
Absolute Max. Output

Max. impact acceleration: 147m/S2(15G)


Authorized time : 11ms
Pulse wave : Sign half-wave pulse (3 times each in X, Y, Z)

SP04EOAV

PLC-S Analog Input (Specifications)


Items
Analog Input point
Analog Input
Resolution

CM3-SP04EAO

CM3-SP04EAA

4 points

2 points

Voltage: 0V~+5V, 1V~+5V, 0V~+10V, -10V~+10V


Current : 0~20mA, 4~20mA
14bit, 0~16000
16bit, 0~64000
Setting by CICON

14bit, 0~16000

Accuracy

0.1%(Full Scale)

Conversion speed
Absolute Max. input

2.1ms / 1ch
Voltage: 12V
Current: 25mA

12V
25mA

Photo-coupler insulation between input terminal and PLC


(No insulation between channels)

Insulation
I/O points occupied

16 points

Power Supply

External DC 24V

Connection Terminal

12 points Terminal Block

Consumption
current (mA)

Inner

@DC3.3V, 15mA

@DC3.3V, 15mA

External

@DC24V, 60mA

@DC24V, 70mA

Features of Analog Module


1) CM3-SP04EAO is Analog Input module which has 4CH voltage/current Input.
CM3-SP04EOAV is Analog Output module which has 4CH voltage output (-10~10V, 0~10V).
CM3-SP04EOAI is Analog Output module which has 4CH current output (4~20mA).
CM3-SP04EAA is Analog Input and Output mixed module which has 2CH voltage/
current input and 2CH voltage/current output.
2) DA conversion module converts digital value, 16bit binary data (data: 14bit) from PLC
CPU, into analog signal (voltage or current output). It converts digital value 0~16000(8000~8000) / 0~64000(-32000~32000) to analog value 0~20mA, 4~20mA,
-10~10V, 0~5V, 0V~10V, 1~5V.
3) AD conversion module converts input Max. and Min value into 0~16000(-8000~8000).
If input value gets out of the range, it converts into -192~16191(8192~8191). If value
gets out of this, -192~16191(-8192~8191) is fixed.
4) There are two AD conversion methods :
1. Average processing 2. Sampling processing
5) Through Hold Clear function, DA module can output offset value (4mA, -10V) when
RUN mode changes to STOP mode or maintain output value being with RUN mode.
6) Channel that converting is prohibited will output the minimum value of each output mode.
(0mA, 4mA, -10V, 0V, 1V)
7) User can set up Offset/Gain value through CICON Ladder Program.

Analog Mux Specifications (SP04EAM)

8) Maximum 11 analog modules can be installed in one slot.


9) Normal status: LED On, Error status: LED blinking by 0.5sec interval.

Items

Standard

Analog Input

4 Channels / 1 Module

Analog Input

Voltage, RTD sensor, TC sensor

Relay
Max/Min ON TIME

Min. 0.1 sec / Max. 1000.0 sec

Insulation Method

Relay

I/O points occupied

16 points

Number of Ports

Input 12ports / Output 3ports

Relay Life Expectancy

Number of Operation of 108

Input / Output Signal


Direction of Signal
(CPU Module)
Input
X00

Direction of Signal
(CPU Module)

