Beruflich Dokumente
Kultur Dokumente
ED04-703
Split-System
Room Air Conditioners
F-Series
Cooling Only
Heat Pump
1.
2.
3.
4.
FTKD50FVM
FTKD60FVM
FTKD71FVM
FTKD50FVM
FTKD60FVM
FTKD71FVM
FTXD50FVM
FTXD60FVM
FTXD71FVM
RKD50BVM
RKD60BVM
RKD71BVM
RKD50BVMA
RKD60BVMA
RKD71BVMA
RXD50BVMA
RXD60BVMA
RXD71BVMA
Features ..................................................................................................3
Power Supply ..........................................................................................8
Functions.................................................................................................9
Specifications ........................................................................................10
4.1 Cooling Only...........................................................................................10
4.2 Heat Pump .............................................................................................12
5. Dimensions ...........................................................................................14
5.1 Indoor Units ............................................................................................14
5.2 Outdoor Units .........................................................................................17
6. Wiring Diagrams....................................................................................19
6.1 Indoor Units ............................................................................................19
6.2 Outdoor Units .........................................................................................19
7. Piping Diagrams....................................................................................21
7.1 Indoor Units ............................................................................................21
7.2 Outdoor Units .........................................................................................23
9. Operation Limit......................................................................................33
9.1 Cooling Only...........................................................................................33
9.2 Heat Pump .............................................................................................33
11.Electric Characteristics..........................................................................38
Room Air Conditioners F-Series
ED04-703
13.Operation Manual..................................................................................55
14.Optional Accessories ............................................................................81
14.1 Option List ..............................................................................................81
14.2 Installation Manual .................................................................................82
ED04-703
Features
1. Features
Features
ED04-703
Intelligent Eye
= Automatic shift up when sensing no human, intelligently saving energy =
Cooling
Normal
operation
Energy
Saving
operation
Absence 20min
Back to
normal
operation
when
presence
detected
Normal
operation
Saving
20%!
Power consumption
Temperature
2C Shift up
Minimum frequency
(34Hz)
Normal
operation
time
Energy saving
operation
activated
05RAG02B- 33
Intelligent Eye
= When absence shift down automatically makes energy saving intelligently =
Heating
Normal
operation
Energy
Saving
operation
Absence 20min
Power consumption
Temperature
2C Shift down
Minimum frequency
(34Hz)
Saving
30%!
Returns to
normal operation
upon sensing
a sign of human
Normal
operation
Normal
operation
Energy saving
operation
activated
time
05RAG02B- 34
ED04-703
Features
Features
ED04-703
ED04-703
Features
06RAG04-17
Power Supply
ED04-703
2. Power Supply
Note:
Indoor Units
Outdoor Units
FTKD50FVM
RKD50BVM
FTKD60FVM
RKD60BVM
FTKD71FVM
RKD71BVM
FTKD50FVM
RKD50BVMA
FTKD60FVM
RKD60BVMA
FTKD71FVM
RKD71BVMA
FTXD50FVM
RXD50BVMA
FTXD60FVM
RXD60BVMA
FTXD71FVM
RXD71BVMA
Power Supply
1, 220~240V, 50Hz
1, 220~230V, 60Hz
ED04-703
Functions
5
~46
5
~46
5
~46
15
~18
PAM Control
Compressor
Swing Compressor
Longlife Filter
Rotary Compressor
Reluctance DC Motor
Washable Grille
Comfort
Control
Operation
Functions
FTXD50/60/71FVM
RXD50/60/71BVMA
FTXD50/60/71FVM
RXD50/60/71BVMA
Basic
Function
Functions
FTKD50/60/71FVM
RKD50/60/71BVMA
FTKD50/60/71FVM
RKD50/60/71BVMA
Category
FTKD50/60/71FVM
RKD50/60/71BVM
FTKD50/60/71FVM
RKD50/60/71BVM
3. Functions
Category
Health &
Clean
Power-Airflow Diffuser
Wide-Angle Louvers
3-D Airflow
Intelligent Eye
Timer
Chargeless
Automatic Defrosting
Power Selection
Automatic Operation
Fan Only
ECONO Mode
Temperature Display
Lifestyle
New Powerful Operation (NonConvenience Inverter)
Flexibility
Remote
Control
Remote
Controller
Wireless
Wired
Specifications
ED04-703
4. Specifications
4.1
Cooling Only
50Hz 220-230-240V / 60Hz 220-230V
Model
Indoor Units
Outdoor Units
Capacity
Rated (Min.~Max.)
Running Current
Rated (Max.)
Power Consumption
Rated (Min.~Max.)
Power Factor
COP
Rated (Min.~Max.)
Liquid
Piping
Gas
Connections
Drain
Heat Insulation
Max. lnterunit Piping Length
Max. lnterunit Height Difference
Chargeless
Amount of Additional Charge of
Refrigerant
Indoor Unit
Front Panel Color
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L/SL
Sound
Outdoor Unit
Casing Color
Type
Compressor
Model
Motor Output
Type
Refrigerant Oil
Charge
Type
Refrigerant
Charge
Fan
m/min (cfm)
Type
Motor Output
Running Current (Rated)
Power Consumption (Rated)
Power Factor (Rated)
Starting Current
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation Sound
Drawing No.
Fan
Note:
10
FTKD60FVM
RKD60BVM
6.2 (1.5~6.5)
21,200 (5,100~22,200)
5,330 (1,290~5,590)
FTKD71FVM
RKD71BVM
7.1 (2.1~7.6)
24,200 (7,200~25,900)
6,110 (1,810~6,540)
7.3-7.0-6.7/7.3-7.0
9.6-9.2-8.8/9.6-9.2
11.7-11.2-10.7/11.7-11.2
1,600 (450~2,300)
2,100 (450~2,700)
2,550 (530~3,210)
99.6-99.4-99.5/99.6-99.4
99.4-99.2-99.4/99.4-99.2
99.1-99.0-99.3/99.1-99.0
W/W
3.25 (3.33~2.57)
2.95 (3.33~2.41)
2.78 (3.96~2.37)
mm
mm
mm
6.4
12.7
18.0
Both Liquid and Gas Pipes
30
20
10
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
20
10
9.5
15.9
18.0
Both Liquid and Gas Pipes
30
20
10
20
20
50
m
m
m
g/m
m/min
(cfm)
kW
Btu/h
kcal/h
FTKD50FVM
RKD50BVM
5.2 (1.5~5.9)
17,700 (5,100~20,100)
4,470 (1,290~5,070)
H
M
L
SL
W
Steps
A
W
%
mm
mm
kg
kg
FTKD50FVM
FTKD60FVM
FTKD71FVM
White
White
White
16.8 (593)
17.5 (618)
18.3 (646)
14.0 (494)
14.6 (516)
15.3 (540)
11.8 (417)
12.2 (431)
12.7 (448)
10.4 (367)
10.8 (381)
11.3 (399)
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
43
43
43
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
0.19-0.18-0.17/0.19-0.18
0.21-0.20-0.19/0.21-0.20
0.23-0.22-0.21/0.23-0.22
40
45
50
95.7-96.6-98.0/95.7-96.6
97.4-97.8-98.7/97.4-97.8
98.8-98.8-99.2/98.8-98.8
Microcomputer Control
Microcomputer Control
Microcomputer Control
2901,050238
2901,050238
2901,050238
3371,147366
3371,147366
3371,147366
12
12
12
17
17
17
dBA
W
L
kg
H
L
W
A
W
%
A
mm
mm
kg
kg
dBA
44/40/35/32
45/41/36/33
46/42/37/34
RKD50BVM
Ivory White
Hermetically Sealed Swing Type
2YC32UXD
1,500
SE56P
0.65
R-22
1.25
42.8 (1,511)
40.7 (1,437)
Propeller
53
7.11-6.82-6.53/7.11-6.82
1,560
99.7-99.5-99.5/99.7-99.5
7.4
735825300
784960390
48
53
H : 47 SL : 44
3D056204
RKD60BVM
Ivory White
Hermetically Sealed Swing Type
2YC32UXD
1,500
SE56P
0.65
R-22
1.60
46.3 (1,653)
42.9 (1,515)
Propeller
53
9.39-9.00-8.61/9.39-9.00
2,055
99.5-99.3-99.4/99.5-99.3
9.6
735825300
784960390
52
57
H : 49 SL : 46
3D056205
RKD71BVM
Ivory White
Hermetically Sealed Swing Type
2YC45ZXD
1,900
SE56P
0.75
R-22
1.80
51.5 (1,819)
41.5 (1,465)
Propeller
53
11.47-10.98-10.49/11.47-10.98
2,500
99.1-99.0-99.3/99.1-99.0
11.7
735825300
784960390
54
59
H : 52 SL : 49
3D056206
The data are based on the conditions shown in the table below.
Cooling
Piping Length
Conversion Formulae
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
7.5m
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
ED04-703
Specifications
Indoor Units
Outdoor Units
Capacity
Rated (Min.~Max.)
Running Current
Rated (Max.)
Power Consumption
Rated (Min.~Max.)
Power Factor
COP
Rated (Min.~Max.)
