SE-400 MANUAL
GROUND-FAULT-RELAY TEST UNIT
Revision 1-A-072115
LITTELFUSE STARTCO
GROUND-FAULT-RELAY TEST UNIT SE-400

AMPERES

THERMAL
LIMIT
USE SWITCHES LABELLED AMPERES TO SET
MAGNITUDE (0.5 TO 9.9 A) OF OUTPUT CURRENT.
USE SWITCHES LABELLED SECONDS TO SET
DURATION (0.1 TO 9.9 s) OF OUTPUT CURRENT.
PRESS TEST TO INITIATE OUTPUT CURRENT.
DISPLAY INDICATES MAGNITUDE OF OUTPUT
CURRENT FOR DURATION OF OUTPUT.
SET SWITCHES LABELLED SECONDS TO 0.0 FOR
MANUAL CONTROL OF OUTPUT DURATION.
PUSH TEST TO SWITCH OUTPUT ON OR OFF.

AMPERES
2

SECONDS

0.5
TO
9.9

0.1
TO
9.9

TEST

Copyright 2015 by Littelfuse Startco


All rights reserved.

Document Number: PM-1605-EN


Printed in Canada.

SE-400 Ground-Fault-Relay Test Unit

This page intentionally left blank.

Page i
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit

TABLE OF CONTENTS
SECTION

PAGE

1
2

General ................................................................. 1
Operation ............................................................. 1
2.1 Front-Panel Controls ............................................. 1
2.1.1 Amperes ..................................................... 1
2.1.2 Seconds ...................................................... 1
2.1.3 Test ............................................................ 1
2.2 Indication .............................................................. 1
2.3 Thermal Limit ....................................................... 1
3
Installation ........................................................... 1
4
Test Procedure .................................................... 1
5
Troubleshooting .................................................. 1
6
Technical Specifications...................................... 4
7
Ordering Information ......................................... 4
8
Warranty ............................................................. 4
Appendix A SE-400 Revision History ........................... 5

LIST OF FIGURES
FIGURE
1
2
3

PAGE

SE-400 Outline and Mounting Details .................. 2


Panel-Mounting Procedure.................................... 3
Typical Connection Diagrams............................... 3

DISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a
result of a malfunction, incorrect application, or incorrect
adjustment.

Page ii
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit

This page intentionally left blank.

Page iii
Rev. 1-A-072115

Page 1
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit


1. GENERAL

3. INSTALLATION

The SE-400 is an ac current source with a


programmable output. The magnitude and duration of
the output can be selected with front-panel switches so
that ground-fault-relay coordination can be confirmed at
the push of a button.
The current output is transformer isolated from supply
voltage.

SE-400 outline and mounting details are shown in


Fig. 1. Panel-mounting procedures are shown in Fig. 2.
Connect L1 and L2 to supply voltage using L2 as N.
Connect ground terminal 1 ( ) to ground. Loop an
output conductor through the windows of the groundfault CT's connected to the ground-fault relays under test.
Connect one end of the output conductor to terminal 1
(OP1) and the other end to terminal 12 (OP2). For
output-conductor lengths under 40 ft, use 14 gauge wire.
For output-conductor lengths over 40 ft and up to 80 ft,
use 12 gauge wire.
If remote operation is required, connect a normally
open momentary contact to terminals 8 and 9 (RMT1 and
RMT2). Low-level contacts are recommended.
Typical connection diagrams are shown in Fig. 3.

2. OPERATION
2.1 FRONT-PANEL CONTROLS
2.1.1 AMPERES
The AMPERES switch has four push buttons and a
two-digit numeric indicator to adjust current output to
the desired value. The range is 0.5 to 9.9 A. If a value
below 0.5 is selected, there will be no output.
2.1.2 SECONDS
The SECONDS switch has four push buttons and a
two-digit numeric indicator to adjust output duration.
The range is 0.1 to 9.9 s, or select 0.0 for continuousoutput operation.
2.1.3 TEST
Press TEST for an output burst of the magnitude and
duration selected by AMPERES and SECONDS. Press
TEST again to stop a continuous-output operation.
2.2 INDICATION
The two-digit LED display indicates the magnitude of
the output current for the duration of the output burst.
The centre decimal point serves as a supply voltage
indicator. A decimal point on the right side of the
display is used to indicate a thermal-limit condition.
2.3 THERMAL LIMIT
When the SE-400 is used in the continuous-output
mode, the internal circuit temperature can reach the
thermal-limit temperature. To prevent damage to the
SE-400, the current output is disabled and the thermallimit indicator turns on. The output remains disabled
until the temperature has fallen to a safe level, at which
time the thermal-limit indicator turns off and the output
is enabled.

