Beruflich Dokumente
Kultur Dokumente
I. INTRODUCTION
Global mobilization, regarding the integration of renewable
power sources in the power system, was done in order to
reduce the conventional production capacities, that produces
large quantities of greenhouse gases [1]. Once connected to the
national power grid, the distributed production units must be
taken into account, when operating regimes are established,
setting protections and beyond.
In the case of smart grids, maintaining the adequate
performance for the relay protection is an essential goal. The
concept of smart substation is no longer a new concept, as it is
based on extending existing systems of protection, control and
monitoring. Compared to conventional substations, smart
substations provide a monitoring, protection, control, effective
and safe, through:
972
a)
b)
Fig.1. a) voltage at relay location during S-T fault.b) isolated S-T
shortcircuit.
For a S-T fault with fault resistance (Fig. 2.) on one circuit
of a double circuit transmission line that is fed from two
sources, the voltage at the protection location is determined as
follows:
U St U Ss = Z L1 ( I St I Ss ) + R f I f
(2)
Considering the apparent current and the expression of the
voltage from (2), the apparent impedance can be expressed as:
U app U St U Ss
(3)
Z app =
=
I app
I St I Ss
Ir = 0
I s = It
(1)
U s = Ut
For R f = 0
where,
I r = current in phase R.
I s = current in phase S.
I t = current in phase T.
U s = phase to earth voltage of phase S.
U t = phase to earth voltage of phase T.
R f = fault resistance.
973
b)
Fig.4. a), b) Correction of impedance.
a)
X'
X app X '
Rapp
(5)
X
X'
X L1 =
R X X app X '
R
Rapp
where,
Rapp = apparent resistance []
X app = apparent reactance []
X = transmission line resistance []
b)
Z app = Z L1 + R f
If
I St I Ss
= Z L1 + R f
If
I St I Ss
e j (6)
(4)
where,
a)
974
I S1 m B f 1 + C f 1
=
I f1
Af 1
(7)
A f 1 = Z L1 ( Z X 1 + ZY 1 ) + ZT 1 ( Z X 1 + ZY 1 + Z L1 )
B f 1 = Z L1 ( Z X 1 + ZY 1 + ZT 1 )
C f 1 = Z L1 ( Z X 1 + ZY 1 + ZT 1 ) + ZT 1 ZY 1
Taking into account (7) and the load current I Stf I Ssf at
the local end of the faulted circuit, I f can be expressed as
I f = I ft I fs = I f 1 + I f 2 a 2 I f 1 aI f 2
If =
If =
I S1
I
I
I
+ S 2 a 2 S1 + a S 2
CDF f 1 CDF f 2
CDF f 1
CDF f 2
I Stf I Ssf
(8)
CDF f 1
I Stf I Ssf
= Arg
I
I
St Ss CDF f 1
1
I Stf I Ssf
= Arg
+ Arg
I St I Ss
CDF f 1
If
= Arg
I St I Ss
(9)
where,
I St = I StL + I Stf
I Ss = I SsL + I Ssf
I StL = T phase load current at the local end of faulted
circuit [A]
I SsL = S phase load current at the local end of faulted
circuit [A]
circuit [A]
Type of shortcircuit
Fault resistance []
975
-3 (zone 5)
+5 (zone 1)
+10.2 (zone 1)
+12 (zone 2)
0
40
Correction
-3 (zone 5)
+5 (zone 1)
+10.2 (zone 1)
+12 (zone 2)
0
40
Source []
Line 1 (2) [/km]
SX
0.745+j1.348
SY
0.312+j2.66
Fault location
[km]
Fault resistance
[]
-3 (zone 5)
0.157+j0.393
+5
(zone 1)
+10.2 (zone 1)
+12 (zone 2)
Distance
algorithm
No Trip
40
0
40
0
40
0
40
No Trip
Trip
No Trip
Trip
No Trip
No Trip
No Trip
Fault resistance
[]
-3 (zone 5)
+5
(zone 1)
+10.2 (zone 1)
+12 (zone 2)
Distance
algorithm
No Trip
40
0
40
0
40
0
40
No Trip
Trip
Trip
Trip
Trip
No Trip
No Trip
-3 (zone 5)
+5 (zone 1)
+10.2 (zone 1)
Fault
resistance
[]
0
40
0
40
0
Actual
value
[]
Distance
algorithm
-0.473
-0.473
-0.821
0.789
0.826
1.609
0.789
1.609
40
+12 (zone 2)
0
40
1.615
1.893
1.893
1.898
location
-3 (zone 5)
Fault
resistance
[]
Actual
value
[]
Distance
algorithm
-1.181
+5 (zone 1)
0
40
0
1.968
-1.181
-2.048
1.968
+10.2 (zone 1)
40
0
4.014
2.060
4.014
4.723
4.723
40
+12 (zone 2)
0
40
976
4.027
4.734
V. CONCLUSIONS
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
977