Beruflich Dokumente
Kultur Dokumente
Ventilation air
intake
Ventilation
air exhaust
Exhaust
Silencer
-13.8 KV switchgear
-CO2 fire system
-480 VAC MCCC for turbine
accessories
-120VDC battery systems
-Allen Bradley TT4000
Monitor/control
Neutral
Grounding
Resistor
Parts
Service
Overhauls
Upgrades
Retrofits
turbine engine
Speed Reduciton from
13,800RPM to 1800 RPM
Ideal or Alstom
Sleeve Bearings with pressure fed sumps
Six-lead WYE connection
Form wound stator windings
Permanent magnet pilot exciter
12,470 13,800 Volt, 3 phase, 60 Hz.
11kV, 3 phase, 50 Hz.
Insulation class F with
Voltage Regulator Characteristics
Solid state, Single-phase sensing
0.5% steady state voltage regulation
Reactive load sharing to within 5% nameplate rating
Crosscurrent compensation capability
NATURAL GAS
o
maximum flow demand rate of 1200 scfm
o
250 psig minimum and 300 psig maximum
Distillate Liquid Fuels
o
maximum flow demand rate of 8.0 gpm.
o
20ft. Suction minimum to 25 psig maximum
Diesel #2
Diesel #2
Natural Gas
Table 1. Dual Fuel Performance Data ISO*, XQ5200 Mobile Power Unit
English
Metric
English
Metric
Power Output
5,200 kWe
5,200 kWe
5,089 kWe
5,089 kWe
Heat Rate
11,263 Btu/kWe-hr
11,900 kJ/kWe-hr
11,376 Btu/kWe-hr
12,002 kJ/kWe-hr
58.6
61.8
57.9
mmBTU/hr
61.
mmkJ/hr
Emissions, NOX
48
25
96
PPMvd
96
PPMvd
CO
50
50
PPMvd
50
PPMvd
Gen. Voltage
12.47 or 13.8 KV
12.47 or 13.8 KV
12.47 or 13.8 KV
12.47 or 13.8 KV
Gen. Frequency
60
60
60
60
0.5%
0.5%
0.5%
0.5%
Short Circuit
mmBTU/hr
PPMvd
PPMvd (1.1 lb.)/MW-hr)
PPMvd
Hz.
48
25
50
mmkJ/hr
PPMvd
PPMvd
PPMvd
Hz.
Hz.
Hz.
Taurus
TM
Shipped Loose
Step deck or 12.2M (40 ft.) High
Cube
8.2MT (18,000 lbs.)
Markham Ontario, 98 MW
Ventilation air
intake
Ventilation
air exhaust
Exhaust
Silencer
-13.8 KV switchgear
-CO2 fire system
-480 VAC MCCC for turbine
accessories
-120VDC battery systems
-Allen Bradley TT4000
Monitor/control
Neutral
Grounding
Resistor
Ease of Placement
Low Profile
7.3M (24 ft.) Stack Height
Rapid Installation
Rapid Installation
Rapid Installation
Rapid Installation
Ease of Use
Metal-Clad
15Kv
Switchgear
400 or 480
Volt Motor
Control
Center
Turbine &
Switchgear
Battery
Systems
Beckwith
Programmable
Protective
Relay Module
Generator
Voltage:
11,000 or
13,800 Class F
Insulation/
Class F
Temperature
Rise
Gas Supply
(240-300 psig) 1725- 2068 KPAG Gas Supply
Grounding to Grid
480VAC, 400A Black Start