Socket detailing
WHITE BOOK supplement
Socket detailing
Internal partition system socket detailing
Victoria Mill,
2
Draycott
60
mins
120
Key facts
Pad.
Plasterboard baffle
Plasterboard
baffle
OR
detailing
GypWall RAPID Socket
and RAPID
dB Plus
Socket detailing
Hilti CP617
Putty Pad
Applications
Suitable for any partition systems where maintence of acoustic and fire integrity are essential.
Sector
Office / commercial
Education
Housing
Healthcare
3
3
www.british-gypsum.com
Socket detailing
System components
Gyproc board products
Gyproc SoundBloc
Thickness
Width
15mm
1200mm
15mm
1200mm
ECSURE
RR
LIFETIM
ANTY
SP
SY
STEM W
Always use genuine branded British Gypsum components to qualify for SpecSure lifetime warranty
Installation overview
Plasterboard baffle - backing method
Holes in plasterboard linings for socket boxes should always be
neatly cut and Gyproc Sealant should be applied where optimum
acoustic performance and / or minimum air leakage is required. In
fire-rated walls, the fire-stopping design is dependent on the
period of fire resistance required. The depth of plasterboard baffle
should be approximately 150mm. Whilst the following example
details relate to 60 and 90 minute fire-resistant specifications, the
principle of the details can generally be adopted for 120 minute
specifications.
Sacrificial linings
The Robust Details pattern book also offers the alternative of a
sacrificial lining in front of a separating wall to create a zone for
service installation. These service zones remove the need for service
penetration of the actual Robust Detail separating wall
construction, which in turn removes the risk of a loss in acoustic
performance as a result of service penetrations.
Socket detailing
For full installation details, refer to the British Gypsum SITE BOOK, available to download from www.british-gypsum.com
5
www.british-gypsum.com
Socket detailing
Design
Performance
Fire resistance and sound insulation
The plasterboard baffle backing is a traditional method that is
recognised to maintain both fire resistance and sound insulation
performance. Tests have been carried out and the Robust Details
manual approves this method.
Fire and acoustic tests have been carried out on British Gypsum
GypWall metal stud partitions drylined with Gyproc plasterboard
incorporating sockets lined with Hilti CP617 Putty Pads. The tests
indicate that Hilti CP617 Putty Pads have the potential to maintain
both the fire and acoustic performance of a perforated partition
when tested under UKAS laboratory conditions, in comparison to
an imperforate partition of the same specification.
Construction details
1 Electrical socket box with plasterboard baffle in
GypWall STAGGERED
GypWall QUIET SF
1
5
2
6
3
Socket detailing
8
9
8
9
10
10
11
11
12
12
8
9
10
11
12
7
6
8
9
10
11
12
1
2
3
4
5
6
7
Gyproc plasterboard
Gypframe C Stud
Gypframe I Stud
Gypframe Spacer Clip
Gypframe RB1 Resilient Bar
Isover insulation
Gypframe 99 FC 50 Fixing Channel
www.british-gypsum.com
Socket detailing
Construction details
5 Electrical socket box with putty pad in GypWall STAGGERED
5
2
8
9
1
2
7
6
8
9
1
2
3
4
5
Gyproc plasterboard
Gypframe C Stud
Gypframe I Stud
Gypframe Spacer Clip
Gypframe RB1 Resilient Bar
6 Isover insulation
7 Gypframe 99 FC 50 Fixing Channel
8 Hilti CP617 Putty Pad fitted inside or outside socket box in accordance
with manfacturers instructions
9 Electrical socket box with metal or plastic back
Construction details
9 Electrical socket box in sacrificial lining to GypWall QUIET
4
5
Socket detailing
9
6
7
10
10
11
11
1
2
3
4
5
6
Gyproc plasterboard
Gypframe C Stud
Gypframe I Stud
Gypframe 99 FC 50 Fixing Channel
Isover insulation
GypLyner UNIVERSAL with minimum 70mm cavity
7
8
9
10
11