General
Specications

Integrated Production Control


System CENTUM VP
System Overview (Vnet/IP Edition)

GS 33L01A10-40E

GENERAL

This document provides the overall system specications of the CENTUM VP Systems with Vnet/IP.

SYSTEM CONFIGURATION
Vnet/IP domain

SNTP
Server

Open
Display
Style
Console
HIS

Enclosed
Display
Style
Console
HIS

HIS
Human
Interface
Station

ProSafe-RS
Safety
Instrumented
System

PC for
engineering
(ENG)

SENG

L3SW
Layer 3 switch
Other
Vnet/IP
domains
L3SW
Layer 3 switch

Bus 1
Vnet/IP
Bus 2

SCS

SIOS
System
Integration
OPC Station
Other
PCS

GSGW
Generic
Subsystem
Gateway

APCS
Advanced
Process
Control
Station

V net router

FCS
(for FIO)
ESB bus
Other system
Local node

Other
V net
domains

ER bus
(Subsystem)
Remote node
F01E.ai

Figure Example of System Conguration

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33L01A10-40E
Copyright Feb. 2008 (YK)
9th Edition Jun. 2, 2010 (YK)

<<Contents>> <<Index>>

SYSTEM COMPONENTS
Human Interface Station (HIS)
An HIS serves as a human machine interface for
plant operators. Software packages are installed in a
general-purpose personal computer (an IBM PC/AT
compatible computer, hereinafter referred to as a
general-purpose PC). The HIS PC can be assembled
in the console box.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information on HIS hardware requirements,
see the following General Specications:
Enclosed Display Style Console Assembly
(GS 33M50B40-40E)
Open Display Style Console Assembly
(GS 33M50B50-40E)
Standard Operation and Monitoring Function
(GS 33M05D10-40E)
Vnet/IP Interface Card (GS 33L50C10-40E)

PC for Engineering (ENG)


This is a PC with engineering functions used to perform
CENTUM VP system generation and maintenance
management.
It can be the same type as the general-purpose PC for
the HIS, and can even be the same PC as the HIS.
By having HIS operation and monitoring functions on
the same PC, you can execute virtual test (control
station emulation) functions to provide an efcient and
easy-to-use engineering environment.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.

Field Control Station (FCS)


An FCS performs process control. Two types of eld
control stations are available:
AFV10S: Field Control Unit (for Vnet/IP, FIO, rackmounted)
AFV10D: Duplexed Field Control Unit (for Vnet/IP,
FIO, rack-mounted)
One eld control station has 8 slots for I/O modules,
and extra I/O expansion nodes can be also connected
via ESB bus or via ER bus.
For more information on the FCS hardware
requirements, see the following General Specications:
Field Control Unit (for Vnet/IP and FIO)
(GS 33L50E20-40E)
ESB Bus Coupler Module (GS 33M50E25-40E)
ER Bus Interface Master Module (for FIO)
(GS 33M50F25-40E)
Node Units (for FIO) (GS 33M50F20-40E)
FIO System Overview (for AFV10)
(GS 33L50F10-40E)

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

Generic Subsystem Gateway Station


(GSGW)
A GSGW can collect and set data of various types of
subsystems through OPC DA servers. No dedicated
communication program is required.
GSGW is a general-purpose PC with LFS1250 Generic
Subsystem Gateway Package.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information, see GSGW Generic Subsystem
Gateway Package (GS 33M20F10-40E).

Safety Control Station (SCS)


An SCS is a component of Safety Instrumented
Systems (ProSafe-RS). ProSafe-RS has been
approved by German safety test labs TV (Technische
berwachungs Verein) as the SIS (Safety Instrumented
System) that meets SIL (Safety Integrity Levels) 3
established by IEC 61508.
The SCS for ProSafe-RS monitors the state of plants
and performs predetermined safety operation according
to each request for safety control.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.