Name of Signal

Output

Module ready

Name of Signal

Y10

X01
X02

SP04EAO USER MEMORY

Y11
Flag indicating the
operation condition set up

Y12

Requesting to set up
operation condition

Address
Hexa

Deci

Description

Default

R/W

0H

CH.1 Digital converted value

1H

CH.2 Digital converted value

2H

CH.3 Digital converted value

3H

CH.4 Digital converted value

4H

CH.1 Input signal value

5H

CH.2 Input signal value

6H

CH.3 Input signal value

7H

CH.4 Input signal value

8H

CH.1 Percentage value

9H

CH.2 Percentage value

AH

10

CH.3 Percentage value

BH

11

CH.4 Percentage value

CH

12

CH.1 Input range setting

R/W

X03

Y13

X04

Y14

X05

Y15

DH

13

CH.2 Input range setting

R/W

X06

Y16

EH

14

CH.3 Input range setting

R/W

X07

Y17

FH

15

CH.4 Input range setting

R/W

10H

16

Raw Value Digital Output set

R/W

11H

17

Reserved

12H

18

CH.1 Average processing setting value

2000h

R/W

X08
X09

Y18

Refer to HELP menu


in CICON

Y19

Refer to HELP menu


in CICON

13H

19

CH.2 Average processing setting value

2000h

R/W

X0A

Y1A

14H

20

CH.3 Average processing setting value

2000h

R/W

X0B

Y1B

15H

21

CH.4 Average processing setting value

2000h

R/W

16H

22

CH.1 Max. alarm set value

R/W

X0C

Y1C

17H

23

CH.2 Max. alarm set value

R/W

18H

24

CH.3 Max. alarm set value

R/W

X0D

Y1D

19H

25

CH.4 Max. alarm set value

R/W

X0E

Y1E

1AH

26

CH.1 Min. alarm set value

R/W

1BH

27

CH.2 Min. alarm set value

R/W

1CH

28

CH.3 Min. alarm set value

R/W

1DH

29

CH.4 Min. alarm set value

R/W

1EH

30

Alarm in Max status

1FH

31

Alarm in Min. status

20H

32

CH.1 Digital Filter Constant

30

R/W

21H

33

CH.2 Digital Filter Constant

30

R/W

22H

34

CH.3 Digital Filter Constant

30

R/W

23H

35

CH.4 Digital Filter Constant

30

R/W

24H

36

Calibration Code

R/W

25H

37

Error Code

26H

38

OS Version

X0F

Flag indicating error in


module

Y1F

Requesting to clear error

SP04EAA USER MEMORY


Address
Hexa
0H
1H
2H
3H
4H
5H
6H
7H
8H
9H
AH
BH
CH
DH
EH
FH
10H
11H
12H
13H
14H
15H
16H
17H
18H
19H
1AH
1BH
1CH
1DH
1EH

Deci
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

Description
CH.1 Digital converted value (AD)
CH.2 Digital converted value (AD)
CH.1 Input signal value (AD)
CH.2 Input signal value (AD)
CH.1 Percentage value (AD)
CH.2 Percentage value (AD)
Alarm in Max status (AD)
Alarm in Min. status (AD)
CH.1 Input range setting (AD)
CH.2 Input range setting (AD)
Raw Value Digital output set (AD)
CH.1 Average processing setting value(AD)
CH.2 Average processing setting value (AD)
CH.1 Max. alarm set value (AD)
CH.2 Max. alarm set value (AD)
CH.1 Min. alarm set value (AD)
CH.2 Min. alarm set value (AD)
CH.1 Digital Filter Constant (AD)
CH.2 Digital Filter Constant (AD)
Enable / Disable to D/A convert setup
CH.1 DA Output type (current 2, voltage 4)
CH.2 DA Output type (current 2, voltage 4)
CH.1 DA range of Digital value
CH.2 DA range of Digital value
CH.1 DA Channel Hold / Clear
CH.2 DA Channel Hold / Clear
CH.1 Digital Output value (DA)
CH.2 Digital Output value (DA)
AD / DA Resolution Set
Error Code
OS Version

10

SP04EOAV / SP04EOAI USER MEMORY


Default
0
0
0
2000h
2000h
0
0
0
0
30
30
0
0
0
0
0
0
0
0
0
0
-

R/W
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R

Address
Hexa
00H
01H
02H
03H
04H
05H
06H
07H
08H
09H
0AH
0BH
0CH
0DH
0EH
0FH
10H
11H
12H
13H
14H
15H
16H

Deci
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

17H

23

Description

Default

R/W

Enable/Disable to D/A convert setup


CH.1 Digital Output value
CH.2 Digital Output value
CH.3 Digital Output value
CH.4 Digital Output value
CH.1 Range of Digital value
CH.2 Range of Digital value
CH.3 Range of Digital value
CH.4 Range of Digital value
CH.1 Channel Hold / Clear
CH.2 Channel Hold / Clear
CH.3 Channel Hold / Clear
CH.4 Channel Hold / Clear
CH.1 Range of Voltage output setup
CH.2 Range of Voltage output setup
CH.3 Range of Voltage output setup
CH.4 Range of Voltage output setup
CH.1 Status
CH.2 Status
CH.3 Status
CH.4 Status
Error Code
OS Version
DA Output Enable
(Same Function to I/O Y Signal)

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R

R/W

11

Features of SP04EAM
Analog Mux module receives analog values from 4 channels and outputs the same
values to one port at a time.
1)

Desired channels can be selected to be enabled or disabled and get operation


status.

2)

Different relay ON time can be set by each channel from 0.1 to 1000.0 seconds
range.

3)

Relay count values can be checked for life expectancy for the relay.

4)

Easy control with Auto/Manual mode.

5)

Power LED blinks by 0.5 second interval when theres an error with CPU
communication.

6)

It is not suitable for current signal use since this module switches analog signals
repeatedly.

