Beruflich Dokumente
Kultur Dokumente
iii.
three-story frame is higher than the nine-story frame by 36% in zone V and 49% in
zone I.
Interior frames have 17% (zone V) to 47% (zone I) higher overstrength as compared to
the exterior frames of the same building. This is because interior frames have higher steel
iv.
Samar et al. (1997) performed a seismic nonlinear time-history analysis on four, six and eight
storey reinforced concrete buildings to evaluate the seismic ductility reduction and overstrength
factors. For comparison purpose they kept the same floor plan for all three buildings and also the
member sizes in all three buildings were kept the same in order to have the same lateral stiffness
which is based on gross moment of inertia.
i.
The dependency of overstrength is most significant on seismic zone and then on number
of stories. The overstrength of buildings in lower seismic zones is significantly higher
ii.
iii.
iv.
Andrew Whittaker et al. (1999) presented a draft formulation that represents the response
modification factor as the product of factors related to reserve strength, ductility, and
redundancy(see in Fig.1.1). Pertinent data from various analytical and experimental studies on
reserve strength and ductility are also presented.
i.
Evaluations of studies by others clearly show that the reserve strength of code-compliant
buildings varies widely as a function of building type, building height, and seismic zone.
ii.
iii.
2
3
4
0.71
0.86
1.00
Apurba mondal et al. (2013) focused on estimation of actual values of R factor for realistic RC
moment frame buildings designed and detailed following the Indian standards and compared
these values with the value suggested in the design code. They used pushover analysis in
determining R factor for regular RC framed building structures, by considering different
acceptable performance limit states. The values of R obtained for four realistic designs at two
performance levels by considering the following effects.
i.
ii.
iii.
Performance level1 refers to limits based on both inter storey drift ratio and member rotation
capacity given by ATC-40 (see Table 1.2).
Table 1.2 Deformation Limits for Different Performance Levels-ATC-40
Performance Level
4
Interstorey Drift
Immediate
Damage
Life
Structural
Occupancy
0.01
Control
0.01-0.02
Safety
0.02
Stability
0.33 Vi/Pi
Performance level2 refers to limits based on member rotation limits based on section dimensions
and actual reinforcements given by ATC-40 (see Table 1.3).
Table 1.3 Plastic Rotation Limits for RC Beams Controlled by Flexure-ATC-40
Immediate
Life
Structural
Occupanc
Safety
Stability
bd
0
0
Transverse
Reinforcemen
t
C
C
V
bw bd f ,c
3
6
0.020
0.010
0.025
0.020
By considering above effects in the non linear analysis, they arrived at following conclusions.
i.
Based on Performance Limit 1, the Indian standard over-estimates the R factor, which
ii.
iii.
iv.
terms of R.
R (for PL1) comes to be close to the IS 1893 recommended value If PD effects are not
considered. So, R= 5.0 may be safe for a design where PD effects are actually negligible
v.
Ferraioli et al. (2012) reviewed the existing methods for determining the behaviour factor of
multi-storey moment-resisting steel frames. The effects of storeys, spans and regularity in
elevation of frames on the behaviour factor were considered.
The conclusions of this study are following.
i.
The mean value of the redundancy factor is R=1.64 for both regular and irregular
moment resisting frames which is greater than the value R=1.3 recommended by EC8
ii.
iii.
axial force reduces the plastic moment capacity of the first-story columns.
On the basis of these results, a local ductility criterion based on a limit of the axial force
ratio is proposed to control the ductility of columns and so ensure that the recommended
behaviour factor is conservative.
Vishva et al. (2015) considered a RC framed staging elevated water tank to evaluate the
response reduction factor with and without considering the effects of flexibility of soil. Three
different types of soil conditions representatives of hard soil, medium soil and soft soil has
considered in their study. A conservative structural design method neglects the soil flexibility and
its effects on super structural response. To neglect the effects of soil flexibility is practical for
light structures in comparatively stiff soil to soft soil such as low rise buildings and simple rigid
retaining walls. The effect of soil flexibility becomes noticeable for heavy structures like power
plants, high-rise buildings and elevated water tanks resting on relatively soft soil. The soil
flexibility can be modeled as by providing translation, rocking and torsional elastic springs
constant instead of rigidity of supports so as by providing soil properties in the model (FEMA
356).
The conclusions of this study are following.
i.
The response reduction factor decreases while time period increases from fixed base to
soft base. So it can be observed that avoidance of effect of soil flexibility might lead to
ii.
iii.