Safety Engineering PC (SENG)


An SENG is a PC with engineering functions for
ProSafe-RS such as editing, downloading and testing
applications as well as carrying out maintenance tasks
on safety control stations (SCSs).
The SENG functions can be installed in a PC that has
HIS or ENG functions.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information, see Safety Instrumented
Systems ProSafe-RS System Overview (for Vnet/IP)
(GS 32S51B10-01E).

System Integration OPC Station (SIOS)


System Integration OPC Station (SIOS) is a station
used to integrate other venders PCS (Process Control
System) to CENTUM VP system. SIOS enables HISs
to access the process data, alarms and events of other
venders PCSs through OPC DA and AE.
The SIOS is a general-purpose PC with LBC2100
System Integration OPC Client Package.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information, see System Integration OPC
Client Package (GS 33M20D10-40E).

Advanced Process Control Station (APCS)


An APCS advanced process control station implements
control functions with a general-purpose PC connected
to a Vnet/IP, aimed at improving advanced control and
plant efciency. The APCS requires LFS 1200 APCS
Control Functions (GS 33M15U10-40E) to be installed.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information, see APCS Control Functions
(GS 33M15U10-40E).

GS 33L01A10-40E

May 1, 2009-00

<<Contents>> <<Index>>

Vnet/IP

Layer 3 Switch

Vnet/IP is the IEEE 802.3 compliant, dual-redundant


high-speed (1Gbps) control network. All the
components of the Vnet/IP network are connected to
the Layer 2 switches. Layer 2 switches are required
for each of the dual redundant networks. One of the
dual-redundant networks (called Bus 1) is exclusively
used for process control communication. The other
(called Bus 2) is used not only for process control
communication redundant with Bus 1, but also for
the open communication with the generic Ethernet
protocol.
Using Layer 3 switches, the Vnet/IP can be divided into
several domains. VI702 the NIC (Network Interface
Card) for Vnet/IP is required for each PC, which is
connected to the Vnet/IP. Commercially available
products are used for all other network equipment such
as switches, LAN cables, or repeaters.

This is the COTS switch with the routing function, and


can divide the Vnet/IP network into several domains.

Layer 2 Switch
This is the COTS (Commercial off-the-shelf) switch
equipment. At least two switches are mandatory for one
Vnet/IP system. The transmission speed for Vnet/IP
has to be 1 Gbps.

V net Router
This is the equipment to connect a Vnet/IP system
and a V net system. This router enables the HIS of
both Vnet/IP and V net to operate the FCS of the other
systems.
The following product is available.
AVR10D: Duplexed V net Router (for redundant use
of communications and power supply
modules)
For information on the hardware specications, see
Duplexed V net Router (GS 33L50D30-40E).

SNTP Server
The time of all the components connected to the
Vnet/IP network is synchronized. By connecting the
COTS SNTP server on the Vnet/IP network, the time
of Vnet/IP components can be synchronized with UTC
(Coordinated Universal Time).

Peripherals Device
Please use compatible models of the peripheral
devices, such as printers, which support the designated
Operation Systems. Consult with a Yokogawa
sales department for more information about those
compatible devices with HIS.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E

Jun. 1, 2010-00

<<Contents>> <<Index>>

SYSTEM SPECIFICATIONS
Number of Tag
Up to 100,000 per system (when using LHS4000, up to
1,000,000 per system)

Minimum System
A minimum system consists of one HIS with
engineering function and one FCS.

Maximum System
64 components/domain
16 domain/system
256 stations/system
Components:
Human Interface Station (HIS)
Field Control Station (FCS)
Advanced Process Control Station (APCS)
Generic Subsystem Gateway (GSGW)
System Integration OPC Station (SIOS)
Safety Instrumented Systems (ProSafe-RS)
OPC Interface Package (Exaopc) OPC server
Field Communications Server for Plant Resource
Manager (PRM)
V net Router (AVR10D)
On the bus 2, up to 124 general-use Ethernet devices
(including intelligent network devices) other than listed
above can be additionally connected.

Expanded System
The former systems than V net such as HF bus or RL
bus can be connected on a Vnet/IP system through a
bus converter on a V net.
Vnet/IP domains and V net domains can be managed
in the same project, or can be connected with a
Multiple Project Connection Package.
For more information, see Multiple Project Connection
Package (GS 33M05K20-40E).