Liquid
Piping
Gas
Connections
Drain
Heat Insulation
Max. lnterunit Piping Length
Max. lnterunit Height Difference
Chargeless
Amount of Additional Charge of
Refrigerant
Indoor Unit
Front Panel Color
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L/SL
Sound
Outdoor Unit
Casing Color
Type
Compressor
Model
Motor Output
Type
Refrigerant Oil
Charge
Type
Refrigerant
Charge
7.4-7.0-6.7/7.4-7.0
9.6-9.2-8.8/9.6-9.2
11.9-11.4-10.9/11.9-11.4
1,600 (450~2,300)
2,100 (630~3,210)
2,600 (720~3,350)
98.3-99.4-99.5/98.3-99.4
99.4-99.2-99.4/99.4-99.2
99.3-99.2-99.4/99.3-99.2
W/W
3.25 (3.33~2.57)
2.95 (3.49~2.37)
2.73 (4.03~2.39)
mm
mm
mm
6.4
12.7
18.0
Both Liquid and Gas Pipes
30
20
10
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
20
10
9.5
15.9
18.0
Both Liquid and Gas Pipes
30
20
10
20
20
50
H
M
L
SL
W
Steps
A
W
%
mm
mm
kg
kg
FTKD50FVM
FTKD60FVM
FTKD71FVM
White
White
White
16.8 (593)
17.5 (618)
18.3 (646)
14.0 (494)
14.6 (516)
15.3 (540)
11.8 (417)
12.2 (431)
12.7 (448)
10.4 (367)
10.8 (381)
11.3 (399)
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
43
43
43
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
0.19-0.18-0.17/0.19-0.18
0.21-0.20-0.19/0.21-0.20
0.23-0.22-0.21/0.23-0.22
40
45
50
95.7-96.6-98.0/95.7-96.6
97.4-97.8-98.7/97.4-97.8
98.8-98.8-99.2/98.8-98.8
Microcomputer Control
Microcomputer Control
Microcomputer Control
2901,050238
2901,050238
2901,050238
3371,147366
3371,147366
3371,147366
12
12
12
17
17
17
dBA
W
L
kg
H
L
m/min (cfm)
Type
Fan
Motor Output
Running Current (Rated)
Power Consumption (Rated)
Power Factor (Rated)
Starting Current
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation Sound
Drawing No.
Note:
FTKD71FVM
RKD71BVMA
7.1 (2.9~8.0)
24,200 (9,900~27,300)
6,110 (2,490~6,880)
g/m
Fan
FTKD60FVM
RKD60BVMA
6.2 (2.2~7.6)
21,200 (7,500~25,900)
5,330 (1,890~6,540)
m
m
m
m/min
(cfm)
kW
Btu/h
kcal/h
FTKD50FVM
RKD50BVMA
5.2 (1.5~5.9)
17,700 (5,100~20,100)
4,470 (1,290~5,070)
W
A
W
%
A
mm
mm
kg
kg
dBA
44/40/35/32
45/41/36/33
46/42/37/34
RKD50BVMA
Ivory White
Hermetically Sealed Swing Type
2YC32UXD
1,500
SE56P
0.65
R-22
1.25
42.8 (1,511)
40.7 (1,437)
Propeller
53
7.21-6.82-6.53/7.21-6.82
1,560
98.3-99.5-99.5/98.3-99.5
7.4
735825300
784960390
48
53
H : 47 SL : 44
3D055905
RKD60BVMA
Ivory White
Hermetically Sealed Swing Type
2YC45ZXD
1,900
SE56P
0.75
R-22
1.80
46.3 (1,635)
42.9 (1,515)
Propeller
53
9.39-9.00-8.61/9.39-9.00
2,055
99.5-99.3-99.4/99.5-99.3
9.6
735825300
784960390
54
59
H : 49 SL : 46
3D055906
RKD71BVMA
Ivory White
Hermetically Sealed Swing Type
2YC63ZXD
1,900
SE56P
0.65
R-22
1.80
51.5 (1,819)
41.5 (1,465)
Propeller
53
11.67-11.18-10.69/11.67-11.18
2,550
99.3-99.2-99.4/99.3-99.2
11.9
735825300
784960390
56
61
H : 52 SL : 49
3D055907
The data are based on the conditions shown in the table below.
Cooling
Piping Length
Conversion Formulae
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
7.5m
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
11
Specifications
4.2
ED04-703
Heat Pump
50Hz 220-230-240V / 60Hz 220-230V
Indoor Units
Model
Outdoor Units
Capacity
Rated (Min.~Max.)
Running Current
Rated (Max.)
Power Consumption
Rated (Min.~Max.)
Power Factor
COP
Rated (Min.~Max.)
Liquid
Piping
Connections Gas
Drain
Heat Insulation
Max. lnterunit Piping Length
Max. lnterunit Height Difference
Chargeless
Amount of Additional Charge of
Refrigerant
Indoor Unit
Front Panel Color
Air Flow Rate m/min
(cfm)
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L/SL
Sound
Outdoor Unit
Casing Color
Type
Compressor Model
Motor Output
Model
Refrigerant
Oil
Charge
Model
Refrigerant
Charge
Fan
Note:
12
FTXD50FVM
RXD50BVMA
FTXD60FVM
RXD60BVMA
kW
Btu/h
kcal/h
Cooling
5.2 (1.5~5.9)
17,700 (5,100~20,100)
4,470 (1,290~5,070)
Heating
6.5 (1.5~8.0)
22,200 (5,100~27,300)
5,590 (1,290~6,880)
Cooling
6.2 (2.2~7.6)
21,200 (7,500~25,900)
5,330 (1,890~6,540)
Heating
7.2 (2.2~9.0)
24,600 (7,500~30,700)
6,190 (1,890~7,740)
9.7-9.3-8.9/9.7-9.3
7.4-7.0-6.7/7.4-7.0
8.5-8.1-7.7/8.5-8.1
9.6-9.2-8.8/9.6-9.2
1,600 (450~2,300)
1,840 (410~2,800)
2,100 (630~3,210)
2,120 (570~3,230)
98.3-99.4-99.5/98.3-99.4
98.4-98.8-99.6/98.4-98.8
99.4-99.2-99.4/99.4-99.2
99.3-99.1-99.3/99.3-99.1
W/W
3.25 (3.33~2.57)
3.53 (3.66~2.86)
2.95 (3.49~2.37)
3.40 (3.86~2.79)
6.4
12.7
18.0
Both Liquid and Gas Pipes
30
20
10
mm
mm
mm
m
m
m
g/m
H
M
L
SL
W
Steps
A
W
%
mm
mm
kg
kg
L
kg
H
L
W
A
W
%
A
mm
mm
kg
kg
dBA
20
20
FTXD50FVM
White
FTXD60FVM
White
16.8 (593)
14.0 (494)
11.8 (417)
10.4 (367)
17.5 (618)
14.9 (526)
12.5 (441)
11.0 (388)
17.5 (618)
14.6 (516)
12.2 (431)
10.8 (381)
dBA
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
20
10
44/40/35/32
42/38/33/30
45/41/36/33
RXD50BVMA
Ivory White
Hermetically Sealed Swing Type
2YC32UXD
1,500
SE56P
0.65
R-22
1.25
42.8 (1,511)
40.7 (1,437)
40.7 (1,437)
40.7 (1,437)
Propeller
53
7.21-6.82-6.53/7.21-6.82
8.31-7.92-7.53/8.31-7.92
1,560
1,800
98.3-99.5-99.5/98.3-99.5
98.5-98.8-99.6/98.5-98.8
8.5
735825300
784960390
49
54
H : 47 SL : 44
H : 48 SL : 45
3D055908
18.7 (660)
16.1 (569)
13.6 (480)
11.8 (417)
44/40/35/32
RXD60BVMA
Ivory White
Hermetically Sealed Swing Type
2YC45ZXD
1,500
SE56P
0.75
R-22
1.80
46.3 (1,635)
44.2 (1,561)
42.9 (1,515)
44.2 (1,561)
Propeller
53
9.39-9.00-8.61/9.39-9.00
9.49-9.10-8.71/9.49-9.10
2,055
2,075
99.5-99.3-99.4/99.5-99.3
99.4-99.1-99.3/99.4-99.1
9.7
735825300
784960390
55
59
H : 49 SL : 46
L : 49 SL : 46
3D055909
The data are based on the conditions shown in the table below.
Cooling
Heating
Piping Length
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
Indoor ; 20CDB
Outdoor ; 7CDB/6CWB
7.5m
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
ED04-703
Specifications
Capacity
Rated (Min.~Max.)
Running Current
Rated (Max.)
Power Consumption
Rated (Min.~Max.)
Power Factor (Rated)
COP
Rated (Min.~Max.)
Liquid
Piping
Connections Gas
Drain
Heat Insulation
Max.Interunit Piping Length
Max.Interunit Height Difference
Chargeless
Amount of Additional Charge of
Refrigerant
Indoor Unit
Front Panel Color
Air Flow Rate
FTXD71FVM
RXD71BVMA
Outdoor Units
kW
Btu/h
kcal/h
Cooling
7.1 (2.9~8.0)
24,200 (9,900~27,300)
6,110 (2,490~6,880)
Heating
8.5 (2.9~9.7)
29,000 (9,900~33,100)
7,310 (2,490~8,340)
11.9-11.4-10.9/11.9-11.4
11.8-11.3-10.9/11.8-11.3
2,600 (720~3,350)
2,580 (660~3,490)
99.3-99.2-99.4/99.3-99.2
99.4-99.3-98.6/99.4-99.3
W/W
2.73 (4.03~2.39)
m
m
m
g/m
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L/SL
Sound
Outdoor Unit
Casing Color
Type
Compressor Model
Motor Output
Model
Refrigerant
Oil
Charge
Model
Refrigerant
Charge
H
M
L
SL
W
Steps
A
W
%
mm
mm
kg
kg
dBA
18.3 (646)
15.3 (540)
12.7 (448)
11.3 (399)
46/42/37/34
Type
Motor Output
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Starting Current
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation Sound
Drawing No.
Fan
W
A
W
%
A
mm
mm
kg
kg
dBA
46/42/37/34
RXD71BVMA
Ivory White
Hermetically Sealed Swing Type
2YC63ZXD
1,900
SE56P
0.65
R-22
1.80
L
kg
H
L
19.8 (699)
17.1 (604)
14.4 (508)
12.6 (445)
Note:
50
FTXD71FVM
White
m/min
(cfm)
Fan
3.29 (4.39~2.78)
9.5
15.9
18.0
Both Liquid and Gas Pipes
30
20
10
mm
mm
mm
51.5 (1,819)
41.5 (1,465)
41.9 (1,480)
37.4 (1,321)
Propeller
53
11.67-11.18-10.69/11.67-11.18
2,550
99.3-99.2-99.4/99.3-99.2
11.57-11.08-10.69/11.57-11.08
2,530
99.4-99.3-98.6/99.4-99.3
11.9
735825300
784960390
57
61
H : 52 SL : 49
H : 52 SL : 49
3D055910
The data are based on the conditions shown in the table below.