EN (1998-1)-2004
EN (1998-1)-2004 seismic design procedure is a single level design procedure that reduces
elastic spectral demands to the strength design level through the use of behavior factor q. This
behaviour factor varies as a function of ductility, building strength, structural system and
stiffness regularity. The behaviour factor q (see in Table 1.4) shall be derived by equation 1.1.
q=
q0k w
1.5
----- (1.1)
kw
q0
systems with walls. For buildings which are not regular in elevation, the value of
q0
shall be
reduced by 20%. The factors u and 1 may be obtained from a nonlinear static (pushover)
global analysis. When the multiplication factor u/1 has not been evaluated through an explicit
calculation, for buildings which are regular in plan the approximate values of u/1 given in
Table 1.5 may be used. For buildings irregular in plan, default value equal to average of default
value of buildings regular in plan and one.
q0
DCM
DCH
u
3.0 /
u
4.5 /
3.0
u
4.0 /
1
1.5
/ 1
u
/ 1
One-Storey Buildings
1.1
1.2
1.3
IS 1893-(Part 1-2002)
IS 1893-(Part 1-2002) seismic design procedure in is a single level design procedure that
reduces elastic spectral demands to the allowable strength design level through the use of
Response modification factor (see in Table 1.6). No reduction in the response reduction factor on
account of any irregularity (vertical or plan-irregularity) in the framing system.
Table 1.6 Values of R for RCC Framed Structures
Structural System
BSLJ-2004
BSLJ-2004 seismic design of Japanese buildings is a two-phase design for
earthquakes. The first phase design is for medium earthquake motions, and
this is basically working stress design. The unreduced seismic forces are
evaluated by following equation 1.2 and 1.3.
n
Q i=C i W i
i=1
----- (1.2)
Ci
Rt Ai C0
=Z
----- (1.3)
C0 =0.2 (for moderate earthquake)
The second phase design is intended to give protection to buildings in case
of severe ground shaking. It requires the checking of several aspects of the
building. These include story drift, vertical stiffness distribution, horizontal
eccentricity and ultimate lateral load carrying capacity. The ultimate lateral load
carrying capacity is calculated by any method, including incremental nonlinear analysis. It is
required that the ultimate lateral load carrying capacity in each story thus found must exceed the
required shear force Qun given by equation 1.4.
Qun=D F
s
es
----- (1.4)
Qud
Qud
reduction factor using in IS code which takes into account inelastic deformations and energy
dissipation (see in Table 1.7). The shape factor (Fes) is intended to take into account their
regularity of the structure expressed in terms of basic shape factors F s and
equation 1.5.
Fe
determined by
Fs
Fe
Fs Fe
-----
(1.5)
Very ductile or
with
Most Ductile
Very Ductile
Ductile
Others
0.3
with
0.30
0.35
0.40
0.45
0.35
0.40
0.45
0.50
0.7
0.7
or less ductile shear wall
0.40
0.45
0.50
0.55
ASCE7-2010
ASCE7-2010 seismic design procedure is a single level design procedure that reduces elastic
spectral demands to the strength design level through the use of response modification factor (R).
This response modification factor varies as a function of ductility, building strength, structural
system and this R values given along with over strength factor and deflection amplification
factors. The seismic acceleration coefficient (
Cs
equation 1.6.
10
C s=
S DS
R
I
------ (1.6)
The Response modification coefficient (see in Table 1.8) reduces forces to a strength level, not
an allowable stress level. For structures having a horizontal structural irregularity and vertical
structural irregularity, the design forces shall be increased 25 percent for the elements of the
seismic force-resisting system. In American code two types of load combinations is given, one
load combination with redundancy factor and second one with overstrength factor.
Table 1.8 R,
Type of System
0C d
R Factor
0 Factor
Cd
Factor
Special Moment
Frames
Intermediate
Moment Frames
Ordinary Moment
Frames
The load combination given in equation 1.7 and 1.8 is used for design of in normal elements of
structure. The value of redundancy factor is either 1.0 or 1.3. This factor has an effect of
reducing the R factor for less redundant structures, thereby increasing the seismic demand.
(1.2 + 0.2SDS)D + QE + L + 0.2S
---- (1.7)
---- (1.8)
Few elements of properly detailed structures are not capable of safely resisting ground-shaking
11
demands through inelastic behavior. To ensure safety, these elements must be designed with
sufficient with overstrength (o) as mentioned in equation 1.9 and 1.10 to remain elastic.
(1.2 + 0.2SDS)D + oQE + L + 0.2S
---- (1.9)
---- (1.10)
NZS4203-1992
NZS4203-1992 design code, the seismic acceleration
Cb
Response spectrum by taking into consideration the fundamental oscillation period (T), the
structural ductility factor () (see in Table 1.9), and the soil type.
