Sie sind auf Seite 1von 5

CLIENT

PROJECT
EQUIPMENT
JOBNO.
DOC.NO.

FLSMIDTH
JSPLBARBIL
HOTGASGENERATOR
122682
122682SL04

REVNO.
DATE
PRPDBY
CHKDBY
APPDBY

0
26.10.2012
FJS
SND
KKJ

FLSmidth Drawing No 60112341


Ver 2.0

SIGNALSEXCHANGELIST

0
REV.

INITIALISSUE
DESCRIPTION

26.10.2012
DATE
Page 1 of 5

FJS
PRPDBY

SND
CHKDBY

KKJ
APRDBY

1
2
3
4
5

REVISION NO:
DATE:
PREPARED BY:
CHECKED BY:
APPROVED BY:

CLIENT: FLSMIDTH
EQUIPMENT: HGG
PROJECT:JSPL-BARBIL
DOCUMENT NO: 12-2682-SL-04

JOBNO:122682

0
26.10.2012
FJS
SND
KKJ

SOFTSIGNALSFROMBMSTODCS
SR.NO.

SIGNALDESCRIPTION

IOaddressdetails

Signal type

Normal State

LATER

status

OILLINEINLETPRESSURESWITCHLOW

OILLINEINLETTEMP.SWITCHLOW

status

ATOM.AIRLINEINLETPRESSURESWITCHLOW

status

PILOTLINEPRESSURESWITCHLOW

status

OILLINESHUTOFFVALVEOPENPOSITION

status

OILLINESHUTOFFVALVECLOSEPOSITION

status

OILLINEOUTLETPRESSURESWITCHHIGH

status

SCAVENGINGLINESHUTOFFVALVEOPENPOSITION

status

SCAVENGINGLINESHUTOFFVALVECLOSEPOSITION

status

10

ATOMAIRLINESHUTOFFVALVEOPENPOSITION

status

ATOMAIRLINESHUTOFFVALVECLOSEPOSITION

status

RETURNLINESHUTOFFVALVEOPENPOSITION

status

13

RETURNLINESHUTOFFVALVECLOSEPOSITION

status

14

SCANNERREADYCONTACT

status

15

MAINFLAMEONCONTACT

status

16

Comb Air PID in Auto Mode

status

17

Comb Air PID in Manual Mode

status

18

HGGOUTLETTEMP.SETPOINT

status

19

OILLINESHUTOFFVALVEOPENCMD.

status
t t

20

ATOM.AIRLINESSOVOPENCMD.

status

21

SCAVENGINGLINESHUTOFFVALVEOPENCMD.

status

22

RETURNLINESHUTOFFVALVECLOSECMD.

status

23

LPGLINESVONCMD.

status

24

OILLINEFCVPOSITIONTRANS.

analog

continuous

25
26
27
28
29
30
31

OILLINEFLOW
COMB.AIRACTUATORPOSITIONTRANS.
DILU.AIRACTUATORPOSITIONTRANS.
FLAMEINTENSITY
HGGOUTLETTEMP.TRASNS.
HGGREFRACTORYTEMP.TRASNS.
MILLOUTLETTEMPTRANS.

analog

continuous

analog
analog
analog
analog
analog
analog

continuous
continuous
continuous
continuous
continuous
continuous

32

OILFCVMODULATIONCOMMAND

analog

continuous

33
34
35
36
37
38
39
40
41
42
43
44
45
46
47

CADI/PCONVERTER
DADI/PCONVERTER

analog

continuous

analog
alarm
alarm
alarm
alarm
alarm
alarm
alarm
alarm
alarm
alarm
alarm
alarm
alarm

continuous

11
12

SYSTEM PERMISSIVE NOT OK


PIPE RACK INLET OIL TEMPERATURE LOW
PIPE RACK INLET OIL PRESSURE LOW
PIPE RACK INLET OIL PRESSURE HIGH
PIPE RACK INLET ATOMIZING PRESSURE LOW
PIPE RACK INLET LPG PRESSURE LOW
PIPE RACK INLET INSTRUMENT AIR PRESSURE LOW
COMBUSTION AIR PRESSURE LOW
DILUTION AIR PRESSURE LOW
HGG REFRACTORY TEMPERATURE HIGH
FLAME FAILURE
COMMAND AND FEEDBACK MISMATCH
EMERGENCY STOP EXECUTED