Input / Output Signal of SP04EAM


Flag Direction (CPU MUX Module)

Flag Direction (CPU MUX Module)

Input

Flag

Output

X20

MUX Channel Change Completed

Y20

Flag

X21

Settings Save Completed

Y21

Mux Channel Change Request

X22

1CH Relay Open Predict

Y22

Settings Save Request

X23

2CH Relay Open Predict

Y23

1CH stoppage Request

X24

3CH Relay Open Predict

Y24

2CH stoppage Request

X25

4CH Relay Open Predict

Y25

3CH stoppage Request

X26

1CH Relay Activate

Y26

4CH stoppage Request

X27

2CH Relay Activate

Y27

X28

3CH Relay Activate

Y28

X29

4CH Relay Activate

Y29

X2A

1CH Relay Count Reset Completed

Y2A

X2B

2CH Relay Count Reset Completed

Y2B

1CH Relay Count Reset Request

X2C

3CH Relay Count Reset Completed

Y2C

2CH Relay Count Reset Request

X2D

4CH Relay Count Reset Completed

Y2D

3CH Relay Count Reset Request

X2E

Module Error

Y2E

4CH Relay Count Reset Request

X2F

MUX Channel Change Completed

Y2F

Error Clear Request

** Note that I/O flags shown above are applied when the MUX module is installed in the first slot

12

13

Wiring Method

SP04EAM USER MEMORY


Address
Hex.

Dec.

0H

Contents

R/W

MUX Channel Enable / Disable

R/W

1H

CH.1 Relay Count High

2H

CH.1 Relay Count Low

3H

CH.2 Relay Count High

4H

CH.2 Relay Count Low

5H

CH.3 Relay Count High

6H

CH.3 Relay Count Low

7H

8H

CM3-SP04EAO
Voltage Input
Channel

+ Terminal

- Terminal

CH 1

Terminal 1

Terminal 3

CH 2

Terminal 4

Terminal 6

CH 3

Terminal 7

Terminal 9

CH 4

Terminal 10

Terminal 12

24V Extenrnal

Connection : bottom of module

Current Input
Channel

+ Terminal

- Terminal

Connection

CH 1

Terminal 1

Terminal 3

Connect 1-2

CH 2

Terminal 4

Terminal 6

Connect 4-5

CH.4 Relay Count High

CH 3

Terminal 7

Terminal 9

Connect 7-8

CH 4

Terminal 10

Terminal 12

Connect 10-11

CH.4 Relay Count Low

9H

Auto/Manual Mode

R/W

AH

10

Operation Status

BH

11

CH.1 ON time setting value

R/W

CH

12

CH.2 ON time setting value

R/W

DH

13

CH.3 ON time setting value

R/W

EH

14

CH.4 ON time setting value

R/W

FH

15

Error Code

10H

16

11H

17

12H

18

13H
14H

24V Extenrnal

Connection : bottom of module

CM3-SP04EAA
Voltage Input / Output
Channel

+ Terminal

- Terminal

AD Ch 1

Terminal 1

Terminal 3

AD Ch 2

Terminal 4

Terminal 6

DA Ch 1

Terminal 7

Terminal 9

DA Ch 2

Terminal 10

Terminal 12

24V Extenrnal

Connection : bottom of module

Current Input / Output


Channel

+ Terminal

- Terminal

Connection

AD Ch 1

Terminal 1

Terminal 3

Connect 1-2

AD Ch 2

Terminal 4

Terminal 6

Connect 4-5

DA Ch 1

Terminal 8

Terminal 9

19

DA Ch 2

Terminal 11

20

24V Extenrnal

OS Version

14

Terminal 12
Connection : bottom of module

15

Wiring Method

Input Wiring

CM3-SP04EOAV, CM3-SP04EOAI

SP04EAO Voltage Input

Channel

+ Terminal

- Terminal

CH 1

Terminal 1

Terminal 2

CH 2

Terminal 3

Terminal 4

CH 3

Terminal 5

Terminal 6

CH 4

Terminal 7

Terminal 8

24V Extenrnal

SP04EAO Current Input

Connection : bottom of module

Prior to wiring Analog Input to Terminal, double check terminal (+) and ()
CM3-SP04EAM
Channel

+ Terminal

- Terminal

CH 1

Terminal 1

Terminal 3

CH 2

Terminal 4

Terminal 6

CH 3

Terminal 7

Terminal 9

CH 4

Terminal 10

Terminal 12

16

17

Input Wiring
SP04EAA Voltage Input

SP04EAA Current Input

18

Output Wiring
SP04EOAI Voltage Output

SP04EOAI Current Output

19

Output Wiring
SP04EAA Voltage Output

SP04EAM Wiring

SP04EAA Current Output

Analog Input

A1+
A1-

MUXING

CH1

COM1
A2+
A2-

Bottom Terminal
CH2
A1+

COM2

A3+
A3-

A1-

COM
CH3

Analog Output

COM3
A4+
A4-

CH4

COM4

20

21

SP04EAM Wiring Example


Analog Output

A1+
A1-

Dimension

Analog Input

All analog modules are the same size.