Installing of Server PCs


Each number shown below includes the number of CS
3000 PCs.
CENTUM VP achieves many functions using le
sharing function of Windows. The number of PCs to
share les simultaneously is restricted on the Windows
Workstation OS. Therefore, when there are 9 or more
stations (HIS, ENG, Exaopc) in one project, the PC with
a server OS may be required.
Please count the total station number in one project
using the equations shown below in order to judge
whether server PC is required or not. If the number
is eight or smaller, a server PC is not required. If the
number is larger than 8, consult with a Yokogawa sales
representative for further examination.
In case of PCs storing master Engineering
database le
When not using Engineering Tool for FOUNDATION
eldbus (SSS5700)
Total station number =
HIS + ((ENG - 1) x 2) + Exaopc
When using Engineering Tool for FOUNDATION eldbus
(SSS5700)
Total station number =
HIS + ((ENG - 1) x 2) + Exaopc + 2
HIS :

Number of PCs in which Standard


Operation and Monitoring Function
(LHS1100 or LHM1101) is installed
ENG:
Number of PCs in which Standard Builder
Function (LHS5100 or LHM5100) is
installed.
Exaopc: Number of PCs with Exaopc Interface
Package (NTPF100)
When using Multiple Project Connection Package
(LHS4450), see Multiple Project Connection Package
(GS 33M05K20-40E).
When using Expanded Test Function (LHS5425),
a server PC is always required for storing master
Engineering database.
In case of PCs storing audit trail data
When using LHS5170 Access Administrator Package,
one PC which is dedicated for storing audit trail data
must be prepared. When there are 9 or more stations
(ENG, Recipe Management PC) in one project, the
server PC may be required for storing audit trail data.
Please count the total station number in one project
using the equations shown below in order to judge
whether server PC is required or not. If the number
is eight or smaller, a server PC is not required. If the
number is larger than 8, consult with a Yokogawa sales
representative for further examination.
Total station number = ENG + Recipe Management
ENG:

Number of PCs in which Standard Builder


Function (LHS5100 or LHM5100) is
installed.
Recipe Management: Number of PCs in which CS
Batch 3000 Recipe Management package
(LHS5161) is installed

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E

Jun. 1, 2010-00

<<Contents>> <<Index>>

Vnet/IP NETWORK SPECIFICATIONS

The Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supports
two types of communications: control-bus communications and open communications. The Vnet/IP is always dualredundant. Usually, control bus communications are carried out via bus 1. Open communications are carried out via
bus 2. If a control communications error occurs on bus 1, control bus communications will be carried out via bus 2.
The Vnet/IP uses general-purpose communications devices for network connection.
HIS ENG
APCS GSGW
Exaopc
1000BASE-T
Max. 100 m

Up to seven levels of
layer 2 switch

Bus 1

V net router
V net
domain

Bus 2

Layer 2 switch

Layer 2 switch
Vnet/IP domain
BCV-H

HF-bus
domain

Wide-area connection
enabled by dedicated-line
connection

Layer 3
switch

Vnet/IP
domain

Vnet/IP
domain

Layer 3
switch

FFCS-L
F03E.ai

Figure Network Conguration

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E

Jul. 1, 2008-00

<<Contents>> <<Index>>

Communications Specications
Control communications
Communication Method: Read/write communication,
message communication, and intercontroller communication
Inter-Controller Communication Period: 100 msec
Open communications
Open communications are executed via bus 2.
Commercially available Ethernet communications
devices can be connected.
The total bandwidth that can be used for open
communications on bus 2 is up to 300 Mbps.
Transmission Path Specications
Network Topology: Star Topology
Transmission Path Redundancy: Available (control
bus communications only)
Transmission Cable: Unshielded twisted pair (UTP) at
enhanced category 5 or better.
Connection
Between
component and
a layer 2 switch
Between layer 2
switches
Between a layer 2
switch and a layer
3 switch
*1:

Cable
Standard
100BASE-TX
(IEEE802.3u)
1000BASE-T
(IEEE802.3ab)
1000BASE-T
(IEEE802.3ab)
1000BASE-LX
(IEEE802.3z)
1000BASE-T
(IEEE802.3ab)
1000BASE-LX
(IEEE802.3z)

Speed
100 Mbps
(*1)
1 Gbps

Maximum
Distance
100 m

1 Gbps

100 m

1 Gbps

5 km

1 Gbps

100 m

1 Gbps

5 km

For V net Router, SCS and Open communication


network.