1.25
Frames
Walls
3
3
Ductile Structures
1
2
6
5
1.3 Summary
From the review of literature, it was found that three factors (
Rs
, R and
RR
) affect the
actual value of response reduction factor (R) and therefore they must be taken into consideration
while determining the appropriate response reduction factor to be used during the seismic design
12
process and also found that the response reduction factor is significantly affected following
factors
Indian code does not explicitly segregate the components of R in terms of ductility and
overstrength. Also it does not specify any reduction in the response reduction factor on account
of any irregularity (vertical or plan-irregularity) in the framing system which should be
considered.
Finding of R factor of regular building frames with two storey, three story, five storey,
13
CHAPTER-2
OVER VIEW OF RESPONSE REDUCTION FACTOR
__________________________________________________________________
2.1 Introduction to Basic Concept of Seismic Design
Design requirements for lateral loads, such as winds or earthquakes are inherently different from
those for gravity (dead and live) loads. Due to frequency of loading scenario, design for wind
loads is a primary requirement. But in areas of high seismicity, structures are designed to
withstand lateral actions also. Since the seismic design deals with events with lower probability
of occurrence, it may therefore be highly uneconomical to design structures to withstand
earthquakes for the performance levels used for wind design. For example, building structures
would typically be designed for lateral wind loads in the range of 1% to 3% of their weight.
Earthquake loads may reach 30%-40% of the weight of the structure, applied horizontally. If
concepts of elastic design normally employed for primary loads are used for earthquake loads,
14
the result will be in the form of extremely heavy and expensive structures. Therefore, seismic
design uses the concepts of controlled damage and collapse prevention.
The basic principal of designing structures for strong ground motion is that the structure should
not collapse but damage to the structural elements is permitted. Since a structure is allowed to be
damaged in case of severe shaking, the structure should be designed for seismic forces much less
than what is expected under strong shaking, if the structures were to remain linearly elastic. The
concept of R factor is based on the observations that well detailed seismic framing systems can
sustain large inelastic deformations without collapse and have excess of lateral strength over
design strength.
2.2 Over-View of Response Reduction Factor
Response reduction factor is the factor by which the actual base shear force should be reduced, to
obtain the design lateral force. Base shear force is the force that would be generated if the
structure were to remain elastic during its response to the design basic earthquake (DBE)
shaking. Response reduction (R) factors are essential seismic design tools, which are typically
used to describe the level of inelasticity expected in lateral structural systems during an
earthquake. The response reduction factor (R) is depends on Over strength (Rs), Ductility (R),
Redundancy (RR) (see in Fig.2.1).
15
In the mid-1980s, data from experimental research at the University of California at Berkeley
were used to develop base shear-roof displacement relationships for steel braced frames and a
draft formulation for the response modification factor. The base shear-roof displacement
relationships were established using data acquired from the testing of two code-compliant braced
steel frames, one concentrically braced (Uang and Bertero, 1986) and one eccentrically braced
(Whittaker et al., 1987). Using these data, the Berkeley researchers proposed splitting R into
three factors (see Eq.2.1) that account for contributions from reserve strength, ductility, and
viscous damping.
R=
Rs R R
. (2.1)
Using data from the most severe earthquake simulation test, the strength factor was calculated as
the maximum base shear force divided by the design base shear force at the strength level. The
ductility factor was calculated as the base shear for elastic response divided by the maximum
base shear force and the damping factor was set equal to 1.0.
Much research (ATC, 1982b; Freeman, 1990; ATC, 1995) has been completed since the first
formulation for R was proposed. Recent studies, including those in the companion Project ATC34, support a new formulation for R (see Eq.2.2), which is the product of three factors as over
strength ductility and redundancy factors.
R=
R s R R R
. (2.2)
This formulation, with the exception of the redundancy factor, is similar to those proposed by the
Berkeley researchers and Freeman (1990). The Freeman formulation, which was developed
independently of the Berkeley formulation, described the response reduction factor as the
product of a strength-type factor and a ductility-type factor. The function of redundancy factor is
to quantify the improved reliability of seismic framing systems that use multiple lines of vertical
seismic framing in each principal direction of a building.
A fourth factor called viscous damping factor (
mainly to account for response reduction provided by supplemental viscous damping devices.
16
Such a viscous damping factor could be used to reduce displacements in a nonlinear framing
system, but cannot be used to proportionally reduce force demands, especially for highly-damped
frames. Recognizing that seismic design using response modification factors will remain forcebased in the near term, the damping factor was excluded from the new formulation.
