Beruflich Dokumente
Kultur Dokumente
Tipton
IEEE Transactions on Industry and General Applications
September/October 1965
E-1
E-2
E-3
Corresponding currents in the secondary neutral circulate in the broken delta and through the resistor. This method is equivalent to losing
On systems involving bare overhead lines on
the delta and grounding the primary neutral through a high resistance.
poles, tracing the signal is simple because all the fault
Figure 2 presents the actual voltage conditions, both normally and
current is forced to return through ground. On syswith a ground fault on the system. A typical 2400-volt power system
tems involving conduit, tracing the signal is harder
of around 5000 kVA may require 3 amperes, as shown, at the point of
because the fault current tends to return through the
fault. This would produce 1 ampere in each primary and, if the transconduit of the circuit involved. To the extent that this
former ratio is 20 to 1, a current of 20 amperes through the resistor at
happens, the return current in the conduit cancels out
208 volts. This allows using a low-voltage resistor and pulsing contactor.
the fault current flowing out through the conductor to
With no ground fault on the system, the voltage at the broken delta
the point of fault. Fortunately, even on all conduit
is zero. When a ground fault occurs, this voltage increases to a maxisystems, this cancelling effect is not 100 percent. If
mum of 208 volts, so that the voltage relay VR can give the alarm.
the hook-on ammeter is sensitive enough and if it is
For the typical system shown, this is equivalent to grounding the
insensitive to other local magnetic effects, the fault
system neutral through a 460-ohm resistor. The voltage conditions
can be located. The return current divides into strange
shown are for a solid ground fault but, even for a high-resistance fault,
unpredictable patterns and appears on conduits and
enough voltage will appear across the resistor to operate the voltage
metal structures not associated with the faulty circuit.
relay and sound an alarm. For example, if the entire ground-fault path
Also, these structures very often carry current attribintroduced 1000 ohms of resistance, the voltage across the resistor
utable to other causes not associated with the fault. In
would be around 55 volts. Relay VR can be set to pick up at approxiany case, the definite rhythmic pulse of the
mately 16 volts, which would actually detect and give the alarm, even
ground-fault current is extremely helpful.
if the incipient ground fault had a resistance of approximate 4000 ohms.
The signal receiver which has been found most
useful in tracing the pulsing ground-fault current is
the hook-on ammeter shown in Figs. 3 and 4. This
The operator then initiates a control circuit which causes the pulsdevice has a split core with a window large enough to
ing contactor to close approximately 40 times per minute to produce
encircle a 5-inch conduit. The handle is insulated from
current pulses of about a half-second duration. These pulses can be
the core so that it can be used safely on power cables
traced to the point of fault, with the use of a hook-on ammeter, as
of 2400- or 4160-volt systems which are not in conshown.
Locating the Fault
E-4
E-5
ondary resistor.
At another location, the same scheme has been used except that a spare breaker in a switchgear line-up was substituted for the fused oil switch. This is a superior method but,
of course, the breaker costs more than the fused switch.
A total of five such installations are set on a resistor tap to
produce approximately 2.7 amperes into a ground fault, with
pulsation to 3.5 amperes while hunting for the fault. The pulsing current will probably be increased to make ground-fault
tracing easier.
A more compact single-enclosure construction is shown
in Figs. 6 and 7. This installation is on a 4160-volt system
involving steam turbine-generators having a total capacity of
15 000-kVA and two 10 000-kVA transformer sources. The
fused disconnect switch and three dry-type grounding transformers are mounted in the left-hand high-voltage section
which is padlocked closed. The low-voltage resistor, relays
and controls are all mounted in the right-hand section and are
readily accessible. Louvres are provided to ventilate the resistor, which must dissipate approximately 15kW when a solid
ground fault occurs on the system. Normally, the resistor carries no current. This 4160-volt system was found to have a
charging current of approximately 6.4 amperes with a total
load of 20 000-kVA. The resistor is set on the tap to produce
6.5 amperes into a ground fault. Pulsing to 9.0 amperes is
utilized when hunting for the fault.
Similar single-enclosure equipment is presented in Figs.
8 and 9. This installation also involves 15 000-kVA of steam
turbine-generation but, in this case, the neutral of each gen-
erator was readily available through three single-pole disconnects. Therefore, the grounding transformer had only to
be a single-phase unit shown at the lower right. Both the
transformer and resistor sections of this equipment meat have
bolted covers. This 2400-volt system was found to have 3.6
amperes charging current with a 13 000-kVA load. The resistor was set to produce 4.5 amperes into a ground fault,
with pulsation to 8.0 amperes while tracking the signal to
locate the fault.
Operating Experience At Richmond Refinery
A pulsing ground-fault detector was installed on the
2400-volt system at the Standard Oil Refinery, Richmond,
Calif., in December 1963. Its primary function was to limit
the transient overvoltages, during a line-to-ground fault on
the system. Its secondary function was to impress a pulse on
the fault current so that a portable signal detector could be
used to trace the pulse to the grounded conductor.
The 2.4-kV system consists of three turbine-driven generators rated at 5000-kVA each, connected through reactors
E-6
E-7
E-8
E-9