Communications between Components


Maximum distance between arbitrary stations: 40 km
Only a couple of media converter between
components can be connected.

Required Network Equipment


Specications
Layer 2 switch
Connection Port: 1000BASE-T, full duplex
Connection between switches: 1000BASE-T,
1000BASE-LX with speed, 1 Gbps (1.5
Mpps@64 byte) or faster, full duplex
Auto-Negotiation: Mandatory
Layer 3 switch
Connection Port: 1000BASE-T, full duplex
Connection between switches: 1000BASE-T,
1000BASE-LX with speed, 1 Gbps (1.5
Mpps@64 byte) or faster, full duplex
Unicast dynamic routing protocol: RIPv2 (RIPv1
compatible mode is mandatory)
Multicast Protocol:
IGMP: Mandatory
DVMRP or PIM-DM: Mandatory
Management function
SNMP

Address Reserved for Vnet/IP


Class C private address is used for communications
for control and open communications.
For Yokogawa equipment supporting Vnet/IP, three
IP addressed are reserved: One for bus 1 control
communication; one for bus 2 control communication;
one for bus 2 open communication.
Make sure that there are no overlaps in IP addresses.
Communications for control
Bus 1:
192.168.(Domain No.).1 to 129 or 254
Bus 2:
192.168.(128 + Domain No.).1 to 129 or
254
The following addresses are reserved for multicast
communications.
For stations within domains
Bus 1:
239.192.24.0
Bus 2:
239.192.24.1
For all domains
Bus 1:
239.192.24.4
Bus 2:
239.192.24.5
Class B address is reserved for the TCP/IP protocol
communications on Vnet/IP.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E

Jul. 1, 2008-00

<<Contents>> <<Index>>

I/O COMMUNICATIONS BUS


ESB Bus
Application
An ESB bus is an I/O communications bus that connects the processing unit of an FCS to the I/O expansion nodes.
The nodes connected on the ESB bus are named local node.
Communication Specications
Connectable Devices: Node units (ANB10S and ANB10D)
Number of Connectable Devices: The number of local node units that can be connected to an ESB bus varies
according to the database selected.
Database
Control Function for Standard Field Control Unit (*1)
Control Function for Standard Field Control Unit plus Application Capacity
Expansion Package (LFS1530)
*1:

Maximum Number of
Local Nodes
3

Total Number of
Local and Remote Nodes
3

14

If local nodes are connected to an AFV10S or AFV10D FCU, ESB Bus Coupler Modules (EC401) have to be installed in
slots 7 and 8.

Transmission Path Specications


Network Topology: Bus topology
Transmission Path Redundancy: Available
Transmission Speed: 128 Mbps
Transmission Cable: Dedicated cable (YCB301)
Transmission Distance: 10 m max.

ER Bus
Application
An ER bus is a remote I/O communications bus to connect an FCU or local node unit to the I/O expansion nodes
remotely. The nodes connected on the ER bus are named remote node.
Communication Specications
Connectable Devices: Remote node units (ANR10S, ANR10D)
Number of ER buses: Max. 4 per FCU
Number of Connectable Devices: The number of remote node units that can be connected to an ER bus varies
according to the model and database selected.
Database
Control Function for Standard Field Control Unit
Control Function for Standard Field Control Unit plus Application Capacity
Expansion Package (LFS1530)
*1:

Maximum Number of
Remote Nodes
3

Total Number of
Local and Remote Nodes
3

14 (*1)