Cooling
Heating
Piping Length
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
Indoor ; 20CDB
Outdoor ; 7CDB/6CWB
7.5m
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
13
Dimensions
ED04-703
5. Dimensions
5.1
Indoor Units
AIR FLOW(INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
REAR
1050
RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50
OPERATION LAMP
SIGNAL RECEIVER
MODEL NAME
PLATE
290
FLAPS
SIGNAL
TRANSMITTER
18
58
MIN.50
(SPACE FOR
MAINTENANCE)
REQUIRED SPACE
INCLUDING
INSTALLATION PLATE
240
238
BLADE ANGLES
52.5
14.5
893.5
HORIZONTAL BLADE
(AUTOMATIC)
COOLING
35 5
35
FAN
60
VERTICAL BLADE(AUTOMATIC)
(ARC433B71)
50
5
55
50
99.5
WALL HOLE
80 HOLE
52
WIRELESS REMOTE
CONTROLLER
52
40 10
40
155.5
290
163
DRY
10
30
REAR
LEFT
MIN.30
(SPACE FOR
PERFORMANCE)
FTKD50FVM
3D055868
55
AIR FLOW(INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
REAR
1050
LEFT
RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50
OPERATION LAMP
SIGNAL RECEIVER
FLAPS
MODEL NAME
PLATE
290
SIGNAL
TRANSMITTER
1050
BLADE ANGLES
893.5
HORIZONTAL BLADE
(AUTOMATIC)
COOLING
40 10
40
CONTROLLER
(ARC433B71)
35
35
FAN
VERTICAL BLADE(AUTOMATIC)
5
50 50
5
55
14
55
60
WALL HOLE FOR
EMBEDDED PIPING
80 HOLE
99.5
52
WIRELESS REMOTE
52
10
155.5
290
163
DRY
52.5
14.5
58
18
MIN.50
(SPACE FOR
MAINTENANCE)
REQUIRED SPACE
INCLUDING
INSTALLATION PLATE
240
238
30
REAR
MIN.30
(SPACE FOR
PERFORMANCE)
FTKD60FVM
WALL HOLE
80 HOLE
3D055869
ED04-703
Dimensions
AIR FLOW(INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
THE MARK () SHOWS PIPING DIRECTION
RIGHT
(SPACE FOR
MAINTENANCE)
MIN. 50
INCLUDING
INSTALLATION PLATE
240
238
OPERATION LAMP
SIGNAL RECEIVER
SIGNAL
TRANSMITTER
18
58
1050
BLADE ANGLES
893.5
HORIZONTAL BLADE
(AUTOMATIC)
COOLING
52.5
14.5
FLAPS
MODEL NAME
PLATE
290
MIN. 50
(SPACE FOR
MAINTENANCE)
REQUIRED SPACE
52
163
155.5
DRY
10
40 10
40
35 5
35
VERTICAL BLADE(AUTOMATIC)
FAN
60
(ARC433B71)
50
5
55
50
99.5
WALL HOLE
80 HOLE
52
WIRELESS REMOTE
CONTROLLER
30
REAR
1050
290
REAR
LEFT
MIN. 30
(SPACE FOR
PERFORMANCE)
FTKD71FVM
3D056088
55
FTXD50FVM
MIN. 30
(SPACE FOR
PERFORMANCE)
AIR FLOW(INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
THE MARK () SHOWS PIPING DIRECTION
REAR
RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50
FLAPS
SIGNAL
TRANSMITTER
1050
BLADE ANGLES
HEATING
DRY
155.5
163
COOLING
52.5
893.5
HORIZONTAL BLADE
(AUTOMATIC)
14.5
58
18
MIN. 50
(SPACE FOR
MAINTENANCE)
REQUIRED SPACE
MODEL NAME
PLATE
290
OPERATION LAMP
SIGNAL RECEIVER
INDOOR UNIT ON/OFF
SWITCH
INSTALLATION
INCLUDING PLATE
240
238
WIRELESS REMOTE
(ARC433B70)
55
FAN
15
35
52
15
40 10
40
5
35
55
VERTICAL BLADE(AUTOMATIC)
5
50
5
55
55
50
60
WALL HOLE FOR
EMBEDDED PIPING
80 HOLE
99.5
52
10
CONTROLLER
30
1050
290
REAR
LEFT
WALL HOLE
80 HOLE
3D055875
15
Dimensions
ED04-703
FTXD60FVM
AIR FLOW(INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
REAR
RIGHT
(SPACE FOR
MAINTENANCE)
MIN. 50
INCLUDING
INSTALLATION PLATE
240
238
OPERATION LAMP
SIGNAL RECEIVER
FLAPS
290
MODEL NAME
PLATE
SIGNAL
TRANSMITTER
18
1050
BLADE ANGLES
HORIZONTAL BLADE
(AUTOMATIC)
COOLING
893.5
DRY
10
35 5
15
55
55
FAN
35
VERTICAL BLADE(AUTOMATIC)
60
CONTROLLER
(ARC433B70)
50
5
55
50
99.5
WALL HOLE
80 HOLE
52
WIRELESS REMOTE
15
40 10
40
52
155.5
163
HEATING
52.5
14.5
58
MIN. 50
(SPACE FOR
MAINTENANCE)
REQUIRED SPACE
30
1050
290
REAR
LEFT
MIN. 30
(SPACE FOR
PERFORMANCE)
3D055876
55
AIR FLOW(INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
THE MARK () SHOWS PIPING DIRECTION
REAR
1050
RIGHT
(SPACE FOR
MAINTENANCE)
MIN. 50
INCLUDING
INSTALLATION PLATE
240
238
OPERATION LAMP
SIGNAL RECEIVER
SIGNAL
TRANSMITTER
18
1050
BLADE ANGLES
HORIZONTAL BLADE
(AUTOMATIC)
COOLING
893.5
HEATING
WIRELESS REMOTE
15
40 10
40
15
55
FAN
35
5
35
55
VERTICAL BLADE(AUTOMATIC)
CONTROLLER
(ARC433B70)
5
5
55
16
50
50
60
WALL HOLE FOR
EMBEDDED PIPING
80 HOLE
99.5
52
10
52
163
DRY
52.5
155.5
290
58
14.5
FLAPS
MODEL NAME
PLATE
290
MIN. 50
(SPACE FOR
MAINTENANCE)
REQUIRED SPACE
30
REAR
LEFT
MIN. 30
(SPACE FOR
PERFORMANCE)
FTXD71FVM
WALL HOLE
80 HOLE
3D056090
55
ED04-703
5.2
Dimensions
Outdoor Units
DRAIN OUTLET
(I.D.15.9 HOSE FOR CONNECTION)
825
100
78
50
50
350
100
IN CASE OF REMOVING
STOP VALVE COVER
WIRING INLET
TERMINAL STRIP
WITH EARTH TERMINAL
89 64
735
NAME PLATE
350
350
50
300
330
580
25
10
350
36
124
100
325
INDICATION LABEL
(REFRIGERANT)
155
18
160
30
GAS STOP VALVE
(12.7 CuT)
SERVICE PORT
3D037848H
DRAIN OUTLET
(I.D.15.9 HOSE FOR CONNECTION)
825
100
78
350
580
50
50
350
100
300
IN CASE OF REMOVING
STOP VALVE COVER
25
350
10
330
50
NAME PLATE
WIRING INLET
TERMINAL STRIP
WITH EARTH TERMINAL
89
64
735
350
36
124
100
325
INDICATION LABEL
(REFRIGERANT)
155
18
160
30
GAS STOP VALVE
(15.9 CuT)
3D050687B
17
Dimensions
ED04-703
DRAIN OUTLET
(I.D. 15.9 HOSE FOR CONNECTION)
825
100
78
350
580
50
50
350
100
330
300
IN CASE OF REMOVING
STOP VALVE COVER
25
10
350
50
NAME PLATE
WIRING INLET
TERMINAL STRIP
WITH EARTH TERMINAL
F RI
E
89
L Y
OZ
64
735
350
36
124
100
325
INDICATION LABEL
(REFRIGERANT)
155
160
18
30
GAS STOP VALVE
(15.9 CuT)
3D050688
18
ED04-703
Wiring Diagrams
6. Wiring Diagrams
6.1
Indoor Units
FTKD50/60/71FVM, FTXD50/60/71FVM
FIELD WIRING.
PCB3
S27
PCB1
S26
H1
~
~
RECTIFIER
Fu
3.15A
H2
t
R1T
S38
BLK
WHT
RED 3
GRN
/
YLW
H3
TRANSMISSION
CIRCUIT
X1M
CAUTION
NOTE THAT OPERATION WILL
RESTART AUTOMATICALLY IF
THE MAIN POWER SUPPLY IS
TURNED OFF AND THEN BACK
ON AGAIN.