The proposed formulation does not specifically address the effects of plan and vertical
irregularity in framing systems. Irregularity could be addressed by reducing the response
modification factor by a regularity factor. Significant force-based penalties (higher design base
shears) for the design of irregular framing systems would both discourage the use of irregular
framing and reduce the uncertainties associated with the nonlinear response of irregularly framed
buildings.
2.3 Components of Response Reduction Factor
R factor is depends on ductility factor (R), structural over strength, structural redundancy and
damping associated with structure as shown on Eq.2.3.
R=
R s R R R R
. (2.3)
R
(
s)
2.3.1 Over Strength Factor
The inertia force due to earthquake motion, at which the first significant yield in a reinforced
concrete structure starts, may be much higher than the prescribed unfactored base shear force
because of many factors given below.
i.
ii.
iii.
iv.
v.
vi.
vii.
17
The structural overstrength also results from internal forces distribution, higher material strength,
strain hardening, confined reinforcement detailing, effect of nonstructural elements, strain rate
effects. Code limits on interstory drift may require the use of member sizes in flexible (longperiod) framing systems that are greater than those required for strength alone giving rise to
period-dependent strength factors for drift limited framing systems. Also, buildings located in
lower seismic zones will likely have different reserve strength values than those in higher
seismic zones because the ratio of gravity loads to seismic loads will differ - resulting in zonedependent values for the strength factor. The Over strength factor (
expressed as ratio of base shear corresponding first yielding (
V 1
Rs
) mathematically
V
( d ) .
Rs
V1
= Vd
. (1.4)
m
y
. (2.5)
18
( m)
to yield displacement
The ductility reduction factor (R) takes advantage of the energy dissipating capacity of properly
designed and well-detailed structures and, hence, primarily depends on the global ductility
demand () of the structure. The ductility reduction factor (R) is a factor which reduces the
elastic force demand to the level of idealized yield strength of the structure and, hence, it may be
represented by Eq.2.6.
R =
Ve
Vy
(2.6)
The relationship between displacement ductility and the ductility factor has been the subject of
much research in recent years. The relationships developed by Newmark and Hall (1982),
Krawinkler and Nassar (1992) and Miranda and Bertero (1994) are presented below.
Newmark and Hall (1982)
Newmark and Hall (1982) was made the first attempt to relate R with for a single-degree-offreedom (SDOF) system with elastic-perfectly plastic (EPP) resistance curve. They concluded
that for a structure of a natural period less than 0.03 second (short period structures), the ductility
does not help in reducing the response of the structure (see Eq.2.7). Hence, for such structures,
no ductility reduction factor should be used. For moderate period structures, corresponding to the
acceleration region of elastic response spectrum T = 0.12 to 0.5 sec the energy that can be stored
by the elastic system at maximum displacement is the same as that stored by an inelastic system
(see Eq.2.8). For relatively long-period structures of the elastic response spectrum they
concluded that inertia force obtained from an elastic system and the reduced inertia force
obtained from an inelastic system cause the same maximum displacement.
. (2.7)
For frequencies between 2 Hz and 8 Hz (periods between 0.12 second and 0.5 second)
R =
2 1
. (2.8)
19
(2.9)
1 /c
= [c(1)+1]
(1.10)
Where
Ta
b
C (T, a) = 1+T b + T
(1.11)
Regression Parameters
a=1
b= 0.42
a=1
b= 0.37
a=1
b= .29
presented in Fig.2.2 for a strain-hardening ratio of 10 percent. Krawinkler and Nassar concluded
that the strength demands for SDOF systems must generally be increased to be applicable for
MDOF frame structures. The modification factor, defined as the required base shear strength of
the MDOF system divided by the inelastic strength demand of the corresponding first-mode
SDOF system, limits the story ductility ratio in the MDOF system to the target ductility ratio.
20
- - T Relationship
Modification factors for target ductility ratios of four and eight, and strain hardening ratios of
percent and 10 percent are presented in Fig.2.4. For buildings with fundamental periods less than
0.75 second, the base shear demand on the MDOF system is approximately equal to the
corresponding SDOF system strength demand, suggesting that higher-mode effects need not be
considered in this period range. For buildings with fundamental periods exceeding 0.75 second,
higher-mode effects will necessitate an increase in the design lateral strength if target ductility
ratios are to be satisfied.
21
. (1.12)
Where is calculated from different equations for rock, alluvium and soft sites as shown below.
. (1.13)
. (1.14)
. (1.15)
A comparison of the Nassar and Krawinkler and Miranda and Bertero
- - T relationships
for rock and alluvium sites is presented in Figure 4.10. Since the differences between these
relationships are relatively small, they can be ignored for engineering purposes.
