62.1:3610
November 2015
D200064X012
ELECTROPNEUMATIC
CONVERTER
X1284
W4920-1
www.Fisher.com
Product Bulletin
62.1:3610
November 2015
D200064X012
Specifications
Electromagnetic Compliance for 3622
electro-pneumatic converter:
Meets EN 61326-1:2013
ImmunityIndustrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 2 below.
EmissionsClass A
ISM equipment rating: Group 1, Class A
Available Configurations
Refer to the type number description on page 6
Input Signal
3610J or 3610JP:
Standard: J 0.2 to 1.0 bar (3 to 15 psig), J 0.4 to 2.0
bar (6 to 30 psig), or J split range, see table 1.
Adjustable: Zero is adjustable from 0.07 to 1.5 bar
(1 to 22 psig) for standard valve rotations. Span is
adjustable from 0.2 to 2.0 bar (3.2 to 28.8 psi) for
standard valve rotations. Location of adjustments are
shown in figure 2.
3620J and 3620JP:
4-20 mA DC constant current with 30 VDC maximum
compliance voltage. Minimum terminal voltage is
2.4 VDC at 20 mA. Split range is also available,
see table 1.
Output Signal
Pneumatic pressure as required by the actuator up to
full supply pressure
Action(1): Field-reversible between J direct and
J reverse within the pneumatic positioner
Operating Influences
Supply Pressure Sensitivity: A 10% change in supply
pressure changes the valve shaft position less than
the following percentages of valve rotation:
3610J and 3620J: 1.0% at 1.4 bar (20 psig) supply
pressure
3610JP and 3620JP: 1.5% at 4.1 bar
(60 psig) supply pressure
Equivalent Circuit
3620J and 3620JP: 120 ohms shunted by three 5.6 V
zener diodes
Typical Performance
Independent Linearity:
Direct-Acting 3610J and 3620J: 1.5% of output span
Reverse-Acting 3610J and 3620J: 0.75% of output span
Direct-Acting 3610JP and 3620JP: 1.25% of output
span
Reverse-Acting 3610JP and 3620JP: 0.5% of output
span
Hysteresis:
3610J: 1.0% of output span
3620J: 0.75% of output span
3610JP: 0.5% of output span
3620JP: 0.6% of output span
Deadband: 0.1% of input span
Supply Pressure(3)
Minimum Recommended: 0.3 bar (5 psig) above
actuator requirement [1.4 bar (20 psig) for a 0.2 to
1.0 bar (3 to 15 psig) nominal actuator signal; 2.4 bar
(35 psig) for a 0.4 to 2.0 bar (6 to 30 psig) nominal
actuator signal].
Maximum: 10.3 bar (150 psig) or maximum pressure
rating of the actuator, whichever is lower.
Supply Medium: Air or Natural Gas
3620J and 3620JP are not approved for use with
natural gas as the supply medium
- continued -
Product Bulletin
62.1:3610
November 2015
D200064X012
Specifications (continued)
Steady-State Air Consumption(2)
Construction Materials
All Positioners:
Case: Low copper aluminum alloy
Cover: Polyester plastic
Feedback Lever: Stainless steel
Range Spring: Zinc-plated steel
Input Module and Relay Diaphragms: Nitrile and
polyester
Relay Valve Plugs and Seats: Stainless steel
Tubing: Copper (standard)
Fittings: Brass (standard)
Gauges: Chrome-plated brass connection with plastic
case
3620J and 3620JP:
Housing and Cap: Low copper aluminum alloy
Pressure Connections
1/4 NPT internal
Product Bulletin
62.1:3610
November 2015
D200064X012
Specifications (continued)
Rotary Valve Rotation
Options
3610J and 3610JP:
J Supply pressure gauge, J tire valves, or J plugs,
J Integral mounted bypass valve on 3610J only
Characterized Cams
Approximate Weight
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. For direct action, an increasing input signal extends the actuator rod. For reverse action, an increasing input signal retracts the actuator rod.
2. Normal m3/hr--normal cubic meters per hour (0_C and 1.01325 bar absolute). Scfh--standard cubic feet per hour (60_F and 14.7 psia).
3. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
Split
Bar
Psig
Bar
Psig
Two-way
0.2 to 0.6
0.6 to 1.0
3 to 9
9 to 15
0.4 to 1.2
1.2 to 2.0
6 to 18
18 to 30
Three-way
0.2 to 0.5
0.5 to 0.7
0.7 to 1.0
3 to 7
7 to 11
11 to 15
3620J AND 3620JP POSITIONERS(1)
0.4 to 0.9
0.9 to 1.5
1.5 to 2.0
6 to 14
14 to 22
22 to 30
Split
Two-way
4 to 9.3
9.3 to 14.7
14.7 to 20
Three-way
1. This table is only valid for the following standard valve rotations/range spring combinations: 90_/18A7845X012 (blue), 75_/18A7846X012 (yellow), and 60_/18A5118X012 (red). Contact
your Emerson Process Management sales office or the factory for input signal ranges not listed.
