Sl. No.
1
2
3
4
EQUIPMENT
MDBFP
PA Fan
CW Pump
FD FAN
Rating (kW)
12000 kW, 11 kV
4200 kW, 11 kV
2250 kW, 11 kV
1425 KW, 3.3kV
Board
(TYP)
11
11
11
3.3
Station
Unit
Unit
Unit Aux.
Revision
Purpose
0
0
0
0
Relay Settings
Relay Settings
Relay Settings
Relay Settings
Date
09-05-2013
09-05-2013
09-05-2013
09-05-2013
Digitally signed by
Shekhar
DN: CN = Shekhar, C =
IN, O = Jindal Power
Limited, OU = Gurgaon
Reason: CAT-04 : The
document is approved
under CAT-04.
Location: Gurgaon
Date: 2013.05.09
15:38:33 +05'30'
Sl. No.
Rev
1
Revision History
Date
Person
0 09-05-2013 Shekhar
Purpose
Relay Setting- P122
S.No.
Description
Motor Name
1 Motor Name
MDBFP
2 Motor Rating
12000 kW, 11 kV
4200 kW, 11 kV
Station Switchgear
3RX3CX300 mm2
1250
40 kA for 3 sec
Unit Switchgear
3CX300 mm2
1250
40 kA for 3 sec
Unit Switchgear
3CX185 mm2
1250
40 kA for 3 sec
CT-1, Core-1
1000
1
PS
10
40 kA for 1 sec
10
350
CT-1, Core-1
400
1
PS
10
40 kA for 1 sec
4
500
CT-1, Core-1
200
1
PS
10
40 kA for 1 sec
3
450
CT-1, Core-1
400
1
PS
10
40 kA for 1 sec
4
270
251
48
150
64
306
85
3
4
5
6
6a
6b1
6b2
6c
6d
6e
6f1
6f2
7
7a
7b
8
8a1
8a2
8b1
8b2
8c1
8c2
9a
9b
10
11
11a
11b
11c
12
PA Fan
720
130
3
4.5
9.9
4.75
4.6
5.5
3.5.2.4
3.5.2.5
3.5.5.1
Rev00
4.5
6
7.5
6.7
3.5
4.75
3
1.5
NA
6
4.4
6.5
1.2
3.6
23 / 15 / 12
31 / 20 / 16
PA Fan
1000/1
400
1
-
EDGE
1
EDGE
1
Inst. Self-reset ?
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Alarm Battery
[50/51] Phase OC sub-menu
PROTECTION G1
[50/51] Phase OC
I> ?
I>
Yes
Yes
144
Delay Type
3.5.5.1.1
Delay Type
tI >
t Reset
3.5.5.1.2.1
t Reset
3.5.5.1.4
I>> ?
I>>
Delay Type
tI >>
t Reset
3.5.5.1.5
I>>> ?
I>>> Sample
I>>>
Selection of the I>>> third threshold current value is adjustable from 0.5 to 40 In.
DMT
Yes
50.2
DMT
DMT
Yes
30
DMT
DMT
306
50
1118
400/1
200
1
EDGE
1
3
2
1
FD FAN
200/1
400
1
EDGE
3
2
1 30 / 120
NA
150
50
871
CW Pump
400/1
1000
1
7.5
6
CT RATIO sub-menu
CONFIGURATION
CT Ratio
Line CT primary
Line CT sec
E/Gnd CT primary
E/Gnd CT sec
Group. Select sub-menu
CONFIGURATION
Group Select
Change Group
Input
Setting Group
Alarms sub-menu
CONFIGURATION
Alarms
FD FAN
13.5
6
MDBFP
3.5.2.2
CW Pump
61.2
DMT
DMT
DMT
0.1
0
0.1
0
0.1
0
0.1
0
NO
NO
NO
NO
NO
NO
NO
NO
Digitally signed by
Shekhar
DN: CN = Shekhar,
C = IN, O = Jindal
Power Limited, OU
= Gurgaon
Reason: CAT-04 :
The document is
approved under
CAT-04.
Location: Gurgaon
Date: 2013.05.09
15:38:46 +05'30'
Page 1 of 2
S.No.
Description
Motor Name
1 Motor Name
3.5.5.2
tI >>>
[50N/51N] EARTH OC sub-menu
PROTECTION G1
[50N/51N] E/Gnd
3.5.5.4
3.5.5.5
PA Fan
CW Pump
FD FAN
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
no
no
no
no
no
no
no
no
no
no
no
no
le >
Delay Type
3.5.5.2.1
Delay Type
tI >
t Reset
3.5.5.2.2
Delay Type
Selection of the Ie> time delay. Select the time delay from 0
to 150 s
Selection of the t Reset value from 0 to 600 s
Ie> IDMT threshold, IEC or IEEE/ANSI curve menu
Display the Ie> inverse time delay (IEC or IEEE/ANSI curves).
Idmt
Tms
3.5.5.2.2.1
t Reset
3.5.5.2.4
Selection of the Ie> curve. Select from IEC SI, IEC STI, IEC VI, IEC EI, IEC LTI, CO2, IEEE MI,
CO8, IEEE VI, IEEE EI
Select the curve TMS value. Select from 0.025 to 1.5
additional Ie> DMT reset time, IEC curves menu
Selection of the t Reset value from 40 ms to 100 s
Ie>> threshold menu
Ie>> ?
Ie>>
The threshold Ie>> is adjustable from : 0.002 to 1Ien (0.002 to 1 Ien Range)
0.01 to 8 Ien (0.01 to 8 Ien Range), and 0.5 to 40 Ien(0.1 to 40 Ion Range).
Delay Type
tIe>>
t Reset
3.5.5.2.5
Ie>>> ?
Ie>>> Sample
Ie>>>
tIe>>>
I2 > ?
I2 >
3.5.5.3.5
MDBFP
Ie> ?
3.5.5.3
Delay Type
[49] Therm OL sub-menu
PROTECTION G1
[49] Therm OL
Therm OL ?
[37] UNDERCURRENT I< sub-menu
PROTECTION G1
[37] Under Current
I<?
I<
tI <
[79] AUTORECLOSE sub-menu
PROTECTION G1
[79] Autoreclose
Autoreclose ?
Ext CB Fail ?
Ext CB Fail
Ext CB Fail Time
Rev00
Page 2 of 2