4. TEST PROCEDURE
Set the required output current level0.5 to 9.9 A.
The recommended test current is 120% of the groundfault trip level of the device being tested.
Set the output duration0.1 to 9.9 s or 0.0 for push-on
push-off operation.
Press the TEST button. The ground-fault unit(s) being
tested should trip.

5. TROUBLESHOOTING
Problem:
No current output when the TEST button is pressed.
Possible Causes:

Loose output connections.


Resistance of the output wire is too high.
VA requirement of the load is too high.
Current is set to less than 0.5 A.
No supply voltage.
Thermal limit exceeded.
Power-supply fuse F1 open.

Troubleshooting:
Check the SE-400 operation by connecting a short
length of wire across the output terminals and
pressing the TEST button.
If using a remote test switch, check remote switch
operation and connection to the SE-400.

Page 2
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit

3.4
(0.13)

3.2
(0.12)

139.7
(5.50)

104.0
(4.09)
91.7
(3.61)

LITTELFUSE STARTCO
GROUND-FAULT-RELAY TEST UNIT SE-400

1
2
3
4
5
6
7
8
9
10
11
12

212.7
(8.37)
218.4
(8.60)

F1

AMPERES

L1
L2

THERMAL
LIMIT
USE SWITCHES LABELLED AMPERES TO SET
MAGNITUDE (0.5 TO 9.9 A) OF OUTPUT CURRENT.

R MT 1
R MT 2
OP 1
OP2

USE SWITCHES LABELLED SECONDS TO SET


DURATION (0.1 TO 9.9 s) OF OUTPUT CURRENT.
PRESS TEST TO INITIATE OUTPUT CURRENT.
DISPLAY INDICATES MAGNITUDE OF OUTPUT
CURRENT FOR DURATION OF OUTPUT.
SET SWITCHES LABELLED SECONDS TO 0.0 FOR
MANUAL CONTROL OF OUTPUT DURATION.
PUSH TEST TO SWITCH OUTPUT ON OR OFF.

AMPERES

SECONDS

0.5
TO
9.9

0.1
TO
9.9

TEST

PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)

NOTES:

M4 OR 8-32 TAP
(NOTE 2)

6.4

R=2. 2 (0.09)

1. DIMENSIONS IN MILLIMETRES
(INCHES).
2.5
(0.10)

2.5
(0.10)

2.5
(0.10)

195.0
(7.68)
200.0
(7.87)
212.7
(8.37)

203.2
(8.00)

2. MOUNTING SCREWS:
M4 x 10 OR 8-32 x 0.375.

(0.25)

98.4
(3.87)
93.3
(3.67)
76.2
(3.00)

2.5
(0.10)

63.5
(2.50)

5.0
(0.20)

14.1
(0.56)

FRONT VIEW

SIDE VIEW

REAR VIEW

REAR PANEL
OUTLINE

SURFACE MOUNT

FIGURE 1. SE-400 Outline and Mounting Details.

R=4. 8 (0.19)
MAXIMUM

8.2
(0.32)

8.2
(0.32)

PANEL-MOUNT CUTOUT

6.4
(0.25)

2.5
(0.10)

BEZEL
OUTLINE

Page 3
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit


STEP 1

STEP 2

STEP 3

1
2
3
4
5
6
7
8
9
10
11
12

2 L1
3
4 L2
5
6
T1
7 R MM T 2
8 R
9
1
1 0 1 O PP 2
1 2 O
1

1
2
3
4
5
6
7
8
9
10
11
12

L1
L2
R MT 1
R MT 2
OP 1
OP2

L1
L2
R MT 1
R MT 2
OP 1
OP2

THE SE-400 MAY BE PANEL MOUNTED WITHOUT


DISASSEMBLY.
NOTE: REMOVE PLUG-IN TERMINAL BLOCK BEFORE
INSTALLING SE-400 THROUGH PANEL.