TC sensor

COM

22

23

Unit : mm

Dimension

24

Revision History
Version

Date

V1.0

2014-02-25

New Revision

Content

V1.1

2015-01-26

SP04EAM added

1 - 28

V1.2

2015-05-27

SP04EAM Wiring /
SP04EAM Wiring Example

21 - 22

V1.3

2015-10-27

Wiring Method

15

25

Page

Product Warranty

Product Warranty
January 2014

All Cimon products including hardware, software, and firmware (collectively called
Products) carry a one-year warranty against defects in materials and workmanship
beginning from the date of product receipt from seller or its appointed distributor. If a
product proves defective in materials and workmanship within one year from the date
of purchase, we will replace or repair it. Products returned under warranty after
30 days may be replaced with refurbished or remanufactured goods at Cimons
discretion. Cimon makes no representation or warranty, express or implied,
that the operation of the Products will be uninterrupted or error free, or that the
functions contained therein will meet or satisfy buyers intended use or requirements.
Repaired or replaced Products provided as a result of this warranty are
warranted for a period of six (6) months from the shipment to buyer or the
remainder of the original warranty term for that particular product, whichever
is longer. Cimons standard policy is that all customers are responsible for freight
charges to Cimon when returning products under the warranty return policy.
This warranty will be void if Products date codes or serial numbers are removed or
defaced. Warranties do not apply to products that have been subjected to abnormal
use, abnormal conditions, improper storage, exposure to moisture or dampness,
unauthorized modifications, unauthorized repair, misuse, neglect, accident, alteration,
improper installation or other acts which are not the fault of Cimon, including damage
caused in shipping. Our warranty also does not apply to any product that has
been damaged by external causes such as fire, flood, sand, dirt, lightning, acts of
God, battery leakage, theft, blown fuses, improper use of any electrical source or
connection to product not recommended in writing for interconnection by Cimon.
In no event will Cimon be liable, whether in contract, tort or under any other legal
theory, for lost profits or revenues, loss of use or similar economic loss, for any
indirect, special, incidental, consequential, punitive or similar damages arising out
of or in connection with any products including non-conforming products, or for any
third party claims against you relating to the products, even if we have been advised of
the possibility of such claim. In no event will our monetary liability in respect of any
product exceed the purchase price that you paid for it.

26

To minimize the risk of potential safety problems, you should follow all applicable
local and national codes that regulate the installation and operation of your
equipment. These codes vary from area to are and usually change with time. It is your
responsibility to determine which codes should be followed, and to verify that the
equipment, installation and operation is in compliance with the latest revision of these
codes.
CIMON SOFTWARE AND HARDWARE (COLLECTIVELY REFFERED TO AS,
PRODUCTS) LICENSE DISCLAIMER AND LIMITATION OF WARRANTIES
YOUR USE OF ANY CIMON PRODUCTS AND CONTENT ACCESSIBLE THROUGH
THE PRODUCTS IS ENTIRELY AT YOUR OWN RISK. EXCEPT AS DESCRIBED IN THIS
AGREEMENT, THE PRODUCTS ARE PROVIDED "AS IS." TO THE MAXIMUM EXTENT
PERMITTED BY APPLICABLE LAW, CIMON, ITS AFFILIATES, AND ITS THIRD PARTY
SERVICE OR DATA PROVIDERS, LICENSORS, DISTRIBUTORS OR SUPPLIERS
(COLLECTIVELY REFERRED TO AS, "SUPPLIERS") DISCLAIM ALL WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY THAT THE PRODUCTS ARE
FIT FOR A PARTICULAR PURPOSE, TITLE, MERCHANTABILITY, DATA LOSS, NONINTERFERENCE WITH OR NON-INFRINGEMENT OF ANY INTELLECTUAL PROPERTY
RIGHTS, OR THE ACCURACY, RELIABILITY, QUALITY OR CONTENT IN OR LINKED TO
THE PRODUCTS.
CIMON AND ITS AFFILIATES AND SUPPLIERS DO NOT WARRANT THAT THE
PRODUCTS ARE SECURE, FREE FROM BUGS, VIRUSES, INTERRUPTION, ERRORS,
THEFT OR DESTRUCTION. FURTHER, CIMON DOES NOT WARRANT ACCESS TO
THE INTERNET OR TO ANY OTHER SERVICE, CONTENT OR DATA TRANSMITTED
THROUGH THE PRODUCTS. IF THE EXCLUSIONS FOR IMPLIED WARRANTIES DO
NOT APPLY TO YOU, ANY IMPLIED WARRANTIES ARE LIMITED TO 60 DAYS FROM
THE DATE OF PURCHASE OR DELIVERY OF THE PRODUCTS, WHICHEVER IS
SOONER.