22
25
CHAPTER-3
NON LINEAR MODELLING AND PUSH OVER ANALYSIS
__________________________________________________________________
3.1 Non-Linear Modelling of RC members
Non-linear static analysis requires the knowledge of material property, stress-strain model,
plastic hinge property, types of hinges, hinge location, hinge length and moment-curvature
relationship. And also estimation of R values of depends mainly on how well the nonlinear
behaviour of these frames is modelled in analyses. Since R values are estimated on the basis of
nonlinear static pushover analyses, the focus of the modelling scheme employed here is to
capture the nonlinear static behaviour of the RC frame members.
3.1.1 Material Non Linearity
Material nonlinearity is associated with the inelastic behaviour of a component or system.
Inelastic behaviour may be characterized by a force-deformation relationship, also known as a
backbone curve, which measures strength against translational or rotational deformation.
Manders confined and unconfined stress-strain curve model has been used in this study to
account concrete material nonlinearity. The stress-strain curve of reinforcement steel of different
grades is shown in Fig.3.2.
26
But practically the expected strength of steel and concrete will be more than charactestic
strength. The Expected strength of steel is about 1.25 characteristic yield stress (fy). Whereas the
expected strength of concrete is equals to target mean strength and it is obtained by Eq.3.1.
f ck ' =f ck +1.65 xS
.3.1
Table 3.1 Assumed Standard Deviation
Grade of Concrete
M10
M15
M20
M25
M30 to M50
3.5
4
5
Monotonic coupon test results shall not be used to determine reinforcement strain limits, because
material will fail at low strains due to cyclic effect. The following Usable Strain Limits shall be
used for pushover analysis recommended by ASCE 41-2013.
Concrete
Steel
The stress-strain curves are drawn for expected strengths of steel and concrete as shown in
Fig3.3 for M20 concrete and Fe415 steel. The increase in strength of steel after yield point is
neglected and assumed that stress is constant up to 14.5% strain.
30
20
Stress (Mpa)
26.56
20
10
-5.00E-03
0
0.00E+00
-10
5.00E-03
Strain
27
1.00E-02
518.75
500
492.81
466.87 415
441
400 415 394.25
373.5
332352.75
Stress (Mpa)
415
518.75
415
300
Expected
Strength fy'
200
Characterstic Strength fy
100
0 0
0
) and
) of the section and the length of the plastic hinge region (Lp). The
u
p=
y l p
(1-
0.5. LP
LV
. (3.2)
y
= y
LV + a v Z
3
H
+ 0.0013 (1+1.5 LV
) + 0.13
db f y
f C
. (3.3)
u
. (3.4)
Plastic Hinge Length
Various empirical expressions have been proposed by investigators for the equivalent length of
plastic hinge (
lp
).
. (3.5)
= 0.25d + 0.075z
. (3.6)
= 0.08Z + 0.022
db f y
(3.7)
The plastic rotation capacities of frame members of the study structures are computed using
Eq.3.7 by assuming the points of contra-flexure to be at the mid-span of members.
29
Prestressed
Columns
Pu
0.5
- 1.0 Ec I g
Pu
Agfc
0.1
- 0.7
Agfc
Ec I g
- 0.3
Ec I g
Description
Operational
Immediate
Occupancy
Life Safety
operable
Moderate damage, some permanent drift, some residual
strength and stiffness left in all stories, damage to partition,
Collapse
Prevention
+ 10% of (
u y
+ 60% of (
u y
+ 90% of (
u y
bd
Transverse
Reinforcemen
Immediate
Life
Structural
Occupanc
Safety
Stability
y
V
bw bd f ,c Plastic Rotation Limit
t
0
0
0.5
0
0
0.5
C
C
C
NC
NC
NC
3
6
3
3
6
3
0.01
0.005
0.005
0.005
0.0015
0.005
32
0.020
0.010
0.01
0.01
0.005
0.01
0.025
0.020
0.02
0.02
0.01
0.01
Immediate
Collapse
Occupanc
Prevention
y
P
A g f ,c
Transverse
Reinforcemen
V
bw bd f ,c
t
0.1
0.1
0.4
0.1
0.1
0.4
C
C
C
NC
NC
NC
3
6
3
3
6
3
0.005
0.005
0.003
0.005
0.005
0.002
0.015
0.012
0.012
0.005
0.004
0.002
0.020
0.016
0.015
0.006
0.005
0.003
It is believed that the conventional elastic design analysis method cannot capture many important
aspects that affect the seismic performance of the building. The ability of a building to undergo
inelastic deformations determines the structural behavior of building during seismic ground
motions. Nonlinear dynamic analysis is a principally convenient approach, but it is very complex
and not practical for every design. From the practical point of view, this method is not suitable
for every design use, and for the time being it is mostly appropriate for research and design of
important structure.
