GENERAL
This GS provides the hardware specications of the digital I/O modules that can be installed in the Safety Node Unit
(SNB10D) and Safety Control Units (SSC10S and SSC10D).
STANDARD SPECIFICATIONS
Input Module
Input modules accept a contact signal from the eld. SDV144 input modules can be dual-redundant.
Item
Specications
Model
SDV144
Number of inputs
Input signal
No-voltage contact
ON: 1 k maximum
OFF: 100 k minimum
Input current
6 mA 20%
(External power supply, 24 V DC at 0 input)
Contact rating
24 V 5%, 10 mA or greater
24 V 5%
Current capacity: 200 mA
30.0 V DC
40 ms maximum
Withstand voltage
Current consumption
Weight
External connection
Note: When dedicated cables are used, the module withstand voltage shall be 500 V AC (between input signal lines and system).
If MIL connector cables are used, the withstand voltage depends on their cables electrical specications.
If SDV144 eld wiring diagnostic functions are used, the following diagnostic elements should be installed for individual channels in the vicinity of the eld equipment:
SCB100 (for defective open circuit detection while accepting off signals) (*1)
SCB110 (for defective short-circuit detection while accepting on signals) (*2)
*1:
*2:
GS 32S06K40-01E
Copyright Feb. 2005
2nd Edition Nov.07,2005
<<Contents>> <<Index>>
When the input signals are normally off while in normal operation, connect the SCB100 in parallel with the contact
output of the eld equipment as given below.
SCB100
SDV144
DCn
INn
When the input signals are normally on while in normal operation, connect the SCB110 in series with the contact output of the eld equipment (take care about the polarity taking note of the polarity).
SCB110
SDV144
DCn
Red
Blue
INn
F02E.ai
When checking for both defective short and open circuits, connect the SCB100 and SCB110 in parallel and series with
the contact outputs of the eld equipment respectively, as given below.
SDV144
DCn
SCB100
Red
SCB110
Blue
INn
F03E.ai
GS 32S06K40-01E
Feb.01,2005-00
<<Contents>> <<Index>>
Output Module
Output modules output 24 V DC on/off status signals to eld equipment.
SDV531 output modules can be dual-redundant. The output modules incorporate eld wiring diagnostic features, so
they require no wiring diagnosis elements.
Item
Specications
Model
SDV531
Number of outputs
Output voltage
24 V DC
24 V DC, 5 A minimum
24 V DC 5%
Current capacity, 5 A
1 V maximum
1.6 mA
Output format
Current source
30 ms maximum
Withstand voltage
Current consumption
2 kV AC (between input signal lines and system), eight input lines collectively
connected (negative lines) (*1)
280 mA maximum (5 V DC)
140 mA maximum (24 V DC)
Weight
External connection
*1:
When dedicated cables are used, the modules withstand voltage shall be 500 V AC (between input signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cables electrical specications.
GS 32S06K40-01E
Nov.07,2005-00
<<Contents>> <<Index>>
EXTERNAL DIMENSIONS
SDV144 Digital Input Module
Unit: mm
107.5
32.8
130
F04E.ai
107.5
32.8
130
F05E.ai
83
655
113
F06E.ai
GS 32S06K40-01E
Feb.01,2005-00
<<Contents>> <<Index>>
SDV144
-S
Basic type
Always 1
3
Option codes
*1:
/D4A00
/B4S00
With pressure clamp terminal block for digital input (without surge absorber)
[Part name: STB4S-00]
/B4S10
With pressure clamp terminal block for digital input (with surge absorber)
[Part name: STB4S-10]
/B4D00
Dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*1)
[Part name: STB4D-00]
/B4D10
Dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*1)
[Part name: STB4D-10]
/CCC01
/CCC02
When this module is used in dual-redundancy, one more module with the same specication is needed, but no option code
is required in its module.
SDV531
-S
Basic type
Always 2
3
Option codes
*1:
/D4A00
/B4S00
With pressure clamp terminal block for digital output (without surge absorber)
[Part name: STB4S-00]
/B4S10
With pressure clamp terminal block for digital output (with surge absorber)
[Part name: STB4S-10]
/B4D00
Dual-redundant pressure clamp terminal block for digital output (without surge absorber) (*1)
[Part name: STB4D-00]
/B4D10
Dual-redundant pressure clamp terminal block for digital output (with surge absorber) (*1)
[Part name: STB4D-10]
/CCC01
/CCC02
When this module is used in dual-redundancy, one more module with the same specication is needed, but no option code
is required in its module.
GS 32S06K40-01E
Nov.07,2005-00
<<Contents>> <<Index>>
Wiring Diagnosis Elements
Description
Model
Sufx codes
*1:
SCB100
Wiring Check Adapter for Digital input (for defective open circuit detection while accepting off
signals) (*1)
-S
Basic type
Always 1 (G3-compatible)
Eight wires/set
Description
Model
Sufx codes
*1:
SCB110
Wiring check adapter for Digital input (for defective short-circuited detection while accepting on
signals) (*1)
-S
Basic type
Always 1 (G3-compatible)
Eight wires/set
ORDERING INFORMATION
TRADEMARKS
GS 32S06K40-01E
Feb.01,2005-00