HT-C2410A Battery Charger

Technical features
The HT-C series is a Switching technology and
Battery Care philosophy, since years parts of the
core know-how at Huegli Tech, led to the
development of this advanced multi-stage battery
charging method, completely automatic and suited
to meet the most advanced requirements of
battery manufacturers. The Battery Care concept is
base on algorithms that implement rapid and
automatic charging, battery charge optimization
during time, flat batteries recovery and real time
diagnostic during installation and operation.

HT-C2410A-Datasheet-13-12-06-um-en

Input: Single-phase 115 230 Vac

Output: Battery charging 24 Vdc; 10 A

Suited for the following battery types: Open Lead


Acid, Sealed Lead Acid, lead Gel and Ni-Cd
(option)

Automatic diagnostic of battery status. Charging


curve IUoUo, constant voltage and current

Switching technology, output voltage 28.8 Vdc


Three charging levels: Boost, Trickle, Recovery.

Protected against short circuit, inverted polarity,


over Load.

Signal output (contact free) for fault battery state

Protection degree IP20 - DIN rail

The Real Time Auto-diagnostic system, monitoring


battery faults such as, elements in short circuit,
accidental
reverse
polarity
connection,
disconnection of the battery, they can easily be
detected and removed by help of Blink Code of
Diagnosis Led; during the installation and after sell.
Each device is suited for all battery types, by
means of jumpers it is possible setting predefined
curves for Open Lead Acid, Sealed Lead Acid, Gel,
Ni-Cd (option). They are programmed for two
charging levels, boost and trickle. A rugged casing
with bracket for DIN rail mounting provide IP20
protection degree. They are extremely compact
and cost-effective

V1.1

06.12.2013

um

Page 1 of 2

General Data

Battery Output (Battery Care)


3000 Vac
1605 Vac
500 Vac
IP20
I, with PE
connected
> 300.000 h
2
2,5mm(24
14AWG)
I, with PE
100x115x135
mm
0.85 Kg approx

Insulation voltage (In /Out)


Insulation voltage (In / PE)
Insulation voltage (Out / PE)
Protection Class (EN/IEC 60529)
Protection class
Reliability: MTBF IEC 61709
Pollution Degree Environment
Connection Terminal Blocks screw Type
Protection class (PE Connected)
Dimensions (w-h-d)
Weight

Climatic Data
-25 +70C
- 2.5%(In) / C
-40 +85C
95% to 25C
Auto Convention

Ambient temperature (operation)


De Rating Ta > 50C
Ambient temperature Storage
Humidity at 25 C no condensation
Cooling

Norms and Certifications


Conforming to:
IEC/EN 60335-2-29
EN60950/UL1950,Electrical safety
89/336/EEC,EMC Directive
2006/95/EC (Low Voltage)
DIN41773 (Charging cycle)
Emission: IEC 61000-6-4
Immunity: IEC 61000-6-2.CE

Boost charge (25 C) (Typ. at In)


Max. time Bust Charge (tpy. At In)
Min. time Bust Charge (tpy. At In)
Trickle charge (25 C) (Typ. at In)
Jumper Configuration battery type
(V cell) Ni-Cd (optional)
Recovery Charge
Charging. Max Ibatt (In)
Efficiency (50% of In)
Charging current limiting Iadj
Quiescent Current
Charging Curve automatic: IUoUo
Detection of element in short circuit
Short-circuit protection)
Over Load protection
Over Voltage Output protection
Adjustable charging current (% In)

Charging
An automatic multi-stage charging and real time diagnostic
allow fast recharge and recovery of deep discharged batteries,
adding value and reliability to the system hosting. Type of
charging it is Voltages and current stabilized IUoUo. The state
of charging battery and Auto-diagnosis of the systems are
identified by a flashing code on a Diagnosis LED and Fault
Battery LED:

Charging
Type

Signal Output (free switch N2 contact)


Yes
Yes
Yes

Main or Backup Power


Low Battery
Fault Battery

Type of Signal Output Contact


Max.
current
can
be
switched
(EN60947.4.1):
Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A
Min.1mA at 5 Vdc

28.8 Vdc
15 h
1 min.
27.5 Vdc
2.23;2,25;2,27;2,3;
1,411,5 (20 elem.)
2 18 Vdc
10 A 5%
88%
20 100 % / In
5 mA
3 stage
Yes
Yes
Yes
Yes
20 100

Auto
diagnosis

State
Trickle
Boost
Recovery
Reverse
polarity
Battery No
connect
Element in
Short C.
Replace
Battery

Diagnosis
LED
1 Blink/sec
2 Blink/sec
5 Blink/sec
1Blink

Battery
Fault LED
OFF
OFF
OFF
ON

2Blink

ON

3Blink

ON

5Blink

ON

Resistive load
Min. load

Input Data
Nominal Input Voltage (2 x Vac)
Input Voltage range (Vac)
Inrush Current (Vn and In Load) I2t
Frequency
Input Current (115 230 Vac)
Internal Fuse
External Fuse (recommended)

HT-C2410A-Datasheet-13-12-06-um-en

115 230
90 135 / 180 264
16 A 5 msec.
47 63 Hz 6%
3.3 2.2 A
6.3 A
16 A (MCB curve B)