To estimate seismic demands for a building, the structural engineering profession is now using
the non-linear static procedure, known as pushover analysis. It is a commonly used technique,
which provides acceptable results. The term static implies that static analysis is applied to
represent a dynamic phenomenon. Pushover analysis is defined as an analysis wherein a
mathematical model directly incorporating the nonlinear load-deformation characteristics of
individual components and elements of the building shall be subjected to monotonically
increasing lateral loads representing inertia forces in an earthquake until a target displacement
is exceeded. Target displacement is the maximum displacement (elastic plus inelastic) of the
building at roof expected under selected earthquake ground motion. The analysis accounts for
material inelasticity, geometrical nonlinearity and the redistribution of internal forces.
3.2.3
The analysis results are sensitive to the selection of lateral load pattern. In pushover analysis
selecting lateral load pattern, a set of guidelines as per FEMA 356 is explained in Section 2.5.2.
The lateral load generally applied in both positive and negative directions in combination with
gravity load (dead load and a portion of live load) to study the actual behavior. Different types of
lateral load used in past decades are as follows. Loading pattern should produce a deflected
shape in the structure similar to that it would undergo in earthquake response.
1. Uniform Lateral Load Pattern
The lateral fore at any story is proportional to the mass at that story. Approximates first mode
response of structure with very soft stories or postyield response of structrues with weak first
storey.
34
Wx
Fx
Wi
VB
i=1
. (3.6)
2. First Elastic Mode Lateral Load Pattern
The lateral force at any story is proportional to the product of the amplitude of the elastic first
mode and mass at that story. First mode response obtained from a modal analysis.
mi i
Fx
mi i
VB
i=1
. (3.7)
3. Inverse Triangular
Approximates first mode response shape of regular structures.
W x hx
Fx
wi hi
VB
i=1
. (3.8)
4. Code Lateral Load Pattern
As per IS1893-2002 (Part-1), the lateral load distribution along the height is given by
W x h x2
Fx
= wi hi2
VB
i=1
(3.9)
R factors are used in current building codes to estimate strength demands for structural systems
designed using linear methods but responding in nonlinear manner. Their values are vital in the
specification of design seismic loading. R factors were originally based on judgment and
qualitative comparisons with known response of some of the framing systems. Now it has come
a long way by actually quantifying it using nonlinear analysis tools and peak ground and spectral
parameters.
35
The values of response reduction factor of RC elevated water tank are given in IS 1893 (Part-II)
2002, which is arrived at empirically based on engineering judgment. The components of R can
be determined in several ways, each dependent on the performance level under consideration. In
this report, only the life-safety performance level is considered explicitly.
CHAPTER-4
RESPONSE REDUCTION FACTOR EVALUATION
__________________________________________________________________3
4.1 General
The structural systems considered in this research is a typical symmetric-in-plan RC frame
structures having four bay configurations, intended for office purpose. It is assumed that infill
walls are located only at external faces and infill walls contain large openings. This assumption
is to avoid the effect of infill walls on R factor. Totally six models of building (Two storey, Three
storey, Five storey, eight storey and Twelve Storey buildings) are considered which covers short,
medium and long time period ranges of Indian Response Spectrum. All considered building
models are assumed to locate on medium soil. To consider the effect of zone the buildings are
considered to locate at zone III and zone IV. The seismic demands on these buildings are
calculated following IS 1893. The RC design of these buildings are based on IS 456 for Ordinary
Moment Resisting Frame and based on IS 456 and IS 13920 for Special Moment Resisting
Frame.
36
Dimensions
-175mm thick
Dead
Super Dead
Concrete-25kN/m3
Floor Finish
Masonry-20kN/m3
37
-1kN/m2
Live Load
Floor -4kN/m2
Roof -1.5kN/m2
Seismic
Details
Nonlinear static pushover analyses (NSPA) of the two storey, three storey and five storey
buildings study frames are performed to estimate their overstrength and global ductility capacity,
which are required for computing R for each frame. The equivalent lateral force distribution
adopted for this pushover analysis is as suggested in IS 1893. Manders confined and unconfined
concrete model has been used for SMRF and OMRF respectively.