FG
PCB4
S37
S21
S1
RED
S36
S35
INTELLIGENT EYE
S32
S28
S6
S8
BLU
BRN
ORG
WHT
H2P H3P
FG
Fu
H1 ~ H3
H1P ~ H3P
M1F
M1S, M2S
PCB1~ PCB5
R1T, R2T
S1 ~ S38
S1W
X1M
M1F
t
S29
SIGNAL
INDOOR
R2T
RECEIVER
WIRELESS
S1W
REMOTE
BRN
RED
ORG
YLW
PNK
BLU
PCB2
RED
ORG
YLW
PNK
BLU
SENSOR
M1S
OUTDOOR
: FRAME GROUND
: FUSE
: HARNESS
: PILOT LAMP
: FAN MOTOR
: SWING MOTOR
: PRINTED CIRCUIT BOARD
: THERMISTOR
: CONNECTOR
: OPERATION SWITCH
: TERMINAL STRIP
: PROTECTIVE EARTH
M2S
3D038530N
CONTROLLER
6.2
Outdoor Units
RKD50/60/71BVM, RKD50/60/71BVMA
AC2
WHT
BLU
V2
t
BLK
BLK
RED
1 S51 5
1 S101 5
S91
MRC W
POWER SUPPLY
~50Hz 220-240V
~60Hz 220-230V
CN14
10
S32
S31
S34
M1C
X11A
U
RED
V M N
YLW 3
BLU
W
BRN
Q1L
10
S90 6
1
BLU
BLU
BLU
BLU
BLU
RED
BLK
WHT
GRN
WHT
YLW
ORG
BLU
BRN
RED
M
S1W
S2
Y2E
S4W
S2~S102
: CONNECTOR
LEDA
: PILOT LAMP
PCB1, PCB2 : PRINTED CIRCUIT BOARD
L
: LIVE
N
: NEUTRAL
S1W : FORCED OPERATION ON/OFF SW (SW1)
S4W : LOCAL SETTING SW (SW4)
SA1 : SURGE ARRESTER
DB1 : DIODE BRIDGE
M1C : COMPRESSOR MOTOR
M1F : FAN MOTOR
L1R : REACTOR
Q1L
CT1
MID
SPM
:
:
:
:
S33
10
S40
S6
PCB1
1 S102 5
LEDA
S71
1 S20 6
1 S52 5
indoor
S80
S72
N
L
FIELD WIRING
BRN
3.15A
V5
BLU
YLW
RED
BRN
RED
R12T
FU2
S10
3
2
1
BLK
W
V
U
X1M
3
2
1
SPM
CN11
GRN
YLW
TO INDOOR UNIT
TB6
TB5
TB4
BLU
BLU
GRY
GRY
BLK
BLK
BLK
H2
RED
+ + +
N1
P2
M1F
BLU
BRN
ORG
WHT
S70
BLK
BLK
YLW
CT1
DB1
+
~
RED
GRY
MRM10
BLK
Z2C
H1
FU201 7
3.15A
BLU
E
AC1
P1
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
30A
MRM20
MID
Z1C
ORG
L2 P1
N1
P2
ORG
L1
BLK
BLK
BLK
BLK
BLK
SA1
HL FU1V3 HAC1
GRN
YLW
YLW
L1R
HE1
WHT
ORG
BRN
BLU
HE2
RED
PCB2
GRN
YLW
outdoor
OVERLOAD PROTECTOR
CURRENT TRANSFORMER
MOLDED INTER CONNECT DEVICE
SYSTEM POWER MODULE
ASSIGNMENTS OF
TERMINALS OF THE COMP.
U
V
N
W
3D037866H
19
Wiring Diagrams
ED04-703
RXD50/60/71BVMA
L1R
PCB2
HE1
YLW
CT1 H2
AC2
: FERRITE CORE
Z1C, Z2C
: TERMINAL STRIP
X1M
: ELECTRONIC EXPANSION VALVE
Y2E
: VARISTOR
V2~V5
FU1, FU2, FU201 : FUSE
HE1, HE2, HAC1
E, AC1, C2
H1, H2, HL
: CONNECTOR
L1, L2, X11A
MRM10, MRM20
: MAGNETIC RELAY
MRC/W
: THERMISTOR
R1T~R3T
BLU
YLW
RED
BRN
M1F
1M
M1C
X11A
U
RED
V M N
YLW
3
BLU
W
BRN
S80
S6
S20 6
S4W
: CONNECTOR
S2~S102
: PILOT LAMP
LEDA
PCB1, PCB2 : PRINTED CIRCUIT BOARD
L
: LIVE
N
: NEUTRAL
S1W : FORCED OPERATION ON/OFF SW (SW1)
S4W : LOCAL SETTING SW (SW4)
SA1 : SURGE ARRESTER
Y1R : REVERSING SOLENOID VALVE COIL
DB1 : DIODE BRIDGE
M1C : COMPRESSOR MOTOR
M1F : FAN MOTOR
S71
1
S33
GRY
Q1L
10
BLK
BLK
S31
S34
BLU
10
4
S40
S90 6
LEDA
S1W
S32
PCB1
S72
10
Y1R
S2
W
V
U
N
RED
CN14
1
3
S91
1 S102 5
1 S52 5
20
GRN
1 S101 5
RED
BLK
WHT
1 S51 5
indoor
BLU
BLU
BLU
BLU
BLU
FIELD WIRING
TB5
TB4
BRN
V5
N
L
POWER SUPPLY
~50Hz 220-240V
~60Hz 220-230V
TB6
W
V
U
BLU
BRN
ORG
WHT
S70
RED
RED
MRC W
3
2
1
S10
1
R12T
FU2
3.15A
X1M
3
2
1
P2
SPM
BLK
N1
P2
CN11
1
BLK
TO INDOOR UNIT
~ -
BLU
V2
RED
WHT
ORG
BRN
BLU
WHT
GRN
YLW
BLK
BLK
Z2C
H1
MRM10
BLK
DB1
+
~
L2 P1
N1
RED
BLU
BLU
GRY
GRY
BLK
BLK
30A
L1
P1
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
HL FU1 V3 HAC1
MRM20
E
AC1
FU201 7
3.15A
MID
Z1C
ORG
BLK
BLK
BLK
BLK
BLK
SA1
ORG
WHT
YLW
ORG
BLU
BRN
RED
GRN
YLW
YLW
HE2
BLK
BLK
GRN
YLW
M
Y2E
outdoor
L1R : REACTOR
Q1L : OVERLOAD PROTECTOR
CT1 : CURRENT TRANSFORMER
MID : MOLDED INTER CONNECT DEVICE
SPM : SYSTEM POWER MODULE
ASSIGNMENTS OF
TERMINALS OF THE COMP.
U
N
V
W
3D037854J
ED04-703
Piping Diagrams
7. Piping Diagrams
7.1
Indoor Units
7.1.1
Cooling Only
FTKD50FVM
FTKD60FVM
INDOOR UNIT
INDOOR UNIT
(7.9CuT)
(7.9CuT)
HEAT EXCHANGER
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
FIELD PIPING
(6.4CuT)
FIELD PIPING
(12.7CuT)
THERMISTOR
ON HEAT EXCH.
M
FAN MOTOR
FAN MOTOR
FIELD PIPING
(15.9CuT)
(12.7CuT)
REFRIGERANT FLOW
COOLING
4D054932A
(12.7CuT)
REFRIGERANT FLOW
COOLING
4D050919E
FTKD71FVM
INDOOR UNIT
(7.9CuT)
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
CROSS FLOW FAN
FIELD PIPING
(9.5CuT)
FIELD PIPING
(15.9CuT)
M
FAN MOTOR
(12.7CuT)
REFRIGERANT FLOW
COOLING
4D053131A
21
Piping Diagrams
7.1.2
ED04-703
Heat Pump
FTXD50FVM
FTXD60FVM
INDOOR UNIT
INDOOR UNIT
(7.9CuT)
(7.9CuT)
HEAT EXCHANGER
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
FIELD PIPING
(6.4CuT)
FIELD PIPING
(12.7CuT)
THERMISTOR
ON HEAT EXCH.
FIELD PIPING
(6.4CuT)
FAN MOTOR
(12.7CuT)
FIELD PIPING
(15.9CuT)
REFRIGERANT FLOW
COOLING
HEATING
M
FAN MOTOR
(12.7CuT)
REFRIGERANT FLOW
COOLING
HEATING
4D040081Q
4D040082P
FTXD71FVM
INDOOR UNIT
(7.9CuT)
HEAT EXCHANGER
THERMISTOR
ON HEAT
EXCH.
