Beruflich Dokumente
Kultur Dokumente
Transcript
Slide 1
Welcome to the Data Center UniversityTM course on Generator Fundamentals.
Slide 2: Welcome
For best viewing results, we recommend that you maximize your browser window now. The screen controls
allow you to navigate through the eLearning experience. Using your browser controls may disrupt the
normal play of the course. Click the Notes tab to read a transcript of the narration.
Slide 3: Learning Objectives
At the end of this course you will be able to:
Identify the main components of a standby generator
Explain the functions of a standby generators prime mover, the alternator and governor
Describe the various fuel types utilized by standby generators
Identify resources for on-site power technology guidelines
Slide 4: Introduction
Consider these statistics. According to Contingency Planning Research power related events such as
blackouts and surges account for 31% of computer downtime episodes lasting more than 12 hours, power
failure and surges account for 45.3% of data loss, and according to IDC power disturbances account for
about 33% of all server failures. A standby generator is one critical equipment component that will keep you
from becoming one of these statistics. Understanding the basic functions and concepts of standby
generator systems helps provide a solid foundation allowing IT professionals to successfully specify, install,
and operate critical facilities. This course is an introduction to standby generators and the subsystems that
power a facilitys critical electrical loads when the utility cannot.
Generator Fundamentals
Page |1
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Generator Fundamentals
Page |2
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
It is referred to as a 4-stroke engine because of the four distinct stages that occur in the combustion cycle.
These stages include intake of the air/fuel mixture, compression of that mixture, combustion or explosion,
and exhaust. When referring to generators, the 4-stroke engine is generally referred as the prime mover.
The following slide describes the core attributes of the prime mover.
Slide 8: Fuel
There are four main fuels used to power generators. These include diesel, natural gas, liquid petroleum
(LP), and gasoline. The selection of a fuel type depends on variables such as storage, cost, and
accessibility. Generator systems with diesel or natural gas engines are the most common standby power
generators utilized to support data centers. Fuel availability generally dictates the type of standby generator
selected. For example, if a generator is located in an isolated area where public utilities are not available, LP
or diesel fuel are logical choices. Additionally, the generators fuel type, as well as the magnitude of potential
step-load changes, or whether the generator will be expected to support an instantaneous change in load
current, from zero to full load for example, will influence the selection of the governor. Because these
factors contribute to the accuracy and stability of the prime movers speed, they must be considered in the
overall design.
Lets review some of the advantages and disadvantages of the different fuel types.
Generator Fundamentals
Page |3
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 9: Diesel
Diesel fuel is often chosen in many applications because of easy onsite storage, fewer problems with long
term storage, reduced fire hazard, and more operating hours between overhauls. Disadvantages to using
diesel fuel are its low volatility at low ambient temperatures and diesel does not burn as cleanly as natural
gas or liquid petroleum and therefore it has potential harmful affects on the environment.
Slide 10: Natural Gas
Natural gas is used quite often due to its numerous advantages. Natural gas is a clean burning fuel with less
exhaust emissions and the exhaust is less harmful to the environment than diesel. Because natural gas is a
cleaner fuel there is minimum carbon build up and cleaner crankcase oil. Additionally, there are no fuel
storage problems, and there is less engine maintenance then diesel or gasoline generators. The
disadvantages of using natural gas are the high cost. Gas generators tend to cost more that other generator
types and you are also limited in the size of the generator. Natural gas is provided by a single source, its
regulated by the pipeline it is connected to. Subsequently, during emergencies, gas lines can get sucked dry
by other consumers and if you're towards the end of the line, you might not be able to get supply. Safety is
also another factor. If there are leaks it has a high explosive capability. Lastly, energy content of natural gas
is lower than most other fuel sources, so you need more of it to generate electricity for you generator.
Slide 11: Liquid Petroleum
The advantages of using a generator powered by liquid petroleum are similar to those of natural gas. Its a
clean burning fuel with less environmental impact than diesel, and the exhaust is less harmful to the
environment. Additionally, there are no fuel storage problems, and there is less engine maintenance then
diesel or gasoline generators. The biggest disadvantage to using a liquid petroleum powered generator is
that Liquid petroleum presents the greatest hazard. If any liquid petroleum vapors are leaked or released,
being heavier than air, the liquid petroleum will flow to low areas such as basements and potentially create
an explosion hazard.