14

Up to eight remote nodes per ER bus can be connected.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E Mar. 14, 2008-00

<<Contents>> <<Index>>
Transmission Path Specications
Network Topology: Bus topology
Transmission Path Redundancy: Available
Transmission Speed: 10 Mbps
Transmission Cable: Coaxial cable (YCB141, YCB311). Use YCB147 ER-bus Adapter and YCB149 ER Bus
Converter Unit for connecting YCB141 and YCB311 cables.
One grounding unit (YCB117) per segment (*1) should be used when connecting YCB311 cable.
Transmission Distance:
YCB141: Max.185 m
When mixing YCB141 and YCB311:
Length of YCB141 + (185/500) x Length of YCB311 185
Number of Bus Adapter Units: Max. 4 per segment (*1)
General-purpose Ethernet Repeater:
The total transmission distance is limited by the number of repeaters.
L 4 - 0.5 n
L: total transmission distance (km)
n: the number of the general-purpose Ethernet repeater (Max. 4 repeaters)
*1:

If repeaters are used on ER bus, each part of the ER bus segregated by a repeater is referred to as a segment.

AFV10D (Node1)

EB401

ER bus
ANR10D (Node2)

EB501

EB401

AFV10D
(Node1)

Repeater

Repeater
Optical Fiber
Cable

Optical Fiber
Cable
Repeater

ANR10D (Node3)

Repeater

EB501

Repeater

Optical Fiber
Cable
Repeater

ANR10D (Node4)

EB501

ANR10D (Node2)

Repeater

Optical Fiber
Cable
Repeater

ER bus

Repeater

EB501

Repeater

Repeater

Repeater

Optical Fiber Optical Fiber


Cable
Cable

Optical Fiber
Cable

Repeater

Repeater

EB501
ANR10D (Node3)

Repeater
Optical Fiber
Cable
Repeater
EB501

ANR10D (Node4)

F04.ai

Figure Example of ER Bus connection

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E Feb. 1, 2009-00

<<Contents>> <<Index>>

SOFTWARE
Operation and Monitoring Software
LHS1100 Standard Operation and Monitoring
Function
LHS1120 Console HIS Support Package for
Enclosed Display Style
LHS1130 Console HIS Support Package for Open
Display Style
LHS1150 Server for Remote Operation and
Monitoring Function
LHS2411 Exaopc OPC Interface Package (for HIS)
LHS2412 CENTUM Data Access Library
LHS4000 Million Tag Handling Package
LHS4100 Congured Information Reference
Package
LHS4150 Recorder Output Package
LHS4190 Line Printer Support Package
LHS4200 Consolidated Historical Message Viewer
(Meeting FDA)
LHS4410 Control Drawing Status Display Package
LHS4420 Logic Chart Status Display Package
LHS4450 Multiple Project Connection Package
LHS4600 Multiple-monitor Package
LHS4700 Advanced Alarm Filter Package
LHS6510 Long-term Data Archive Package
LHS6530 Report Package
LHS6600 CS Batch 3000 Process Management
Package
LHS6710 FCS Data Setting/Acquisition Package
(PICOT)
For more information on the above functions, see the
respective GSs.
The following operating systems can be used on HIS
which supports operation, monitoring, and engineering.
Windows Vista Business Edition
Windows XP Professional Edition
Windows Server 2003 Standard Edition
Windows Server 2008 Standard Edition
As for Windows OS and Service Pack, see Standard
Operation and Monitoring Function (GS 33M05D1040E) and Standard Builder Function (GS 33M10D1040E).
If it is necessary to run other third-party software on
the HIS, consult with a Yokogawa sales department to
conrm that it is supported.