FIELD PIPING
(9.5CuT)
FIELD PIPING
(15.9CuT)
M
FAN MOTOR
(12.7CuT)
REFRIGERANT FLOW
COOLING
HEATING
4D040083G
22
ED04-703
Piping Diagrams
7.2
Outdoor Units
7.2.1
Cooling Only
RKD50BVM, RKD50BVMA
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
THERMISTOR
7.9CuT
7.9CuT
12.7CuT
7.9CuT
CAPILLARY TUBE 1
7.9CuT
MUFFLER
WITH
FILTER
7.9CuT
CAPILLARY TUBE 2
CAPILLARY TUBE 3
HEAT EXCHANGER
THERMISTOR
REFRIGERANT FLOW
COOLING
6.4CuT 6.4CuT
9.5CuT
7.9CuT
FILTER
CAPILLARY TUBE 4
MOTOR OPERATED
VALVE
MUFFLER
WITH
FILTER
PROPELLER FAN
7.9CuT
12.7CuT
6.4CuT
7.9CuT
DISCHARGE PIPE
THERMISTOR
12.7CuT
LIQUID
STOP VALVE
12.7CuT
GAS STOP VALVE
WITH SERVICE PORT
ACCUMULATOR
COMPRESSOR
FIELD PIPING
(6.4 CuT)
FIELD PIPING
(12.7 CuT)
3D037851B
RKD60BVM, RKD60BVMA
OUTDOOR UNIT
HEAT EXCHANGER
7.9CuT
7.9CuT
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 1
7.9CuT
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 2
CAPILLARY TUBE 3
7.9CuT
HEAT
EXCHANGER
THERMISTOR
7.9CuT
CAPILLARY TUBE 4
MUFFLER
WITH
FILTER
PROPELLER FAN
7.9CuT
12.7CuT
MOTOR OPERATED
VALVE
12.7CuT
6.4CuT
7.9CuT
DISCHARGE PIPE
THERMISTOR
REFRIGERANT FLOW
COOLING
FILTER
MUFFLER
WITH
FILTER
6.4CuT
6.4CuT 6.4CuT
9.5CuT
12.7CuT
LIQUID
STOP VALVE
12.7CuT
ACCUMULATOR
COMPRESSOR
FIELD PIPING
(6.4 CuT)
FIELD PIPING
(15.9 CuT)
3D037852H
23
Piping Diagrams
ED04-703
RKD71BVM, RKD71BVMA
OUTDOOR UNIT
HEAT EXCHANGER
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 1
7.9CuT
7.9CuT
9.5CuT
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 2
CAPILLARY TUBE 3
7.9CuT
7.9CuT
HEAT
EXCHANGER
THERMISTOR
MUFFLER
WITH
FILTER
6.4CuT
7.9CuT
CAPILLARY TUBE 4
FILTER
MOTOR OPERATED
VALVE
MUFFLER
WITH
FILTER
PROPELLER FAN
7.9CuT
12.7CuT
7.9CuT
12.7CuT
DISCHARGE PIPE
THERMISTOR
REFRIGERANT FLOW
COOLING
6.4CuT 6.4CuT
12.7CuT
6.4CuT
LIQUID
STOP VALVE
12.7CuT
ACCUMULATOR
COMPRESSOR
FIELD PIPING
(9.5 CuT)
FIELD PIPING
(15.9 CuT)
3D050337
7.2.2
Heat Pump
RXD50BVMA
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
THERMISTOR
7.9CuT
7.9CuT
CAPILLARY TUBE 1
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 2
CAPILLARY TUBE 3
HEAT EXCHANGER
THERMISTOR
MUFFLER
WITH
FILTER
PROPELLER FAN
12.7CuT
FOUR WAY
VALVE
ON:HEATING
MOTOR OPERATED
VALVE
12.7CuT
7.9CuT
HEATING
FILTER
CAPILLARY TUBE 4
12.7CuT
REFRIGERANT FLOW
COOLING
6.4CuT 6.4CuT
7.9CuT
MUFFLER
WITH
FILTER
15.9CuT
12.7CuT
MUFFLER
6.4CuT
LIQUID
STOP VALVE
7.9CuT
DISCHARGE PIPE
THERMISTOR
12.7CuT
ACCUMULATOR
COMPRESSOR
24
FIELD PIPING
(6.4 CuT)
FIELD PIPING
(12.7 CuT)
3D037849C
ED04-703
Piping Diagrams
RXD60BVMA
OUTDOOR UNIT
HEAT EXCHANGER
7.9CuT
7.9CuT
7.9CuT
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 1
7.9CuT
7.9CuT
7.9CuT
7.9CuT
HEAT
EXCHANGER
THERMISTOR
CAPILLARY TUBE 2
CAPILLARY TUBE 3
MUFFLER
WITH
FILTER
6.4CuT
7.9CuT
CAPILLARY TUBE 4
12.7CuT
12.7CuT
7.9CuT
MOTOR OPERATED
VALVE
MUFFLER
WITH
FILTER
FOUR WAY
VALVE
ON:HEATING
12.7CuT
HEATING
FILTER
M
PROPELLER FAN
REFRIGERANT FLOW
COOLING
6.4CuT 6.4CuT
12.7CuT
12.7CuT
MUFFLER
7.9CuT
6.4CuT
DISCHARGE PIPE
THERMISTOR
LIQUID
STOP VALVE
12.7CuT
GAS STOP VALVE
WITH SERVICE PORT
ACCUMULATOR
COMPRESSOR
FIELD PIPING
(6.4CuT)
FIELD PIPING
(15.9CuT)
3D037850C
RXD71BVMA
OUTDOOR UNIT
HEAT EXCHANGER
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 1
7.9CuT
7.9CuT
7.9CuT
7.9CuT
7.9CuT
CAPILLARY TUBE 2
CAPILLARY TUBE 3
7.9CuT
7.9CuT
7.9CuT
HEAT
EXCHANGER
THERMISTOR
CAPILLARY TUBE 4
12.7CuT
PROPELLER FAN
7.9CuT
MUFFLER
WITH
FILTER
FOUR WAY
VALVE
ON:HEATING
12.7CuT
12.7CuT
REFRIGERANT FLOW
COOLING
HEATING
FILTER
MUFFLER
WITH
FILTER
6.4CuT
6.4CuT 6.4CuT
12.7CuT
MOTOR OPERATED
VALVE
12.7CuT
FIELD PIPING
(9.5CuT)
MUFFLER
7.9CuT
DISCHARGE PIPE
THERMISTOR
6.4CuT
LIQUID
STOP VALVE
12.7CuT
COMPRESSOR
ACCUMULATOR
FIELD PIPING
(15.9CuT)
3D050338
25
Capacity Tables
ED04-703
8. Capacity Tables
8.1
Cooling Only
16.8
BF
0.29
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
30
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.33
3.84
1.23
5.09
3.71
1.35
4.84
3.59
1.46
4.75
3.54
1.51
4.60
3.47
1.58
4.36
3.35
1.70
16.0
22
5.57
3.77
1.23
5.32
3.65
1.35
5.08
3.54
1.47
4.99
3.49
1.52
4.84
3.42
1.59
4.60
3.31
1.71
18.0
25
5.81
3.93
1.24
5.56
3.82
1.36
5.32
3.71
1.48
5.23
3.67
1.53
5.08
3.60
1.60
4.84
3.50
1.71
19.0
27
5.93
4.13
1.25
5.68
4.02
1.36
5.44
3.92
1.48
5.35
3.87
1.53
5.20
3.81
1.60
4.96
3.71
1.72
22.0
30
6.29
3.97
1.26
6.04
3.88
1.37
5.80
3.79
1.49
5.70
3.75
1.54
5.56
3.70
1.61
5.32
3.61
1.73
24.0
32
6.53
3.86
1.26
6.28
3.78
1.38
6.04
3.69
1.50
5.94
3.66
1.55
5.80
3.61
1.62
5.56
3.53
1.74
Symbols
32
35
40
NOTE:
AFR
BF
: Bypass factor
(m/min.)
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056394
17.5
BF
0.30
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.96
4.20
1.61
5.96
4.20
1.77
5.77
4.10
1.92
5.66
4.04
1.98
5.49
3.95
2.08
5.20
3.80
2.23
16.0
22
6.64
4.33
1.62
6.35
4.18
1.78
6.06
4.04
1.93
5.94
3.98
1.99
5.77
3.90
2.09
5.48
3.76
2.24
18.0
25
6.92
4.48
1.63
6.63
4.35
1.78
6.35
4.21
1.94
6.23
4.16
2.00
6.06
4.08
2.10
5.77
3.95
2.25
19.0
27
7.07
4.68
1.63
6.78
4.55
1.79
6.49
4.42
1.94
6.37
4.36
2.01
6.20
4.29
2.10
5.91
4.16
2.26
22.0
30
7.49
4.49
1.65
7.21
4.38
1.80
6.92
4.26
1.96
6.80
4.21
2.02
6.63
4.15
2.11
6.34
4.03
2.27
24.0
32
7.78
4.36
1.66
7.49
4.25
1.81
7.20
4.15
1.97
7.09
4.10
2.03
6.91
4.04
2.12
6.63
3.94
2.28
Symbols
30
32
35
40
NOTE:
AFR
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056395
26
ED04-703
Capacity Tables
18.3
BF
0.31
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
30
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
6.15
4.33
1.96
6.15
4.33
2.14
6.15
4.33
2.33
6.15
4.33
2.41
6.15
4.33
2.52
5.95
4.23
2.71
16.0
22
7.55
4.84
1.97
7.27
4.69
2.16
6.94
4.52
2.34
6.81
4.45
2.42
6.61
4.35
2.53
6.28
4.18
2.72
18.0
25
7.93
5.01
1.98
7.60
4.85
2.17
7.27
4.69
2.36
7.13
4.62
2.43
6.94
4.53
2.54
6.61
4.37
2.73
19.0
27
8.09
5.21
1.98
7.76
5.05
2.17
7.43
4.89
2.36
7.30
4.83
2.44
7.10
4.74
2.55
6.77
4.59
2.74
22.0
30
8.58
4.99
2.00
8.25
4.85
2.19
7.92
4.71
2.38
7.79
4.66
2.45
7.59
4.58
2.57
7.26
4.44
2.76
24.0
32
8.91
4.84
2.01
8.58
4.71
2.20
8.25
4.58
2.39
8.12
4.53
2.47
7.92
4.46
2.58
7.59
4.33
2.77
Symbols
AFR
32
35
40
NOTE:
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056396
16.8
BF
0.29
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.33
3.84
1.23
5.09
3.71
1.35
4.84
3.59
1.46
4.75
3.54
1.51
4.60
3.47
1.58
4.36
3.35
1.70
16.0
22
5.57
3.77
1.23
5.32
3.65
1.35
5.08
3.54
1.47
4.99
3.49
1.52
4.84
3.42
1.59
4.60
3.31
1.71
18.0
25
5.81
3.93
1.24
5.56
3.82
