SE-400 MANUAL
GROUND-FAULT-RELAY TEST UNIT
Revision 1-A-072115
LITTELFUSE STARTCO
GROUND-FAULT-RELAY TEST UNIT SE-400
AMPERES
THERMAL
LIMIT
USE SWITCHES LABELLED AMPERES TO SET
MAGNITUDE (0.5 TO 9.9 A) OF OUTPUT CURRENT.
USE SWITCHES LABELLED SECONDS TO SET
DURATION (0.1 TO 9.9 s) OF OUTPUT CURRENT.
PRESS TEST TO INITIATE OUTPUT CURRENT.
DISPLAY INDICATES MAGNITUDE OF OUTPUT
CURRENT FOR DURATION OF OUTPUT.
SET SWITCHES LABELLED SECONDS TO 0.0 FOR
MANUAL CONTROL OF OUTPUT DURATION.
PUSH TEST TO SWITCH OUTPUT ON OR OFF.
AMPERES
2
SECONDS
0.5
TO
9.9
0.1
TO
9.9
TEST
Page i
Rev. 1-A-072115
TABLE OF CONTENTS
SECTION
PAGE
1
2
General ................................................................. 1
Operation ............................................................. 1
2.1 Front-Panel Controls ............................................. 1
2.1.1 Amperes ..................................................... 1
2.1.2 Seconds ...................................................... 1
2.1.3 Test ............................................................ 1
2.2 Indication .............................................................. 1
2.3 Thermal Limit ....................................................... 1
3
Installation ........................................................... 1
4
Test Procedure .................................................... 1
5
Troubleshooting .................................................. 1
6
Technical Specifications...................................... 4
7
Ordering Information ......................................... 4
8
Warranty ............................................................. 4
Appendix A SE-400 Revision History ........................... 5
LIST OF FIGURES
FIGURE
1
2
3
PAGE
DISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a
result of a malfunction, incorrect application, or incorrect
adjustment.
Page ii
Rev. 1-A-072115
Page iii
Rev. 1-A-072115
Page 1
Rev. 1-A-072115
3. INSTALLATION
2. OPERATION
2.1 FRONT-PANEL CONTROLS
2.1.1 AMPERES
The AMPERES switch has four push buttons and a
two-digit numeric indicator to adjust current output to
the desired value. The range is 0.5 to 9.9 A. If a value
below 0.5 is selected, there will be no output.
2.1.2 SECONDS
The SECONDS switch has four push buttons and a
two-digit numeric indicator to adjust output duration.
The range is 0.1 to 9.9 s, or select 0.0 for continuousoutput operation.
2.1.3 TEST
Press TEST for an output burst of the magnitude and
duration selected by AMPERES and SECONDS. Press
TEST again to stop a continuous-output operation.
2.2 INDICATION
The two-digit LED display indicates the magnitude of
the output current for the duration of the output burst.
The centre decimal point serves as a supply voltage
indicator. A decimal point on the right side of the
display is used to indicate a thermal-limit condition.
2.3 THERMAL LIMIT
When the SE-400 is used in the continuous-output
mode, the internal circuit temperature can reach the
thermal-limit temperature. To prevent damage to the
SE-400, the current output is disabled and the thermallimit indicator turns on. The output remains disabled
until the temperature has fallen to a safe level, at which
time the thermal-limit indicator turns off and the output
is enabled.
4. TEST PROCEDURE
Set the required output current level0.5 to 9.9 A.
The recommended test current is 120% of the groundfault trip level of the device being tested.
Set the output duration0.1 to 9.9 s or 0.0 for push-on
push-off operation.
Press the TEST button. The ground-fault unit(s) being
tested should trip.
5. TROUBLESHOOTING
Problem:
No current output when the TEST button is pressed.
Possible Causes:
Troubleshooting:
Check the SE-400 operation by connecting a short
length of wire across the output terminals and
pressing the TEST button.
If using a remote test switch, check remote switch
operation and connection to the SE-400.
Page 2
Rev. 1-A-072115
3.4
(0.13)
3.2
(0.12)
139.7
(5.50)
104.0
(4.09)
91.7
(3.61)
LITTELFUSE STARTCO
GROUND-FAULT-RELAY TEST UNIT SE-400
1
2
3
4
5
6
7
8
9
10
11
12
212.7
(8.37)
218.4
(8.60)
F1
AMPERES
L1
L2
THERMAL
LIMIT
USE SWITCHES LABELLED AMPERES TO SET
MAGNITUDE (0.5 TO 9.9 A) OF OUTPUT CURRENT.
R MT 1
R MT 2
OP 1
OP2
AMPERES
SECONDS
0.5
TO
9.9
0.1
TO
9.9
TEST
PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)
NOTES:
M4 OR 8-32 TAP
(NOTE 2)
6.4
R=2. 2 (0.09)
1. DIMENSIONS IN MILLIMETRES
(INCHES).
2.5
(0.10)
2.5
(0.10)
2.5
(0.10)
195.0
(7.68)
200.0
(7.87)
212.7
(8.37)
203.2
(8.00)
2. MOUNTING SCREWS:
M4 x 10 OR 8-32 x 0.375.
(0.25)
98.4
(3.87)
93.3
(3.67)
76.2
(3.00)
2.5
(0.10)
63.5
(2.50)
5.0
(0.20)
14.1
(0.56)
FRONT VIEW
SIDE VIEW
REAR VIEW
REAR PANEL
OUTLINE
SURFACE MOUNT
R=4. 8 (0.19)
MAXIMUM
8.2
(0.32)
8.2
(0.32)
PANEL-MOUNT CUTOUT
6.4
(0.25)
2.5
(0.10)
BEZEL
OUTLINE
Page 3
Rev. 1-A-072115
STEP 2
STEP 3
1
2
3
4
5
6
7
8
9
10
11
12
2 L1
3
4 L2
5
6
T1
7 R MM T 2
8 R
9
1
1 0 1 O PP 2
1 2 O
1
1
2
3
4
5
6
7
8
9
10
11
12
L1
L2
R MT 1
R MT 2
OP 1
OP2
L1
L2
R MT 1
R MT 2
OP 1
OP2
SE-CS30
NEUTRAL
FROM
POWER
SOURCE
LOAD
TO SE-330
4
NGR
L
N
11
3
5
OP1
REMOTE
TEST
12
R1 L
L1
L2
1
8
OP2
N
ITEST
TO SENSING
RESISTOR
TERMINAL N
SE-400
11
10
RMT2
S1 S2
L1
L2/N
3
5
OP1
REMOTE
TEST
8
9
OP2
L1
L2
NOTE:
SE-704
R2
11
RMT1
SE-400
RMT1
RMT2
R1 = 1 , 10 W, 1%
R2 = 0.1 , 10 W, 1%
ITEST = 1/10 SE-400 SETTING
12
Page 4
Rev. 1-A-072115
7. ORDERING INFORMATION
SE-400-
8. WARRANTY
The SE-400 Ground-Fault-Relay Test Unit is warranted
to be free from defects in material and workmanship for a
period of five years from the date of purchase.
Littelfuse Startco will (at Littelfuse Startcos option)
repair, replace, or refund the original purchase price of an
SE-400 that is determined by Littelfuse Startco to be
defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care. Littelfuse Startco does not warrant products repaired
or modified by non-Littelfuse Startco personnel.
Page 5