EQUIPMENT DAMAGE OR SERIOUS INJURY TO PERSONNEL INCLUDING DEATH


CAN RESULT FROM THE FAILURE TO FOLLOW ALL APPLICABLE CODES AND
STANDARDS INCLUDING ENGINEERING STANDARDS. CIMON DOES NOT
ASSUME ANY RESPONSIBILITY FOR YOUR PRODUCT DESIGN, INSTALLATION OR
OPERATION.

27

Product Warranty

MEMO

CIMON LTD AND ITS AFFILIATES AND SUPPLIERS DISCLAIM ANY REPRESENTATIONS OR WARRANTIES THAT YOUR USE OF THE PRODUCTS WILL
SATISFY OR ENSURE COMPLIANCE WITH ANY LEGAL OBLIGATIONS OR LAWS OR
REGULATIONS.
LIMITATION OF LIABILITY AND INDEMNITY. TO THE MAXIMUM EXTENT PERMITTED
BY APPLICABLE LAW, THE ENTIRE LIABILITY OF CIMON, AND ITS AFFILIATES
AND SUPPLIERS FOR ALL MATTERS OR CLAIMS RELATING TO THIS AGREEMENT
SHALL BE LIMITED TO THE AMOUNT YOU PAID FOR THE PRODUCTS DURING THE
TWELVE (12) MONTHS PRIOR TO SUCH CLAIM.
THE STATUTE OF LIMITATIONS FOR FILING A CLAIM SHALL BE LIMITED TO THE
SHORTER OF TWELVE MONTHS, OR THE SHORTEST PERIOD ALLOWED UNDER
APPLICABLE LAW.
SUBJECT TO APPLICABLE LAW, CIMON AND ITS AFFILIATES AND SUPPLIERS ARE
NOT LIABLE FOR ANY OF THE FOLLOWING: (A) INDIRECT, SPECIAL, INCIDENTAL,
PUNITIVE OR CONSEQUENTIAL DAMAGES; (B) DAMAGES RELATING TO FAILURES
OF TELECOMMUNICATIONS, THE INTERNET, ELECTRONIC COMMUNICATIONS,
CORRUPTION, SECURITY, LOSS OR THEFT OF DATA, VIRUSES, SPYWARE, LOSS
OF BUSINESS, REVENUE, PROFITS OR INVESTMENT, OR USE OF SOFTWARE
OR HARDWARE THAT DOES NOT MEET CIMON SYSTEM REQUIREMENTS. THE
ABOVE LIMITATIONS APPLY EVEN IF CIMON AND ITS AFFILIATES AND SUPPLIERS
HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES AND/OR THE
POSSIBILITY OF DAMAGES GREATER THAN THE LIMITATION ABOVE. THIS
AGREEMENT SETS FORTH THE ENTIRE LIABILITY OF CIMON, ITS AFFILIATES AND
YOUR EXCLUSIVE REMEDY WITH RESPECT TO THE SOFTWARE AND ITS USE.
THE PARTIES FURTHER AGREE THAT THE APPLICABLE LAW AND VENUE FOR
ANY DISPUTED ARE THE LAWS OF CALIFORNIA. TO THE EXTENT ALLOWED BY
APPLICABLE LAW, ANY CLAIMS SHALL BE BROUGHT IN LOS ANGELES CALIFORNIA
AND CALIFORNIA LAW SHALL APPLY. THE CALIFORNIA VERSION OF THE UCC IS
THE PREFERRED LAW TO BE APPLIED TO ANY WARRANT AND RELATED CLAIMS.

28

29

MEMO

MEMO

30

31

CIMON CO.,LTD.
H.Q Address : 5F KDT B/D, #48, Beolmal-ro, Bundang-gu,Seongnam-si, GyeongGi-do, Korea
463-836
Tel : +82-31-778-3071
Homepage : www.cimon.com
USA : 3699 Wilshire Blvd suite 1250 Los Angeles CA90010
Tel : 213 384-8703
Homepage : www.cimon.com

Version:1.3
Revision Date : Oct, 2015
Printed : May, 2015
BCP18044

Das könnte Ihnen auch gefallen