Page 2 of 5

0
0
0
0
0
0
0
0
0
0
0
0
0

1
2
3
4
5

CLIENT: FLSMIDTH
EQUIPMENT: HGG
PROJECT:JSPL-BARBIL
DOCUMENT NO: 12-2682-SL-04

48
49
50

CAD FAIL TO ACHIEVE HIGH FIRE POSITION


CAD FAIL TO ACHIEVE LOW FIRE POSITION
PURGE CYCLE FAIL

51

Dilution Air PID in Auto Mode

status

52

Dilution Air PID in Manual Mode

status

1
2
3
4
5
6

HGGoutletTemperatureSetpoint

analog
status
status
analog
status
status

continuous

JOBNO:122682

REVISION NO:
DATE:
PREPARED BY:
CHECKED BY:
APPROVED BY:
alarm
alarm
alarm

0
26.10.2012
FJS
SND
KKJ

0
0
0

SOFTSIGNALSFROMDCSTOBMS
Comb Air PID in Auto Mode
Comb Air PID in Manual Mode

MillOutletTemperatureSetpoint
DilutionAirPIDAutoMode
DilutionAirPIDManualMode

Page 3 of 5

1
0
continuous
1
0

1
2
3
4
5

CLIENT: FLSMIDTH
EQUIPMENT: HGG
PROJECT:JSPL-BARBIL
DOCUMENT NO: 12-2682-SL-04
JOB NO:- 12-2682

0
26.10.2012
FJS
SND
KKJ

SOFTLINKSIGNALBETWEENFIELDANDDCS/MCC
SR.NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

SIGNALDESCRIPTION
TIS201SETPOINT1FEEDBACK
TIS201SETPOINT2FEEDBACK
TIS202SETPOINT1FEEDBACK
TIS202SETPOINT2FEEDBACK
TISSETPOINT1(DOTOUTLET)FEEDBACK
TISSETPOINT2(DOTOUTLET)FEEDBACK
Pump1STARTCMD
Pump1STOPCMD
Pump2STARTCMD
Pump2STOPCMD
CombustionBlowerSTARTCMD
CombustionBlowerSTOPCMD
DilutionBlowerSTARTCMD
DilutionBlowerSTOPCMD
Pump1STARTPushbutton
Pump2STARTPushbutton
Pump1STOPPushbutton
Pump2STOPPushbutton
CombustionBlowerSTARTPushbutton
DilutionBlowerSTARTPushbutton
CombustionBlowerPushbutton
DilutionBlowerSTOPPushbutton
HEATER1BANK1ONCMD
HEATER1BANK2ONCMD
HEATER2BANK1ONCMD
HEATER2BANK2ONCMD
SUCTIONHEATERBANK1ONCMD
SUCTIONHEATERBANK2ONCMD

From
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
Local operating station
Local operating station
Local operating station
Local operating station
Local operating station
Local operating station
Local operating station
Local operating station
DCS
DCS
DCS
DCS
DCS
DCS

Page 4 of 5

To

SetPoint

DCS
DCS
DCS
DCS
DCS
DCS
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
FIELD
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC
DCS/MCC

118C
120C
118C
120C
46C
50C

MCC
MCC
MCC
MCC
MCC
MCC

1
2
3
4
5

CLIENT: FLSMIDTH
EQUIPMENT: HGG
PROJECT: JSPL-BARBIL
DOCUMENT NO: 12-2682-SL-04
JOB NO:- 12-2682

REVISION NO:
DATE:
PREPARED BY:
CHECKED BY:
APPROVED BY:

0
26.10.2012
FJS
SND
KKJ

HARDWIREDSIGNALFROMBMSTODCS
SR.NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14

SIGNALDESCRIPTION
LOCALMODESELECTED
BMSMODESELECTED
DCSMODESELECTED
IGNITIONON
FLAMEON
PURGEREADY
PURGEINPROGRESS
PURGECOMPLETE
BURNERREADYTOFIRE
PILOTON
BURNERON
RELEASEFORMODULATION
BURNERTRIP
HOOTERONCMD.

BMSPanelTB

DCS Panel TB

Normal State

by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client

1
0
0
0
0
1
0
0
0
0
0
0
0
0

DCS Panel TB

Normal State

by
yC
Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client
by Client

1
1
1
1
1
0
0
1
1
0
0

Later
Later
Later
Later
Later
Later
Later
Later
Later
Later
Later
Later
Later
Later

HARDWIREDSIGNALFROMDCSTOBMS
SR.NO.
1
2
3
4
5
6
7
8
9
10
11

SIGNALDESCRIPTION
SYST M P RMISSIV
SYSTEMPERMISSIVE
PUMP1ON(FEEDBACK)
PUMP2ON(FEEDBACK)
COMB.AIRBLOWERONFEEDBACK
DILU.AIRBLOWERONFEEDBACK
PURGESTART
BURNERSTART
BURNERSTOP
EMERGENCYSTOP
ACKNOWLEDGE
RESET

BMSPanelTB
Later
ate
Later
Later
Later
Later
Later
Later
Later
Later
Later
Later

Page 5 of 5