1.36
5.32
3.71
1.48
5.23
3.67
1.53
5.08
3.60
1.60
4.84
3.50
1.71
19.0
27
5.93
4.13
1.25
5.68
4.02
1.36
5.44
3.92
1.48
5.35
3.87
1.53
5.20
3.81
1.60
4.96
3.71
1.72
22.0
30
6.29
3.97
1.26
6.04
3.88
1.37
5.80
3.79
1.49
5.70
3.75
1.54
5.56
3.70
1.61
5.32
3.61
1.73
24.0
32
6.53
3.86
1.26
6.28
3.78
1.38
6.04
3.69
1.50
5.94
3.66
1.55
5.80
3.61
1.62
5.56
3.53
1.74
Symbols
AFR
30
32
35
40
NOTE:
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056481
27
Capacity Tables
ED04-703
17.5
BF
0.30
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
30
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.96
4.20
1.16
5.96
4.20
1.77
5.77
4.10
1.92
5.66
4.04
1.98
5.49
3.95
2.08
5.20
3.80
2.23
16.0
22
6.64
4.33
1.62
6.35
4.18
1.78
6.06
4.04
1.93
5.94
3.98
1.99
5.77
3.90
2.09
5.48
3.76
2.24
18.0
25
6.92
4.48
1.63
6.63
4.35
1.78
6.35
4.21
1.94
6.23
4.16
2.00
6.06
4.08
2.10
5.77
3.95
2.25
19.0
27
7.07
4.68
1.63
6.78
4.55
1.79
6.49
4.42
1.94
6.37
4.36
2.01
6.20
4.29
2.10
5.91
4.16
2.26
22.0
30
7.49
4.49
1.65
7.21
4.38
1.80
6.92
4.26
1.96
6.80
4.21
2.02
6.63
4.15
2.11
6.34
4.03
2.27
24.0
32
7.78
4.36
1.66
7.49
4.25
1.81
7.20
4.15
1.97
7.09
4.10
2.03
6.91
4.04
2.12
6.63
3.94
2.28
Symbols
AFR
32
35
40
NOTE:
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056482
18.3
BF
0.31
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
6.15
4.33
1.99
6.15
4.33
2.19
6.15
4.33
2.38
6.15
4.33
2.46
6.15
4.33
2.57
5.95
4.23
2.76
16.0
22
7.55
4.84
2.01
7.27
4.69
2.20
6.94
4.52
2.39
6.81
4.45
2.47
6.61
4.35
2.58
6.28
4.18
2.77
18.0
25
7.93
5.01
2.02
7.60
4.85
2.21
7.27
4.69
2.40
7.13
4.62
2.48
6.94
4.53
2.59
6.61
4.37
2.79
19.0
27
8.09
5.21
2.02
7.76
5.05
2.22
7.43
4.89
2.41
7.30
4.83
2.48
7.10
4.74
2.60
6.77
4.59
2.79
22.0
30
8.58
4.99
2.04
8.25
4.85
2.23
7.92
4.71
2.43
7.79
4.66
2.50
7.59
4.58
2.62
7.62
4.44
2.81
24.0
32
8.91
4.84
2.05
8.58
4.71
2.24
8.25
4.58
2.44
8.12
4.53
2.51
7.92
4.46
2.63
7.59
4.33
2.82
Symbols
AFR
30
32
35
40
NOTE:
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056483
28
ED04-703
8.2
Capacity Tables
Heat Pump
16.8
BF
0.29
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
30
PI
TC
SHC
32
PI
TC
SHC
35
PI
TC
SHC
40
PI
14.0
20
5.33
3.84
1.23
5.09
3.71
1.35
4.84
3.59
1.46
4.75
3.54
1.51
4.60
3.47
1.58
4.36
3.35
1.70
16.0
22
5.57
3.77
1.23
5.32
3.65
1.35
5.08
3.54
1.47
4.99
3.49
1.52
4.84
3.42
1.59
4.60
3.31
1.71
18.0
25
5.81
3.93
1.24
5.56
3.82
1.36
5.32
3.71
1.48
5.23
3.67
1.53
5.08
3.60
1.60
4.84
3.50
1.71
19.0
27
5.93
4.13
1.25
5.68
4.02
1.36
5.44
3.92
1.48
5.35
3.87
1.53
5.20
3.81
1.60
4.96
3.71
1.72
22.0
30
6.29
3.97
1.26
6.04
3.88
1.37
5.80
3.79
1.49
5.70
3.75
1.54
5.56
3.70
1.61
5.32
3.61
1.73
24.0
32
6.53
3.86
1.26
6.28
3.78
1.38
6.04
3.69
1.50
5.94
3.66
1.55
5.80
3.61
1.62
5.56
3.53
1.74
Heating
AFR
17.5
INDOOR
EDB
10
10
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
15.0
4.38
1.56
5.11
1.63
5.84
1.71
6.72
1.80
7.31
1.86
20.0
4.15
1.60
4.89
1.67
5.62
1.75
6.50
1.84
7.09
1.90
22.0
4.06
1.61
4.80
1.69
5.53
1.77
6.41
1.86
7.00
1.92
24.0
3.97
1.63
4.71
1.71
5.44
1.78
6.32
1.87
6.91
1.93
25.0
3.93
1.64
4.66
1.71
5.39
1.79
6.28
1.88
6.86
1.94
27.0
3.84
1.66
4.57
1.73
5.31
1.81
6.19
1.90
6.77
1.96
Symbols
AFR
NOTE:
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056484
29
Capacity Tables
ED04-703
17.5
BF
0.30
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
30
PI
TC
SHC
32
PI
TC
SHC
35
PI
TC
SHC
40
PI
14.0
20
5.96
4.20
1.61
5.96
4.20
1.77
5.77
4.10
1.92
5.66
4.04
1.98
5.49
3.95
2.08
5.20
3.80
2.23
16.0
22
6.64
4.33
1.62
6.35
4.18
1.78
6.06
4.04
1.93
5.94
3.98
1.99
5.77
3.90
2.09
5.48
3.76
2.24
18.0
25
6.92
4.48
1.63
6.63
4.35
1.78
6.35
4.21
1.94
6.23
4.16
2.00
6.06
4.08
2.10
5.77
3.95
2.25
19.0
27
7.07
4.68
1.63
6.78
4.55
1.79
6.49
4.42
1.94
6.37
4.36
2.01
6.20
4.29
2.10
5.91
4.16
2.26
22.0
30
7.49
4.49
1.65
7.21
4.38
1.80
6.92
4.26
1.96
6.80
4.21
2.02
6.63
4.15
2.11
6.34
4.03
2.27
24.0
32
7.78
4.36
1.66
7.49
4.25
1.81
7.20
4.15
1.97
7.09
4.10
2.03
6.91
4.04
2.12
6.63
3.94
2.28
Heating
AFR
18.7
INDOOR
EDB
10
10
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
15.0
4.85
1.79
5.66
1.88
6.47
1.97
7.45
2.07
8.01
2.14
20.0
4.60
1.84
5.41
1.93
6.22
2.02
7.20
2.12
7.85
2.19
22.0
4.50
1.86
5.31
1.95
6.12
2.03
7.10
2.14
7.75
2.21
24.0
4.40
1.88
5.21
1.97
6.03
2.05
7.00
2.16
7.65
2.23
25.0
4.35
1.89
5.16
1.98
5.98
2.06
6.95
2.17
7.60
2.24
27.0
4.25
1.91
5.06
1.99
5.88
2.08
6.85
2.19
7.47
2.26
Symbols
NOTE:
AFR
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056485
30
ED04-703
Capacity Tables
18.3
BF
0.31
INDOOR
EWB
EDB
20
25
TC
SHC
PI
TC
SHC
PI
TC
SHC
30
PI
TC
SHC
32
PI
TC
SHC
35
PI
TC
SHC
40
PI
14.0
20
6.15
4.33
1.99
6.15
4.33
2.19
6.15
4.33
2.38
6.15
4.33
2.46
6.15
4.33
2.57
5.95
4.23
2.76
16.0
22
7.55
4.84
2.01
7.27
4.69
2.20
6.94
4.52
2.39
6.81
4.45
2.47
6.61
4.35
2.58
6.28
4.18
2.77
18.0
25
7.93
5.01
2.02
7.60
4.85
2.21
7.27
4.69
2.40
7.13
4.62
2.48
6.94
4.53
2.59
6.61
4.37
2.79
19.0
27
8.09
5.21
2.02
7.76
5.05
2.22
7.43
4.89
2.41
7.30
4.83
2.48
7.10
4.74
2.60
6.77
4.59
2.79
22.0
30
8.58
4.99
2.04
8.25
4.85
2.23
7.92
4.71
2.43
7.79
4.66
2.50
7.59
4.58
2.62
7.26
4.44
2.81
24.0
32
8.91
4.84
2.05
8.58
4.71
2.24
8.25
4.58
2.44
8.12
4.53
2.51
7.92
4.46
2.63
7.59
4.33
2.82
Heating
AFR
19.8
INDOOR
EDB
10
10
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
15.0
5.72
2.18
6.68
2.29
7.64
2.39
8.79
2.52
9.56
2.61
20.0
5.43
2.24
6.39
2.35
7.35
2.45
8.50
2.58
9.27
2.66
22.0
5.31
2.26
6.27
2.37
7.23
2.48
8.38
2.60
9.06
2.69
24.0
5.19
2.29
6.15
2.39
7.11
2.50
8.27
2.63
8.51
2.71
25.0
5.14
2.30
6.10
2.40
7.05
2.51
8.21
2.64
8.24
2.72
27.0
5.02
2.32
5.98
2.43
6.94
2.53
7.69
2.66
7.69
2.75
Symbols
NOTE:
AFR
(m/min.)
BF
: Bypass factor
EWB
(C)
EDB
(C)
TC
: Total capacity
(kW)
SHC
(kW)
PI
: Power input
(kW)
3D056486
31
Capacity Tables
8.3
ED04-703
0.9
0.8
Range of the Refrigerant Additional Charge
5
10
15
20
25
30
32
ED04-703
Operation Limit
9. Operation Limit
9.1
Cooling Only
RKD50/60/71BVM, RKD50/60/71BVMA
50
46
40
20
10
Pull-down period
Continuous operation
30
0
-5
-10
10
14
20 23
Indoor temp. (CWB)
Notes:
The graph is based
on the following conditions.
Equivalent piping length
7.5m
Level difference
0m
Air flow rate
High
9.2
28 30
4D027639F
Heat Pump
RXD50/60/71BVMA
Heating
Cooling
20
50
18
46
15
40
10
-5
Continuous operation
Outdoor temp.(CWB)
10
Pull-down period
20
Continuous operation
Outdoor temp.(CDB)
30
0
-5
-10
-10
-15
(-15CDB)
20 23
10
14
Indoor temp.(CWB)
28 30
Notes:
The graphs are based
on the following conditions.