W x hx2
Fx
= w i hi 2
VB
i=1
.4.2
As mentioned earlier in literature review, two performance limits are considered in the
computation of R for the study frames. The first one (Performance Limit 1) corresponds to the
Structural Stability limit state defined in FEMA-356. This limit state is defined both at the storey
level (in terms of the maximum interstorey drift ratio) and at the member level (in terms of the
allowable plastic hinge rotation at member ends). The second limit state (Performance Limit 2) is
based on plastic hinge rotation capacities that are obtained for each individual member
depending on its cross-section geometry.
4.2 Response Reduction Factor Evaluation
In this present section two storey, three storey and five storey buildings are designed by
Equivalent Static Method as these buildings are regular and buildings are assumed to locate in
zone III. After designing of the buildings nonlinear hinge properties of beams and columns are
calculated by using Manders model from the SAP 2000 and given as input to the SAP. A
nonlinear gravity dead load case D.L+0.5L.L (50% Live Load because Floor Live Load=4
kN/mm2 >3kNn/mm2) is given before running pushover analysis. Since there is no perfect yield
point in the base shear curve, FEMA-356 Coefficient Method is used to find yield displacement
and yield force. The maximum displacement of the building is limited by Collapse Prevention
Level and Maximum Drift Ratio. That ultimate displacement of the building is taken as
38
displacement at which any member reaches collapse prevention level or building reaches
maximum drift ratio whichever occurs first.
Firstly, the building is analyzed as Ordinary Moment Resisting Frame by assuming R=3. After
that building is designed as per IS 456-200 and R factor is calculated. Secondly, for the same
analysis the building is designed as per ductile detailing IS 13920 to find the effect of ductility.
For the Special Moment Resisting Frame the nonlinear hinge properties are calculated by using
Manders Confined Concrete Model as the joints region are confined in case of ductile detailing.
From the literature review, it is observed that buildings designed as IS 13920 ductile detailing
safe in shear and members fail by flexure before shear failure. Whereas in case of OMRF
buildings designed as per IS 456 may fail in shear before flexural failure. So in case of SMRF
buildings, beams and columns are modelled by flexural nonlinear hinges only and in case of
OMRF buildings, beams and columns are modelled by nonlinear shear hinges also. The building
configuration, reinforcement details, pushover curve and Response Reduction Factor are
presented in the following section.
a. Two Storey Building
39
40
The details of the building are given below. The reinforcement of all interior frames is kept same
and reinforcement details are shown in Fig.4.2.
Details of Building
42
Yield Displacement
Ultimate Load
Ultimate Displacement
Ductility Ratio (
Vu
=0.0446m
= 2042 kN
Vd
=0.0984m
=865 kN
) = 2.20
43
Ductility Factor (
) = 1.84
Rs
) = 2.36
Yield Displacement
Ultimate Load
Ultimate Displacement
Ductility Ratio (
Ductility Factor (
Vu
=0.0494m
= 2145 kN
m
Vd
=0.191m
=865 kN
) = 3.86
) = 2.6
Rs
) = 2.48
44
45
46
Details of Building
Yield Displacement
Ultimate Load
Ultimate Displacement
Ductility Ratio (
Ductility Factor (
Vu
=0.0628m
= 3408 kN
m
Vd
=0.146m
=1521 kN
) = 2.32
) = 1.91
Rs
) = 2.24
Yield Displacement
Ultimate Load
Ultimate Displacement
Ductility Ratio (
Ductility Factor (
Vu
=0.0659m
= 1521 kN
m
Vd
=0.265m
=3529 kN
) = 4.02
) = 2.65
48
Rs
) = 2.32
49
50
Details of Building
51
52
Yield Displacement
Yield Load
Ultimate Displacement
Ductility Ratio (
Ductility Factor (
Vu
=0.107m
= 3679 kN
m
Vd
=0.295m
=1725 kN
) = 2.76
) = 2.12
Rs
) = 2.13
53
Yield Displacement
Yield Load
Ultimate Displacement
Ductility Ratio (
Ductility Factor (
Vu
=0.108m
= 3749 kN
m
Vd
=0.450m
=1725 kN
) = 4.16
) = 2.71
Rs
) = 2.173
Two Storey
Ductility Factor
R
( )
OMRF
SMRF
OMRF
SMRF
2.36
2.48
1.84
2.6
54
Response
Reduction Factor
(R)
OMRF
SMRF
4.34
6.45
Three Storey
2.24
2.32
1.91
2.65
4.28
6.15
Five Storey
2.13
2.17
2.12
2.71
4.53
5.89
Rs
rise buildings can deform large displacements wihout failing due to high ductilty.