Engineering Software
LHS5100
LHS5110
LHS5150
LHS5160
LHS5161

Standard Builder Function


Access Control Package
Graphic Builder
CS Batch 3000 Builder
CS Batch 3000 Recipe Management
Package
LHS5170 Access Administrator Package (FDA: 21
CFR Part 11 compliant)
LHS5420 Test Function
LHS5425 Expanded Test Functions
LHS5426 FCS Simulator Package
LHS5427 HIS Simulator Package
LHS5450 Multiple Project Connection Builder
LHS5490 Self-documentation Package
LHS5800 Turbomachinery I/O Module Logic Builder
Package
For more information on the above functions, see the
respective GSs.
All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

Standard FCS Software


LFS1500 Control Function for Standard Field
Control Unit (for FIO, Vnet/IP)
LFS1530 Application Capacity Expansion Package
(for AFV10)
For more information, see Control Function for Basic
Field Control Unit, Application Capacity Expansion
Package (GS 33L15C20-40E).

Optional FCS Software


LFS3132 Valve Pattern Monitor Package
LFS8620 Off-site Block Package
For more information, see the respective GSs.

Subsystem Communication Software


For each subsystem, optional communications software
is available.
LFS2410 FA-M3 Communication Package (for
ALR111, ALR121)
LFS2420 YS Communication Package (for ALR121)
LFS2421 YS Communication Package with Direct
Connection (for ALR121)
LFS2430 MELSEC Communication Package (for
ALE111)
LFS2431 FA-M3 Communication Package (for
ALE111)
LFS2432 DARWIN/DAQSTATION Communication
Package (for ALE111)
LFS2433 PLC-5/SLC500 Communication Package
(for ALE111)
LFS2453 Modbus Communication Package (for
ALE111)
LFS2456 SLC500 Communication Package (for
ALR111, ALR121)
LFS2457 PLC-5 Communication Package (for
ALR111, ALR121)
LFS2542 PROFIBUS Communication Package (for
ALP111)
LFS2610 Foundation Fieldbus Communication
Package (for ALF111)
LFS2710 HART Communication Package (for
AI-H)
LFS2753 YFGW Communication Package (for
ALE111) (*1)
LFS9153 Modbus Communication Package (for
ALR111, ALR121)
LFS9162 MELSEC-A Communication Package (for
ALR111, ALR121)
For more information, see the respective GSs.
*1:

Supported by R4.02.30 or later versions

GS 33L01A10-40E

Jun. 2, 2010-00

10

<<Contents>> <<Index>>

Sequence of Events Manager Software


LPC6900 SOE Server Package
LPC6910 SOE Server Congurator Package
LPC6920 SOE Viewer Package
LPC6930 SEM OPC Interface Package
For more information, see SEM Sequence of Events
Manager (for FIO and Vnet/IP) (GS 33L30D10-40E).

Documents
LHS5495 Electronic Document
For more information, see Electronic Instruction
Manual (GS 33M01W10-40E).

Plant Resource Management


SSS7700 Plant Resource Management Server
SSS7710 Plant Resource Management Client
SSS7720 Field Communications Server
For more information, see Plant Resource Manager
(GS 33Y05Q10-32E).

Operation Support Software (for HIS)


NTPS100 Exaplog Event Analysis Package
NTPS200 Exapilot Operation Efciency
Improvement Package
For more information, see NTPS100 Exaplog Event
Analysis Package (GS 36J06A10-01E) and NTPS200
Exapilot Operation Efciency Improvement Package
(GS 36J06B20-01E).

Safety Instrumented System


CHS5100 Safety System Generation and
Maintenance Package
CFS1100 Safety Control Functions Package
For more information, see ProSafe-RS Safety
Instrumented System Overview (for Vnet/IP) (GS
32S51B10-01E).