FIGURE 2. Panel-Mounting Procedure.

SE-CS30

NEUTRAL

FROM
POWER
SOURCE

LOAD

TO SE-330
4

NGR
L
N

11
3
5

OP1

REMOTE
TEST

12

R1 L

L1
L2

1
8

OP2

N
ITEST

TO SENSING
RESISTOR
TERMINAL N

SE-400

11
10

RMT2

S1 S2

L1
L2/N

3
5

OP1

1. FOR DEVICES WITH LOWER TRIP LEVELS SUCH AS THE


SE-704 USE THE CIRCUIT AT RIGHT. RESISTORS R1 AND
R2 WILL LOWER TEST CURRENT TO 10% OF SE-400 SETTING.
2. FOR A TEST CURRENT HIGHER THAN 9.9 A, USE MULTIPLE
OUTPUT-CONDUCTOR WRAPS THROUGH THE CT WINDOW.

FIGURE 3. Typical Connection Diagrams.

REMOTE
TEST

8
9

OP2

L1
L2

NOTE:

SE-704

R2
11

RMT1

SE-400

RMT1
RMT2

R1 = 1 , 10 W, 1%
R2 = 0.1 , 10 W, 1%
ITEST = 1/10 SE-400 SETTING

12

Page 4
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit


6. TECHNICAL SPECIFICATIONS
Supply :
120 Vac ............................... 80 VA, 120 Vac,
(+12, -30%), 50/60 Hz
240 Vac ............................... 80 VA, 240 Vac,
(+12, -30%), 50/60 Hz
Fuse Rating (F1) ....................... 1 A, 250 Vac
Fuse Part Number ..................... Littelfuse 313.001 or
Bussman AGC1
Output:
Current Setting .................... 0.5 to 9.9 A,
0.1-A increments
Duration Setting .................. 0.1 to 9.9 s,
0.1-s increments
or continuous
Maximum Burden ............... 0.13 ohms
Voltage ............................... 5.0 Vac maximum
Duty Cycle at 25C (77F):
12 VA............................... Continuous
34 VA Maximum ............. 15 minutes ON
30 minutes OFF
Accuracy ............................. 3%
PWB Conformal Coating ......... MIL-1-46058 qualified,
UL QMJU2 recognized
Dimensions:
Height ................................. 212.7 mm (8.4)
Width .................................. 104.0 mm (4.1)
Depth .................................. 142.9 mm (5.6)
Shipping Weight ....................... 2.2 kg (4.8 lb)
Environment:
Operating Temperature ....... -40 to 60C (-40 to
140F)
Storage Temperature........... -55 to 80C (-67 to
160F)

7. ORDERING INFORMATION
SE-400-

BLANK 120-Vac Supply


02 240-Vac Supply

SE-410 ......................................... Selector Switch


SE-400IRC .................................. Impact Resistant Case

8. WARRANTY
The SE-400 Ground-Fault-Relay Test Unit is warranted
to be free from defects in material and workmanship for a
period of five years from the date of purchase.
Littelfuse Startco will (at Littelfuse Startcos option)
repair, replace, or refund the original purchase price of an
SE-400 that is determined by Littelfuse Startco to be
defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care. Littelfuse Startco does not warrant products repaired
or modified by non-Littelfuse Startco personnel.

Page 5
Rev. 1-A-072115

SE-400 Ground-Fault-Relay Test Unit

MANUAL
RELEASE DATE
July 21, 2015

APPENDIX A
SE-400 REVISION HISTORY
MANUAL
PRODUCT REVISION
REVISION
(REVISION NUMBER ON PRODUCT LABEL)
1-A-072115

MANUAL REVISION HISTORY


REVISION 1-A-072115
SECTION 5
Fig. 3 updated.
SECTION 6
Voltage and accuracy specifications added.
APPENDIX A
Revision history added.

PRODUCT REVISION HISTORY


PRODUCT REVISION 05B
Current release.

05B

SE-400 Ground-Fault-Relay Test Unit

This page intentionally left blank.

Page 6