55
Rs
and
Ordinary Moment Resisting Frame to Special Moment Resisting Frame (see in Table
4.2). This is because of increasing ductility capacity in case of SMRF due to confinement
of joints.
56
REFERENCES
__________________________________________________________________
1. Applied Technology Council (ATC). 1995a. Structural response modification factors.
Rep. No. ATC-19, Redwood City, California.
2. Applied Technology Council (ATC). 1996. Seismic evaluation and retrofit of concrete
buildings. Rep. No. ATC-40, Redwood City, California.
3. American Society of Civil Engineers (ASCE). 2000. Prestandard and commentary on
the seismic rehabilitation of buildings. Rep. No. FEMA-356, Washington, D.C.
4. American Society of Civil Engineers (ASCE). 2005. Minimum design loads for
buildings and other structures. Rep. No. ASCE-07, Reston (USA).
5. Bureau of Indian Standards (BIS). 2000. Indian standard code of practice for plain and
reinforced concrete. Rep. No. IS-456, New Delhi, India.
6. Bureau of Indian Standards (BIS). 2002. Criteria for earthquake resistant design of
structures. Rep. No. IS-1893, Part-1, New Delhi, India.
7. European Committee for Standardization (CEN). 2004. Eurocode 8: Design of structures
for earthquake resistance-Part 1: General rules, seismic actions and rules for buildings.
Rep. No. EN 1998-1, Brussels, Belgium.
57
8. Hayri, B.O., and Mehmet, I. (2008). Evaluation of strength reduction factor for existing
mid-rise buildings. Proc., 14th World Conf. on Earthquake Eng., Beijing, China, 165174.
9. Jain, S. K., and Rahul, N. (1995). Seismic overstrength in reinforced concrete frames.
J. Struct. Eng., 121 (3), 580-585.
10. Mander, J. B., Priestley, M. J. N., and Park, R. (1988). "Observed stress-strain behavior
of confined concrete." J. Struct. Eng., ASCE, 114(8), 1827-1849.
11. Miranda, E., and Bertero, V. V. (1994). Evaluation of strength reduction factors for
earthquake resistant design. Earthquake Spectra, 10(2), 357-379.
12. Mondal, A., Ghosh, S., and Reddy, G. (2013). Performance based evaluation of the
response reduction factor for ductile RC frames. J. Struct. Eng., 56, 1808-1819.
13. Maheri, M.R., and Akbari, R. (2013). Seismic behavior factor, R, for steel X-braced and
knee-braced RC buildings. J. Struct. Eng., 25 (15), 15051513.
14. Samar, A. B., Abdallah, I. H., and Anis, S. A. (2012). A step towards evaluation of the
seismic response reduction factor in multistorey reinforced concrete frames. Natural
Hazards, 16 (1), 6580.
15. Standards Association of New Zealand (NZS). 1992. "Code of practice for general
structural design and design loadings for buildings." Rep. No. NZS 4203, Wellington,
New Zealand.
16. Vishva, K. S., and Jignesh, A. A. (2015). Effects of soil condition on response reduction
factor of elevated rcc water tank., International Journal of Advance Engineering and
Research Development., 2 (6), 33-67.
17. Whittaker, A., Hart, G., and Rojahn, C. (1999). Seismic response modification factors.
J. Struct. Eng., 125(4), 438-444.
58
ANNEXURE I
Load Calculations and R factor Calculations of Five Storey Building
Seismic Weight Calculations
Dead Load
= 8814kN
Dead Slab
= 16056kN
Wall Load
= 7970kN
Live Load
= 0.5x9216 = 4608kN
Roof Live
= 0x864 =0
Seismic Weight
TX
TY
= 0.075x h
0.75
=0.787 sec
0.1611.726
W=
23
37450 = 1725kN
R factor Calculations
OMRF
59
Yield Displacement
Ultimate Load
=0.107m
Vu
= 3679 kN
m
Ultimate Displacement
Vd
Ductility Ratio (
=1725kN
Ductility Factor (
y
m
2 1 = 2 x 2.761 =2.12
Rs
=0.295m
) =
Vu
Vd
0.295
0.107
= 2.76
3679
1725
=2.13
SMRF
From pushover curve (see Fig.4.7.c)
y
Yield Displacement
Ultimate Load
Vu
= 3749 kN
m
Ultimate Displacement
Design Base Shear
Ductility Ratio (
Ductility Factor (
=0.108m
=0.450m
Vd
=1725kN
y
m
2 1 = 2 x 2.761 =2.71
0. 450
0.108
= 4.16
60
Rs
) =
Vu
Vd
3749
1725
61
=2.173