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

INSTALLATION AND
ENVIRONMENTAL CONDITIONS

The installation and environmental conditions for


Yokogawas components (not including the generalpurpose PCs, General-Purpose Network Device,
console HISs, node units for FIO and I/O modules) are
shown below.
For a general-purpose PC and Network equipment,
see their specications. For an Enclosed display style
console HIS, an Open display style console HIS, a
node unit for FIO, or an I/O module, see the general
specications for each device (GS 33M50B40-40E, GS
33M50B50-40E or GS 33M50F10-40E).
Ambient Temperature:
5 to 40 C (YAX101, YAX801)
0 to 50 C (FCS)
Ambient Humidity:
20 to 80 %RH
10 to 90 %RH (FCS)
Non-condensation
Temperature Change Rate:
10 C per hour
Power Requirements:
100 to 120 V AC 10 %, 50 or 60 Hz
3 Hz
220 to 240 V AC 10 %, 50 or 60 Hz 3
Hz
24 V DC 10 %
Withstanding Voltage:
1500 V AC for 1 minute (for 100-120 and
220-240 V AC model)
500 V AC for 1 minute (for 24 V DC
model)
Insulation Resistance:
20 M at 500 V DC
10 M at 500 V DC (YAX101, YAX801)
Grounding:
Independent ground of up to 100
Noise:
Electric Field: Up to 3 V/m (26 MHz to 1.0 GHz)
Up to 3 V/m (1.4 to 2.0 GHz)
Up to 1 V/m (2.0 to 2.7 GHz)
Magnetic Field: Up to 30 A/m (AC), up to 400 A/m
(DC)
Static:
Up to 4 kV (direct discharge), up to 8 kV
(aerial discharge)
Continuous Vibration:
Displacement amplitude: Up to 0.25 mm
(1 to 14 Hz)
Acceleration: Up to 2 m/s2 (14 to 100 Hz)

GS 33L01A10-40E Nov. 1, 2008-00

11

<<Contents>> <<Index>>

CENTUM VP Entry Class

The CENTUM VP Entry Class is available for small-scale systems. Up to 8,000 tag names can be used in a CENTUM
VP Entry Class system.

Components and Software


The CENTUM VP Entry Class uses specic Entry Class packages such as built-in HIS packages. There is no
restriction on FCS models.

Operation and Monitoring Software


The following software packages are provided for the Entry Class. Except for the packages listed below, current
CENTUM VP system operation and monitoring software packages can be used. But, the LHS4000 Million Tag
Handling Package cannot be used in an HIS with the built-in LHM1101 Standard Operation and Monitoring Function.
Operation and Monitoring Software
Entry Class Model
LHM1101
LHM1150
LHM4410
LHM4420

Product
Standard Operation and Monitoring Function
Server for Remote Operation and Monitoring Function
Control Drawing Status Display Package
Logic Chart Status Display Package
CS Batch 3000 Process Management Package

LHM6600
LHM6710

FCS Data Setting/Acquisition Package (PICOT)

Remarks
Number of operation and monitoring tags : up to 8000

Maximum number of active recipes:


Type A: 4
Type B: 10
Type C: 999

Engineering Software
Entry Class Model
LHM5100
LHM5150
LHM5490

Product
Standard Builder Function
Test Function
Self-documentation Package

Remarks

Restrictions
For CENTUM VP Entry Class, the following restrictions apply.
Only one domain per system
The HIS in a CENTUM VP Entry Class project cannot access the FCSs in other projects of CENTUM VP, CENTUM
VP Entry Class, CENTUM CS 3000 and CENTUM CS 3000 Entry Class.
The HIS in a CENTUM VP Entry Class project can access the FCSs in the Micro-XL system ,but not other former
CENTUM systems.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L01A10-40E Mar. 14, 2008-00