Generator Fundamentals
Page |4
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Page |5
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
long runtime must be supported. This is because fuel lines and filters can be isolated and changed while
the engine remains running. Not having spare parts for filters and other "consumables" can result in
downtime. Proactive monitoring of these filters is done with Differential Pressure Indicators. They show the
pressure difference across a filter or between two fuel lines during engine operation. When applied to air
filters, these proactive monitoring devices are known as Air Restrict Indicators. These provide a visual
indication of the need to replace a dry-type intake air filter while the generator engine runs.
Slide 16: Starter motor
The last component of the prime mover that we will be discussing is the starter motor. As shown in this
illustration, the starter motor system is one of the most critical elements to the successful use of a generator.
The majority of generator systems use a battery-operated starter motor, as in automotive applications,
although pneumatic or hydraulic alternatives are sometimes found on the heaviest prime movers. The
critical element in the conventional starter is clearly the battery system. For example, the battery-charging
alternator present on some engines does nothing to prevent battery discharge during the unused periods.
Providing a separate, automatic charging system with remote alarm is considered a "best practice. It is
also essential to keep the battery warm and corrosion-free.
Generator Fundamentals
Page |6
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Engine block heaters also contribute to the startup success rate by reducing the frictional forces that the
starter motor must work against when energized. Numerous studies have found startup failures to be the
leading cause of generator system failures.
Slide 17: Starter motor
When considering a standby generator, the minimum time to detect a power problem, start the prime mover,
establish stable output frequency and voltage, and connect to loads is usually at least 10-15 seconds.
However, many systems in use today do not reliably perform to this very quick deployment due to such
factors as uncharged or stolen batteries. Other factors include improper maintenance and human error.
Conscientious maintenance and design of a starter motor is absolutely critical to achieving a respectable
success rate for generator startup systems.
Slide 18: The Alternator: The Electrical Generation Component
The alternator is another critical component of the generator. The main function of the alternator is to
convert mechanical energy from the prime mover into alternating current. This is similar to the alternator in
an automobile, however in an automobile it is usually driven by a belt, whereas in a generator it is driven by
the main drive shaft of the prime mover. Through the years, certain characteristics of alternator components
have been improved to increase the efficiency, capacity and reliability of the alternator.
Lets start by looking at some of these improvements used in todays data center generators.
Slide 19: Brushless and Self Excited Alternators
The following diagram illustrates a cross sectional view of a self excited, externally regulated, brushless
alternator.
Generator Fundamentals
Page |7
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
The brushless designation refers to the fact that this design requires no contacts be placed against any
revolving parts to transfer electrical energy to or from the components. Brushes in motors and very small
generators may still be an acceptable design, but predictably the brushes wear out with use, and are
impossible to inspect in a proactive manner. A large generator design that relies on brushes is not up to the
reliability standards needed for mission-critical operation. When a generator is described as self excited it
means that the electricity used to create the electromagnetic field is created within the alternator itself
thereby allowing the alternator to produce large amounts of electricity with no other energy then what is
provided by the prime mover.
Slide 20: Main Stator/ Armature Windings
The Main Stator or Armature Windings are the stationary coils of wire where the electricity for the critical
loads begins to be generated. The characteristics of the alternating current produced are related to the
quantity and geometry of the coil windings. A large variety of configurations are available to deliver
combinations of ampacity and voltage requirements.
Generator Fundamentals
Page |8
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Generator Fundamentals
Page |9
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Generator Fundamentals
P a g e | 10
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
The ATS also re-transfers the load to utility when normal conditions are restored. Other common features of
ATS related equipment includes automatic generator test scheduling and monitoring of important cool-down
Generator Fundamentals
P a g e | 11
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
cycles for the generator after the utility is restored. Traditionally this hardware is sourced from a variety of
vendors, including the generator manufacturers, distribution switchgear manufacturers, and specialists in
ATS design.