Equivalent piping length 7.5m
Level difference
0m
Air flow rate
High
10
20
Indoor temp.(CDB)
30
3D027640H
33
Sound Level
ED04-703
Outdoor Unit
1m
0.8m
1m
(R1759)
Note:
34
(R1003)
Heating
Indoor ; 20CDB
Outdoor ; 7CDB/6CWB
Piping Length
5m
ED04-703
Sound Level
FTKD60FVM
70
OVER ALL ( dB )
50Hz/60Hz
50Hz/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(H)
(L)
44
35
A
NC-60
60
NC-50
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
NC-30
50Hz/60Hz 220-240/220-230V(H)
30
50Hz/60Hz 220-240/220-230V(L)
Cooling
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
70
50/60Hz
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(H)
(L)
NC-60
60
NC-50
45
36
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Cooling
NC-20
20
4D040651B
8000
OVER ALL ( dB )
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
4D040304E
8000
FTKD71FVM
70
OVER ALL ( dB )
50/60Hz
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(H)
(L)
NC-60
60
NC-50
46
37
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Cooling
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
4D040305G
8000
FTXD50FVM
COOLING
70
OVER ALL ( dB )
50/60Hz
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(H)
(L)
NC-60
60
44
NC-50
35
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Cooling
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
70
HEATING
OVER ALL ( dB )
50/60Hz
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(H)
(L)
NC-60
60
42
NC-50
33
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Heating
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
8000
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
3D054979A
8000
FTXD60FVM
COOLING
70
OVER ALL ( dB )
50/60Hz
SCALE 220-240/220-230V
(H)
NC-60
60
45
NC-50
50/60Hz
220-240/220-230V
(L)
36
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Cooling
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
8000
70
HEATING
OVER ALL ( dB )
50/60Hz
SCALE 220-240/220-230V
(H)
NC-60
60
35
44
NC-50
50/60Hz
220-240/220-230V
(L)
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
NC-30
50/60Hz 220-240/220-230V(H)
30
50/60Hz 220-240/220-230V(L)
Heating
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
8000
3D040300E
35
Sound Level
ED04-703
FTXD71FVM
COOLING
70
OVER ALL ( dB )
50/60Hz
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(L)
(H)
NC-60
60
NC-50
46
37
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Cooling
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
70
HEATING
OVER ALL ( dB )
50/60Hz
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
(L)
(H)
NC-60
60
NC-50
46
37
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V(H)
NC-30
30
50/60Hz 220-240/220-230V(L)
Heating
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
8000
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
3D040301D
8000
RKD60BVM, RKD60BVMA
NC-60
SCALE
60
NC-50
50/60Hz
220-240/220-230V
47
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
Cooling
30
NC-20
20
70
OVER ALL ( dB )
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
70
60
NC-50
SCALE
50/60Hz
220-240/220-230V
49
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
Cooling
30
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
4D027648D
8000
OVER ALL ( dB )
NC-60
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
4D040949E
8000
RKD71BVM, RKD71BVMA
70
OVER ALL ( dB )
NC-60
60
NC-50
SCALE
50/60Hz
220-240/220-230v
52
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
Cooling
30
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
4D027650E
8000
RXD50BVMA
COOLING
NC-60
60
NC-50
47
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
Cooling
30
NC-20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
36
SCALE
50/60Hz
220-240/220-230V
50
20
70
OVER ALL ( dB )
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
8000
70
HEATING
OVER ALL ( dB )
NC-60
60
NC-50
SCALE
50/60Hz
220-240/220-230V
48
50
OPERATING CONDITIONS
NC-40
40
JIS STANDARD
50/60Hz 220-240/220-230V
Heating
NC-30
30
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
8000
3D027645P
ED04-703
Sound Level
RXD60BVMA
COOLING
NC-60
60
50/60Hz
220-240/220-230V
SCALE
A
NC-50
49
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
Cooling
30
NC-20
20
70
OVER ALL ( dB )
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
70
HEATING
OVER ALL ( dB )
NC-60
60
NC-50
SCALE
50/60Hz
220-240/220-230V
49
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
30
Heating
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
8000
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
3D035059G
8000
RXD71BVMA
COOLING
NC-60
60
NC-50
SCALE
50/60Hz
220-240/220-230V
52
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
50/60Hz 220-240/220-230V
NC-30
Cooling
30
NC-20
20
70
OVER ALL ( dB )
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
8000
70
HEATING
OVER ALL ( dB )
NC-60
60
NC-50
SCALE
50/60Hz
220-240/220-230V
52
50
OPERATING CONDITIONS
NC-40
POWER SOURCE
40
220-240/220-230V 50/60Hz
JIS STANDARD
50/60Hz 220-240/220-230V
Heating
NC-30
30
NC-20
20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)
8000
3D027647F
37
Electric Characteristics
ED04-703
Outdoor Unit
Power Supply
Hz-Volts
Voltage Range
COMP
MCA
MFA
RHz
50 - 220
50 - 230
FTKD50FVM
RKD50BVM
60 - 230
FTKD60FVM
RKD60BVM
20
74
60 - 230
FTKD71FVM
RKD71BVM
60 - 230
FTKD50FVM
FTXD50FVM
RKD50BVMA
RXD50BVMA
19.75
20
96
60 - 230
50 - 230
RKD60BVMA
RXD60BVMA
60 - 220
50 - 230
RKD71BVMA
RXD71BVMA
20
83
60 - 230
8.3
53
0.20
43
0.16
10.2
53
0.28
43
0.18
53
0.19
43
0.15
53
0.28
43
0.16
53
0.30
43
0.18
11.2
10.7
6.9
6.5
19.75
20
74
6.2
6.9
6.5
9.1
8.7
19.75
20
70
8.3
9.1
8.7
11.4
50 - 240
60 - 220
0.15
10.7
19.75
50 - 220
FTKD71FVM
FTXD71FVM
43
8.7
50 - 240
60 - 230
0.19
11.2
50 - 220
FTKD60FVM
FTXD60FVM
53
9.1
50 - 240
60 - 220
6.2
8.7
50 - 220
50 - 230
FLA
6.5
50 - 240
60 - 220
9.1
50 - 220
50 - 230
FLA
6.8
50 - 240
60 - 220
6.5
19.75
50 - 220
50 - 230
RLA
IFM
6.8
50 - 240
60 - 220
OFM
10.9
19.75
20
63
10.4
11.4
10.9
SYMBOLS:
NOTE:
MCA
MFA
RLA
OFM
IFM
FLA
RHz
38
ED04-703
Installation Manual
SAFETY PRECAUTIONS
Read these SAFETY PRECAUTIONS carefully to ensure correct installation.
This manual classifies the precautions into WARNINGS and CAUTIONS.
Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNINGS
Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTIONS
Failure to follow any of CAUTION may in some cases result in grave consequences.
Never attempt.
After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the
use and cleaning of the unit according to the Operation Manual.
WARNINGS
Installation should be left to the dealer or another professional. Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual. Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the supplied or specified installation parts. Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the units weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules
or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection.
Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.
After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on
the electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified refrigerant
(R22), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)
During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the shut-off valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.
During installation, attach the refrigerant piping securely before running the compressor.
When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.
Failure to install an earth leakage breaker may result in electric shocks, or fire.
CAUTIONS
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.
Establish drain piping according to the instructions of this manual. Inadequate piping may cause flooding.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.
39
Installation Manual
ED04-703
Accessories
A Mounting plate
Insulation tape
K Operation manual
L Installation manual
FVM: 2
Model
2
2
FV2Z: 1
1.
Indoor unit.
The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air intake and exhaust have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the remote controller range,
8) the unit is at least 1 metre away from any television or radio set (unit may cause interference with the picture or sound),
9) install at the recommended height (1.8m).
2.
Installation Tips
<When there is no work space because the unit is close to ceiling>
Removal method
Hook fingers on the panel protrusions on the left and right
of the main body, and open until the panel stops. Slide
the front panel sideways to disengage
the rotating shaft. Then pull
the front panel toward you
to remove it.
CAUTION
1) Push up.
Installation method
1) Install the front grille and firmly engage the upper hooks (3 locations).
2) Install 3 screws of the front grille.
3) Install the air filter and then mount the front panel.
Installation method
Removal method
mark area
(3 locations)
Upper hook
Push
down.
Upper hook
Upper hook
Address
Push the
rotating shaft
of the front
panel into the
groove.
JA
JA Address
EXIST
CUT
1
2
J4
J4 ADDRESS
EXIST
CUT
40
1
2
ED04-703
Installation Manual
A Mounting plate
A Mounting
plate
Clip
Bottom frame
Front grille
Mark (rear side)
Caulk
pipe hole
gap
with putty.
Front panel
Wrap the insulation pipe with
the finishing tape from bottom
to top.
50mm or more
from walls
(on both sides)
Intelligent-eye sensor
Air filters
M4 16L
Service lid
Opening service lid
Service lid is opening/closing type.
Opening method
1) Remove the service lid screws.
2) Pull out the service lid diagonally
down in the direction of the arrow.
3) Pull down.
D Wireless
remote controller
Intelligent-eye Sensor
CAUTION
1) Do not hit or violently push the intelligent-eye sensor. This can lead to damage and malfunction.
2) Do not place large objects near the sensor. Also keep heating units or humidifiers outside the
sensors detection area.
41
Installation Manual
ED04-703
100
55
125
90
290
Use tape
measure
as shown.
Position the
end of tape
measure at .
80
52
52
80
60
83
413.5
44.5
100
99.5
1050
Through-the-wall
Drain hose position hole 80mm
Removed pipe
port cover
A Mounting
plate
2.
42
Inside
Wall embedded pipe
(Field supply)
Outside
Caulking
80
ED04-703
Installation Manual
Right-back piping
Right-bottom
piping
A Mounting plate
3) Pass the drain hose and refrigerant pipes through the wall
hole, then set the indoor unit on the mounting plate hooks by
using the markings at the top of the indoor unit as a guide.
4) Open the front panel, then open the service lid. (Refer to
Installation Tips.)
5) Pass the inter-unit wiring from the outdoor unit through the
feed-through wall hole and then through the back of the indoor
unit. Pull them through the front side.
Bend the ends of tie wires upward for easier work in advance.
(If the inter-unit wiring ends are to be stripped first, bundle wire
ends with adhesive tape.)
6) Press the bottom frame of the indoor unit with both hands to
set it on the mounting plate hooks. Make sure that the wires do
not catch on the edge of the indoor unit.