Phenomenon
Electrostatic Discharge (ESD)
Enclosure
Radiated EM field
Rated power frequency
magnetic field
Burst (fast transients)
Basic Standard
Test Level
IEC 61000-4-2
4 kV contact; 8 kV air
IEC 61000-4-3
IEC 61000-4-8
60 A/m at 50 Hz
IEC 61000-4-4
1 kV
IEC 61000-4-5
IEC 61000-4-6
Performance
Criteria(2)
Product Bulletin
62.1:3610
November 2015
D200064X012
COARSE SPAN
ADJUSTMENT
MINOR LOOP
GAIN
ADJUSTMENT
FINE SPAN
ADJUSTMENT
W3783
W4900-1
Features
nAccurate, Efficient, Vibration-Resistant
Product Bulletin
62.1:3610
November 2015
D200064X012
RELAY BEAM
SUPPLY PRESSURE
NOZZLE PRESSURE
INPUT SIGNAL
RELAY
B
RELAY
A
OUTPUT SIGNAL
OUTPUT SIGNAL
MINOR LOOP
GAIN ADJ
AIR
SUPPLY
ZERO ADJ
RANGE SPRING
COARSE
SPAN
ADJ
FINE
SPAN
ADJ
COUNTER SPRING
SUMMING BEAM
FLAPPER
PIVOT
B
PIVOT A
NOZZLE
FIXED
RESTRICTION
AIR SUPPLY
CAVITY A
CAVITY B
INPUT SIGNAL
PRESSURE
POSITIONER CAM
INPUT MODULE
FEEDBACK
LEVER
PISTON
ACTUATOR
END VIEW OF
ROTARY SHAFT
38A8900-B
B1845-1
Type Number
Description1
The following descriptions provide specific
information on the different positioner constructions.
3610J: A single-acting pneumatic rotary valve
positioner for use with Fisher 1051 and 1052
actuators.
3610JP: A double-acting pneumatic rotary valve
positioner for use with Fisher 1061 and 1069
actuators.
3620J: A single-acting electro-pneumatic rotary valve
positioner for use with 1051 and 1052 actuators.
Principle of Operation
3610J positioners accept a pneumatic input signal and
3620J positioners accept a DC current input signal
from a control device.
Product Bulletin
62.1:3610
November 2015
D200064X012
FOR 3620JP
ONLY
SUPPLY PRESSURE
NOZZLE PRESSURE
MINOR LOOP
GAIN ADJ
INPUT SIGNAL
RELAY
B
RELAY
A
OUTPUT SIGNAL
AIR
SUPPLY
ZERO ADJ
OUTPUT SIGNAL
RANGE SPRING
COARSE
SPAN
ADJ
FINE
SPAN
ADJ
COUNTER SPRING
SUMMING BEAM
FLAPPER
PIVOT A
PIVOT
B
NOZZLE
FIXED
RESTRICTION
INPUT MODULE
CAVITY A
CAVITY B
FEEDBACK
LEVER
POSITIONER
CAM
CONVERTER
MODULE
PISTON
ACTUATOR
SUPPLY
END VIEW OF ROTARY SHAFT
38A8900-B
B2148
Product Bulletin
62.1:3610
November 2015
pressure, continues to increase until the summing
beam torques are in equilibrium. At this point, the
valve shaft is in the correct position for the specific
input signal applied.
For reverse action, input signal pressure is channeled
to both cavities A and B. An increase in signal pressure
results in an upward force on the summing beam,
pivoting the summing beam clockwise and causing
relay B to exhaust upper actuator cylinder pressure to
atmosphere and relay A to increase lower actuator
cylinder pressure. As a result, the actuator rod retracts
and the actuator rotary shaft rotates
counterclockwise. This causes the feedback arm to
pivot counterclockwise reducing the force applied to
the summing beam by the range spring.
As the valve shaft rotates counterclockwise, the range
spring force to the summing beam continues to
reduce until the summing beam torques are in
equilibrium. At this point, the valve shaft is in the
correct position for the specific input signal applied.
3620J or 3620JP positioners (figure 4) are a
combination of a 3610J or a 3610JP positioner with a
3622 electro-pneumatic converter. The
electro-pneumatic converter provides a 0.2 to 1.0 bar
(3 to 15 psig) output pressure proportional to the
D200064X012
4-20 mA DC input signal. The 0.2 to 1.0 bar (3 to 15
psig) output pressure becomes the input signal
pressure to the 3610J or 3610JP pneumatic positioner.
Installation
The supply pressure medium must be a clean, dry, and
oil-free air, or noncorrosive gas (3610J positioners
only). If the supply pressure source is capable of
exceeding the maximum actuator operating pressure
or positioner supply pressure, appropriate steps must
be taken during installation to protect the positioner
and all connected equipment against overpressure.
Typical positioner mounting on an actuator is shown
on the front page. Overall dimensions are shown in
figure 5.