Slide 26: Grounding
When considering the best practices for a generator proper grounding should be first on the list. Grounding
is a necessity when it comes to both safety and the reliability of a generator. Grounding performs such
critical functions as:
Preventing the shock or electrocution of maintenance or repair technicians
Ensuring that circuit breakers trip before electrical malfunctions develop into fires and
Provide a low-impedance path for internal processing signals
Slide 27: Air & Noise Pollution
One key issue when discussing generators is that of air and noise pollution. Environmental laws, building
permits, and duration of generator use vary considerably by locale. For example, if the facility is located in a
stringent area, the generator system declarations on emissions may be required when applying for permits.
Industry professionals are usually experienced with the approval process in the locations they serve. As we
had discussed earlier, generators are very similar to automobiles engines. Just as automobile noise and
exhaust is a significant issue, so is the noise and air pollution caused by a generator. While the concept of
minimizing noise and ducting exhaust air is straightforward, the environmental and regulatory issues are not.
Slide 28: Noise Pollution
Local ordinances on noise pollution typically dictate the highest recordable background noise allowed in a
24-hour period. Exhaust mufflers are generally categorized as industrial, residential, or critical. Critical
offers the highest level of sound reduction. To spare the expense of a retrofit design, one should consider
the noise rating of the system prior to purchase and have these numbers qualified by the zoning authority in
the planning stages. Mechanical vibration also contributes to the overall noise level and the perception of
noise for occupants in the surrounding area. Mounting and isolation techniques exist to minimize this
concern.
Generator Fundamentals
P a g e | 12
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Now that we have explored the topic of environmental pollution lets a take a closer look at a few
organizations that set the regulatory standards for standby generators.
Slide 29: Regulations
In the United States, the Federal Environmental Protection Agency (EPA) has delegated to each state the
jurisdictional authority and discretion on how to achieve air quality goals established on the national level.
Other countries have similar regulatory bodies that set limits on generator emissions. For instance, Defra
(Department for Environment Food and Rural Affairs) sets policies for environmental protection in the United
Kingdom. And in India, the Ministry of Environment and Forests (MoEF) plays this role. In addition, there
are worldwide organizations that offer a wealth of information about emissions and other standby generator
considerations. One such organization is the EGSA (Electrical Generating Systems Association). EGSA
serves as a source of information, education, and training and develops performance standards for on-site
power technology.
Slide 30: Aesthetics
Another important consideration for generators is that of aesthetics. Some municipalities have requirements
in terms of placement of the generator, including that it be housed within concrete block walls that match the
main buildings appearance. This keeps the generator from being noticed and keeps it aesthetically neutral
to the surrounding neighborhood. Now that we have discussed some of the regulatory issues of standby
generators, lets look more closely at some key maintenance measures that ensure optimal performance.
Slide 31: Maintenance Measures
Maintenance is the key to ensuring the seamless operation of your generator. As we have mentioned
throughout the course there are many different way in which you can optimize your standby generator.
When you consider the fact that malfunctions can be almost completely eliminated, with the proper
preventative maintenance, the importance of such preventative steps hits home.
Generator Fundamentals
P a g e | 13
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Here are a few steps to take to ensure that your generator is ready when you need it.
Its important to note that a good preventative maintenance program is going to require shutting off
all power for approximately 10-20 hours once a year. This will help to check the tightness of all
medium voltage (MV) and switchgear terminations
If a total shut down is not a possibility, thermal imaging can be used to detect any hot spots caused
by electrical terminations and connections
The trip setting of major circuit breakers should be tested
Transformers and cables should be tested, and lastly
Coolant samples should be taken for signs of insulation deterioration
Slide 32: Maintenance Measures
Additionally, a management system that monitors all generator subsystems and provides early warning
through preventative maintenance reminders is a great way to ensure reliability. Here are a few key
preventative maintenance initiatives that can be taken to ensure reliability of your generator:
Coolant hoses, coolant level, water pump operation, and antifreeze protection must be diligently
reviewed for acceptable performance.
Real time remote and local monitoring system that provides critical information and alarms at every
interface
Battery monitoring and weak battery detection
An automatic alarm that is sent whenever the controller is not set to automatic, the emergency stop
is engaged, or the generator output breaker is not closed
Block temperature and coolant level monitoring and alarms
Fuel level and load power measurements, available even when the generator is in standby
Oil level monitoring so that oil can be added or leaks repaired, rather than waiting for the generator
to start and shutdown due to low pressure
Generator Fundamentals
P a g e | 14
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Generator Fundamentals
P a g e | 15
2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.