12

<<Contents>> <<Index>>

REGULATORY COMPLIANCE

CENTUM VP hardware components conform to


the following standards. See the applicable general
specications to ensure each devices compliance.
Safety Standards (*1)
[CSA]
CSA C22.2 No. 61010-1
[CE Marking] Low Voltage Directive
EN 61010-1 (*2)
EMC Conformity Standards (*1)
[CE Marking] EMC Directive
EN 55011 Class A Group 1 (*3)
EN 61000-6-2 (*4)
EN 61000-3-2 (*5)
EN 61000-3-3 (*6)
[C-Tick Marking]
EN 55011 Class A Group 1 (*3)
Standards for Hazardous Location Equipment
[CSA Non-Incendive] (*7)
Class I, Division 2, Groups A, B, C and D
Temperature code T4
CSA Standard C22.2 No. 157-92
CSA Standard C22.2 No. 213-M1987
ISA Standard ISA-S12.12 1994
(for 100-120 V AC and 24 V DC power supply)
[FM Non-Incendive] (*8)
Class I, Division 2, Groups A, B, C and D
Temperature code T4
FM Class Number 3600: 1998
FM Class Number 3611: 2004
FM Class Number 3810: 2005
(for 100-120 V AC, 220-240 V AC and 24 V DC
power supply)
[Type n] (*9)
II 3G Ex nC [nL] II C T4
EN 60079-15: 2005
IEC 60079-0: 2004
IEC 60079-11: 1999
(for 24 V DC power supply)
II 3G EEx nA II T4
EN 50021: 1999
(I/O Module with built-in barrier, for 24 V DC power
supply)
[Type i (Intrinsic Safety)]
II (1) G D [EEx ia] II C
EN 50014: 1997 +A1 +A2
EN 50020: 1994
[FM Intrinsic Safety]
Associated intrinsically safe apparatus for
connection to
Class I, II and III, Division 1, Groups A, B, C, D, E,
F and G or
Class I, Zone 0, Group II C
FM Class Number 3600: 1998
FM Class Number 3610: 1999
ANSI/ISA-12.12.02: 2003
*1:
*2:

*3:

*4:

*5:

*6:
*7:

*8:

*9:

A Class A hardware device is designed for use in


the industrial environment.
Please use this device in the industrial
environment only.
A lightning arrestor or its equivalent is required to
meet this surge immunity standard.
The length of the cable to feed the external power
supply for AGS813 AO channels should not
exceed 30 meters.
An external device such as a power unit with
harmonic current neutralizer and an active
harmonics conditioner must be connected to meet
this harmonic current emission standard.
The specied limits of voltage drops across wiring
must be satised to meet this standard.
To meet the standard for hazardous location
equipment, 19-inch rack-mounted devices must
be installed in a keyed metallic cabinet approved
by CSA or non-incendive regulator in your area.
To meet the standard for hazardous location
equipment, 19-inch rack-mounted devices must
be installed in a keyed metallic cabinet approved
by FM or non-incendive regulator in your area.
To be compatible with Type n, the specication
requirements of EN 61010-1 and EN 60079-15
must be met, and a keyed metallic cabinet, whose
degree of protection is IP 54 or above, prescribed
by IEC 60529 must be used for housing.

Note: According to the New Approach Directive, the


manufacturer and the representative ofce in EU
are indicated below:
Manufacturer: Yokogawa Electric Corporation (29-32 Nakacho, Musashino-shi, Tokyo 180-8750,
Japan).
Representative ofce in EU Community:
Yokogawa Europe B.V. (Euroweg 2, 3825 HD
Amersfoort, The Netherlands).

TRADEMARKS

CENTUM, Vnet/IP, DARWIN, DAQSTATION ProSafe


and Exaopc are registered trademarks of Yokogawa
Electric Corporation.
Exaplog and Exapilot are trademarks of Yokogawa
Electric Corporation.
Windows is a registered trademark of Microsoft
Corporation in the United States and/or other
countries.
Ethernet is a registered trademark of XEROX
Corporation.
Modbus is a registered trademark of Schneider
Electric and/or such related companies.
PLC, PLC-5 and SLC500 are trademarks or
registered trademarks of Rockwell Automation, Inc.
MELSEC and MELSEC-A are registered trademarks
of Mitsubishi Electric Corporation.
SYSMAC is a registered trademark of Omron
Corporation.
FOUNDATION of FOUNDATION eldbus is a registered
trademark of Fieldbus Foundation.
Other product and company names appearing in this
document are trademarks or registered trademarks of
their respective holders.

To conform to safety standards and EMC


conformity standards, install 19-inch rackmounted devices in a keyed metallic cabinet.
The analog input side of this equipment is
measurement category 1.
For details, see CENTUM VP Installation
Guidance (TI 33L01J10-40E).

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation


Subject to change without notice.

GS 33L01A10-40E