Note
3620J and 3620JP positioners are not approved for use with
natural gas as the supply medium.
Product Bulletin
62.1:3610
November 2015
D200064X012
140
(5.50)
49.3
(1.94)
OUTPUT A
CONNECTION
(PLUGGED ON
3610J) 1
208
(8.19)
OUTPUT B
CONNECTION
63.5
(2.50)
GAUGE
BLOCK
SUPPLY
CONNECTION
208
(8.19)
3622
17.5
(0.69)
100.1
(3.94)
63.5
(2.50)
19A1442-C
BYPASS
VALVE
OUTPUT B
CONNECTION
INSTRUMENT
CONNECTION
31.8
(1.25)
63.5
(2.50)
103
(4.06)
1/2 NPT
CONDUIT
CONNECTION
OUTPUT A
CONNECTION
(PLUGGED) 1
OUTPUT A
CONNECTION
(PLUGGED ON
3620J) 1
208
(8.19)
63.5
(2.50)
19A1444-B
GAUGE
BLOCK
100.1
(3.94)
119.1
(4.69)
57.2
(2.25)
110.2
(4.34)
SUPPLY
CONNECTION
OUTPUT B
CONNECTION 1
1
57.2
(2.25)
11B2612-C
SUPPLY
CONNECTION
110.2
(4.34)
Note:
1 Instrument, Output, and Supply connections are 1/4 NPT.
C0681-2
Product Bulletin
62.1:3610
November 2015
D200064X012
CAM
B
CAM
A
CAM
C
DIRECT
REVERSE
PERCENT OF FLOW
(PRESSURE DROP CONSTANT)
CAM
B
CAM
A
CAM
C
DIRECT
REVERSE
PERCENT OF FLOW
(PRESSURE DROP CONSTANT)
DIRECT
REVERSE
33A4960-A
A1582-2
33A4959-A
A1581-2
CAM
C
CAM
A
CAM
B
Ordering Information
When ordering, specify the product application and
construction:
Application
1. Positioner type number
Characterized Cams
4. Cam characteristic
10
5. Input signal
Construction
Product Bulletin
62.1:3610
November 2015
D200064X012
Table 3. Hazardous Area Classifications for Fisher 3622 Electro-Pneumatic Converter(1)CSA (Canada)
Certification Body
Certification Obtained
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591
Ex ia Intrinsically Safe
Class I, II Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28591
CSA
Entity Rating
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
Temperature Code
T4 (Tamb 82C)
T5 (Tamb 62C)
T6 (Tamb 47C)
Explosion-proof
Ex d IIC T5
Class I, Division 1, GP A,B,C,D T5
---
T5 (Tamb 82C)
Type n
Ex nA IIC T6
---
T6 (Tamb 82C)
T6 (Tamb 82C)
---
T5 (Tamb 82C)
T6 (Tamb 82C)
Table 4. Hazardous Area Classifications for Fisher 3622 Electro-Pneumatic Converter(1)FM (United States)
Certification Body
Certification Obtained
Intrinsically Safe
Class I Zone 0 AEx ia IIC T4/T5/T6 per drawing GE28590
Class I, II, III Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28590
FM
Entity Rating
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
Temperature Code
T4 (Tamb 82C)
T5 (Tamb 62C)
T6 (Tamb 47C)
Explosion-proof
Class I Zone 1 AEx d IIC T5
Class I, Division I, GP A,B,C,D T5
---
T5 (Tamb 82C)
Type n
Class I Zone 2 AEx nA IIC T5
---
T5 (Tamb 82C)
---
T5 (Tamb 82C)
Certification Obtained
Entity Rating
Temperature Code
II 1 G & D
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 Ga
Dust
Ex ia IIIC Da T120C (Tamb 82C)/ T100C (Tamb 62C) /
T85C (Tamb 47C)
T4 (Tamb 82C)
T5 (Tamb 62C)
T6 (Tamb 47C)
Ui = 30 VDC
Ii = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
---
II 2 G & D
ATEX
Flameproof
Gas
Ex d IIC T5 Gb
T5 (Tamb 82C)
---
Dust
Ex tb IIIC Db T82C (Tamb 79C)
---
II 3 G & D
Type n
Gas
Ex nA IIC T6 Gc
Dust
Ex tc IIIC Dc T85C (Tamb 82C)
T6 (Tamb 82C)
-----
11
Product Bulletin
62.1:3610
November 2015
D200064X012
Certification Obtained
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 Ga
IECEx
Flameproof
Gas
Ex d IIC T5 Gb
Type n
Gas
Ex nA IIC T6 Gc
Entity Rating
Ui = 30 VDC
Ii = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
Temperature Code
T4 (Tamb 82C)
T5 (Tamb 62C)
T6 (Tamb 47C)
---
T5 (Tamb 82C)
---
T6 (Tamb 82C)
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management,
Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
E
121983, 2015 Fisher Controls International LLC. All rights reserved.