This GS provides the hardware specications of the digital I/O modules that can be installed in the Safety Node Unit
(SNB10D) and Safety Control Units (SSC10S and SSC10D).

STANDARD SPECIFICATIONS
Input Module
Input modules accept a contact signal from the eld. SDV144 input modules can be dual-redundant.
Item

Specications

Model

SDV144

Number of inputs

16, collective isolation

Input signal

No-voltage contact
ON: 1 k maximum
OFF: 100 k minimum

Input current

6 mA 20%
(External power supply, 24 V DC at 0 input)

Contact rating

24 V 5%, 10 mA or greater

External power supply

24 V 5%
Current capacity: 200 mA

Instantaneous maximum permissible


input voltage

30.0 V DC

Input response time

40 ms maximum

Withstand voltage

2 kV AC between input signal and system, 16-input line collectively connected

Current consumption

290 mA maximum (5 V DC)


140 mA maximum (24 V DC)

Weight

0.31 kg (with no option codes)

External connection

Pressure clamp terminal


MIL cable
Dedicated cable

Note: When dedicated cables are used, the module withstand voltage shall be 500 V AC (between input signal lines and system).
If MIL connector cables are used, the withstand voltage depends on their cables electrical specications.

If SDV144 eld wiring diagnostic functions are used, the following diagnostic elements should be installed for individual channels in the vicinity of the eld equipment:
SCB100 (for defective open circuit detection while accepting off signals) (*1)
SCB110 (for defective short-circuit detection while accepting on signals) (*2)
*1:
*2:

Input signals are normally off while in normal operation.


Input signals are normally on while in normal operation.

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5816 Fax.: 81-422-52-0571

GS 32S06K40-01E
Copyright Feb. 2005
2nd Edition Nov.07,2005

<<Contents>> <<Index>>
When the input signals are normally off while in normal operation, connect the SCB100 in parallel with the contact
output of the eld equipment as given below.
SCB100

SDV144
DCn

INn

: Field equipment switch


F01E.ai

When the input signals are normally on while in normal operation, connect the SCB110 in series with the contact output of the eld equipment (take care about the polarity taking note of the polarity).
SCB110

SDV144
DCn

Red
Blue

INn
F02E.ai

When checking for both defective short and open circuits, connect the SCB100 and SCB110 in parallel and series with
the contact outputs of the eld equipment respectively, as given below.
SDV144
DCn
SCB100
Red
SCB110
Blue

INn
F03E.ai

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation

GS 32S06K40-01E

Feb.01,2005-00

<<Contents>> <<Index>>
Output Module
Output modules output 24 V DC on/off status signals to eld equipment.
SDV531 output modules can be dual-redundant. The output modules incorporate eld wiring diagnostic features, so
they require no wiring diagnosis elements.
Item

Specications

Model

SDV531

Number of outputs

Eight, collective isolation

Output voltage

24 V DC

External power supply rating

24 V DC, 5 A minimum

External power supply

24 V DC 5%
Current capacity, 5 A

Output voltage drop

1 V maximum

Maximum leak current at output off


status

1.6 mA

Output format

Current source

Maximum load current

0.6 A/output line (4.8 A in total output line)

Output response time

30 ms maximum

Withstand voltage
Current consumption

2 kV AC (between input signal lines and system), eight input lines collectively
connected (negative lines) (*1)
280 mA maximum (5 V DC)
140 mA maximum (24 V DC)

Weight

0.28 kg (with no option codes)

External connection

Pressure clamp terminal


MIL cable
Dedicated cable

*1:

When dedicated cables are used, the modules withstand voltage shall be 500 V AC (between input signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cables electrical specications.

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation

GS 32S06K40-01E

Nov.07,2005-00

<<Contents>> <<Index>>

EXTERNAL DIMENSIONS
SDV144 Digital Input Module
Unit: mm

107.5

32.8

130

F04E.ai

SDV531 Digital Output Module


Unit: mm

107.5

32.8

130

F05E.ai

SBC100 and SBC110 Wiring Diagnosis Elements


25010

83
655

113
F06E.ai

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation

GS 32S06K40-01E

Feb.01,2005-00

<<Contents>> <<Index>>

MODEL AND SUFFIX CODES


Digital Input Module
Description
Model
Sufx codes

SDV144

Digital input module (16 input channels, collective isolation)

-S

Basic type

Always 1
3

Option codes

*1:

G3-compatible and temperature-adaptive

/D4A00

With signal cable interface adapter


[Part name: STD4A-00]

/B4S00

With pressure clamp terminal block for digital input (without surge absorber)
[Part name: STB4S-00]

/B4S10

With pressure clamp terminal block for digital input (with surge absorber)
[Part name: STB4S-10]

/B4D00

Dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*1)
[Part name: STB4D-00]

/B4D10

Dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*1)
[Part name: STB4D-10]

/CCC01

With connector cover for MIL cable (ribbon cable)


[Part name: SCCC01]

/CCC02

With connector cover for MIL cable (separated cable)


[Part name: SCCC02]

When this module is used in dual-redundancy, one more module with the same specication is needed, but no option code
is required in its module.

Digital Output Module


Description
Model
Sufx codes

SDV531

Digital output module (eight outputs, collective isolation)

-S

Basic type

Always 2
3

Option codes

*1:

G3-compatible and temperature-adaptive

/D4A00

With signal cable interface adapter


[Part name: STD4A-00]

/B4S00

With pressure clamp terminal block for digital output (without surge absorber)
[Part name: STB4S-00]

/B4S10

With pressure clamp terminal block for digital output (with surge absorber)
[Part name: STB4S-10]

/B4D00

Dual-redundant pressure clamp terminal block for digital output (without surge absorber) (*1)
[Part name: STB4D-00]

/B4D10

Dual-redundant pressure clamp terminal block for digital output (with surge absorber) (*1)
[Part name: STB4D-10]

/CCC01

With connector cover for MIL cable (ribbon cable)


[Part name: SCCC01]

/CCC02

With connector cover for MIL cable (separated cable)


[Part name: SCCC02]

When this module is used in dual-redundancy, one more module with the same specication is needed, but no option code
is required in its module.

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation

GS 32S06K40-01E

Nov.07,2005-00

<<Contents>> <<Index>>
Wiring Diagnosis Elements
Description
Model
Sufx codes
*1:

SCB100

Wiring Check Adapter for Digital input (for defective open circuit detection while accepting off
signals) (*1)

-S

Basic type

Always 1 (G3-compatible)

Eight wires/set
Description

Model
Sufx codes
*1:

SCB110

Wiring check adapter for Digital input (for defective short-circuited detection while accepting on
signals) (*1)

-S

Basic type

Always 1 (G3-compatible)

Eight wires/set

ORDERING INFORMATION

Specify the model and sufx codes when ordering.

TRADEMARKS

ProSafe is a registered trademark of Yokogawa Electric Corporation.


Other company and product names appearing in this document are trademarks or registered trademarks of their
respective holders.

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation


Subject to change without notice.

GS 32S06K40-01E

Feb.01,2005-00

Das könnte Ihnen auch gefallen