A Mounting plate
When stripping the
ends of inter-unit wiring
in advance, bind
right ends of wires with
insulating tape.
Inter-unit wiring
Remove pipe
port cover
here for leftside piping.
Left-side
piping
Left-back
piping
ap
A Mounting plate
Drain hose
A
Mounting
plate
Refrigerant
pipes
Bottom frame
H M4 12L (2 point)
50mm
or more
Outer wall
Inner wall
Drain hose
Vinyl chloride
drain pipe
(VP-30)
43
Installation Manual
ED04-703
4.
, install as described in the installation manual supplied with the Multi outdoor unit.
Terminal block
Wiring.
1) Strip wire ends (15mm).
2) Match wire colours with terminal numbers on indoor and outdoor units
terminal blocks and firmly screw wires to the corresponding terminals.
3) Connect the earth wires to the corresponding terminals.
Attach the earth wire so that it is not connected to the fan
motor connector.
4) Pull wires to make sure that they are securely latched up,
then retain wires with wire retainer.
5) In case of connecting to an adapter system. Run the remote
controller cable and attach the S21.
(Refer to 5. When connecting to an HA system.)
6) Shape the wires so that the service lid fits securely, then close service lid.
Outdoor unit
1 23
Indoor
unit
LN
1
2
3
H05VV
WARNING
1) Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause
overtheating, electrical shock,or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc.,
from the terminal block.) Doing so may cause electric shock or fire.
5.
Drain piping.
1) Connect the drain hose, as described below.
The drain hose should
be inclined downward.
No trap is permitted.
Indoor unit
drain hose
18
6.
HA cord
44
ED04-703
Installation Manual
1.
, install as described in the installation manual supplied with the Multi outdoor unit.
Check
(Cut exactly at
right angles.)
Flares inner
surface must
be flaw-free.
Remove burrs
Flaring
Set exactly at the position shown below.
A
Die
A
RIGID
0.5 mm
IMPERIAL
1.0 mm
WARNING
1) Incomplete flaring may cause refrigerant gas leakage.
2.
Refrigerant piping.
1) Align the centres of both flares and
tighten the flare nuts 3 or 4 turns by
hand. Then tighten them fully with the
torque wrenches.
Use torque wrenches when tightening
the flare nuts to prevent damage to
the flare nuts and escaping gas.
Liquid side
1/2 inch
5/8 inch
1/4 inch
3/8 inch
49.5-60.3N m
61.8-75.4N m
14.2-17.2N m
32.7-39.9N m
(144-175kgf cm)
(333-407kgf cm)
Torque wrench
Spanner
Piping union
Flare nut
2) To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare.
2-1. Caution on piping handling.
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a
pipe bender for bending.
(Bending radius should be 30 to 40mm or larger.)
Rain
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Inter-unit wiring
Gas pipe
Gas pipe
insulation
Liquid side
Liquid pipe
Liquid pipe
insulation
Finishing tape
Gas side
Wall
Be sure to
place a cap.
Drain hose
50 class
60/71 class
50/60 class
71 class
50 class
60/71 class
50/60 class
71 class
O.D. 12.7mm
O.D. 15.9mm
O.D. 6.4mm
O.D. 9.5mm
I.D. 14-16mm
I.D. 16-20mm
I.D. 8-10mm
I.D. 12-15mm
Thickness 0.8mm
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
45
Installation Manual
ED04-703
In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
Use the remote controller for trial operation as described below.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C in cooling mode,
20C to 24C in heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
For Cooling only
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and
parts, such as louver movement, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original
operation mode when the circuit breaker is opened again.
2.
Test items.
Test items
Symptom
(diagnostic display on RC)
Water leakage
Water leakage
Electrical leakage
Inoperative
Check
3P192027-2
46
ED04-703
Installation Manual
Safety Precautions
Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTIONS
Failure to follow any of CAUTION may in some cases result in grave consequences.
Never attempt.
After completing installation, test the unit to check for installation errors. Give the user adequate instructions
concerning the use and cleaning of the unit according to the Operation Manual.
WARNINGS
Installation should be left to the dealer or another professional.
Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the units weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring
rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection.
Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.
After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the
electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified
refrigerant (R22), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)
Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire.
A high surge current from lightning or other sources may cause damage to the air conditioner.
Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks, or fire.
CAUTIONS
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
47
Installation Manual
ED04-703
Accessories
Accessories supplied with the outdoor unit:
(B) Drain plug (Heat pump-Models)
1
There is on the bottom packing case.
Caution
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
2) Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a baffle
plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the snow
will not affect the unit.
Precautions on Installation
20
Check the strength and level of the installation ground so that the unit will not cause any operating vibration or
noise after installed.
In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare four
sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20 mm from the foundation surface.
When installing the unit on the frame, fix water proof plate within 150 mm from the bottom of the unit to prevent
water from entering.
48
ED04-703
Installation Manual
50 class
60 class
30 m
20 m
Additional refrigerant
required for refrigerant
pipe exceeding 10 m
in length.
20g/m
O.D. 12.7 mm
Gas pipe
71 class
Liquid pipe
50g/m
O.D. 15.9 mm
O.D. 6.4 mm
O.D. 9.5 mm
Service lid
250 m
0
33
(Foot
m
le cen
tres)
ole
-h
olt
tb )
oo tres
F
( en
c
5 80 m
bolt-ho
m
m
m from
120mm
(From
units
side)
wall
Installation Guidelines
Where a wall or other obstacle is in the path of outdoor units intake or exhaust airflow, follow the installation
guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200 mm or less.
Wall facing one side
More than 100
1200
or less
More than 50
More than 50
Top view
Side view
More
than 350
Top view
Unit: mm
49
Installation Manual
ED04-703
2.
Drain Work
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place additional
foot bases of at least 30 mm in height under the outdoor units feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
3.
Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
(Cut exactly at
right angles.)
Remove burrs
Flaring
Set exactly at the position shown below.
A
Die
RIGID
0.5 mm
IMPERIAL
1.0 mm
Check
Flares inner
surface must
be flaw-free.
Warning
1) Incomplete flaring may cause refrigerant gas leakage.
4.
Refrigerant Piping
1) Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with
the torque wrenches.
Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas.
2) To prevent gas leakage, apply refrigeration machine oil on both inner and outer surfaces of the flare. (Use
refrigeration oil for R-22)
Torque wrench
Spanner
Piping union
Flare nut
Gas side
Liquid side
5/8 inch
1/4 inch
3/8 inch
1/2 inch
Liquid side
5/8 inch
1/4 inch
48.1~59.7N m
44.1~53.9N m
(490~610kgf cm) (450~550kgf cm)
50
3/8 inch
21.6~27.4N m
(220~280kgf cm)
10.8~14.7N m
(110~150kgf cm)
ED04-703
Installation Manual
When piping work is completed, it is necessary to purge the air and check for gas leakage.
Warning
1)
2)
3)
4)
Do not mix any substance other than the specified refrigerant (R-22) into the refrigeration cycle.
To prevent air pollution, a vacuum pump should be used for air purging wherever possible.
Refrigerant gas leaks during air purging, ventilate the room as soon as possible.
Use a vacuum pump for R-22 exclusively. Using the same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.
Compound
Pressure meter
pressure gauge
Gauge
manifold
High-pressure
valve Valve lids
Low-pressure
valve
Charging
hoses
Liquid
shut-off
valve
Gas
shut-off
Vacuum pump Service port valve
1) Connect projection side (on which worm pin is pressed) of charging hose (which comes from gauge manifold) to gas
shut-off valves service port.
2) Fully open gauge manifolds low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)
3) Do vacuum pumping and make sure that the compound pressure gauge reads 0.1MPa ( 76 cmHg)*1.
4) Close gauge manifolds low-pressure valve (Lo) and stop vacuum pump.
(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
5) Remove valve lids from liquid shut-off value and gas shut-off valve.
6) Turn the liquid shut-off valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor units flare and outdoor units flare and valve rods.
After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas shut-off valves service port, then fully open liquid and gas shut-off valves.
(Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve lids and service port cap for the liquid and gas shut-off valves with a torque wrench at the specified torques.
Up to 15 metres
Run time
*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe
joint may exists. Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).
51
Installation Manual
ED04-703
Wall
Be sure to
place a cap.
Rain
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045 kcal/mhC)
Refrigerant gas pipes surface temperature reaches 110C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation
dimensions as below.
Gas pipe
Gas side
50 class
Liquid side
60/71
class
O.D.
O.D.
12.7mm 15.9mm
Thickness Thickness
0.8mm
1.0mm
Liquid pipe
50/60
class
71 class 50 class
O.D.
6.4mm
O.D.
I.D.
I.D.
I.D.
I.D.
9.5mm 14-16mm 16-20mm 8-10mm 12-15mm
Thickness 0.8mm
60/71
class
Inter-unit wiring
50/60
class
71 class
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Close
Valve lid
Service port
SW1
S2
LED-A
ON
SW4
1A
A B C
52
ED04-703
Installation Manual
Wiring
Warning
Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overheating,
electrical shock, or fire.
Do not turn ON the safety breaker until all work is completed.
1) Strip the insulation from the wire (20 mm).
2) Connect the connection wires between the
indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead screwdriver
be used to tighten the screws.
Indoor
unit
1 23
LN
1
2
3
Safety
breaker
20A
Firmly fix the wires with
the terminal screws.
Earth leakage
circuit breaker
H05VV
Power
supply
50Hz 220-240V
60Hz 220-230V
Earth
Power supply
terminal block
Shape wires so
that the service
lid and shut-off
valve cover fit
securely.
Firmly secure
wire retainer so
wire terminations
will not receive
external stress.
Round crimp-style
terminal
Electric Wire
Caution
When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.
Good
Wrong
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
53
Installation Manual
ED04-703
In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C in cooling mode, 20C
to 24C in heating mode).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.
For Cooling only
1-3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and
parts, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original
operation mode when the circuit breaker is opened again.
2.
Test Items.
Test Items
Check
Symptom
Water leakage
Water leakage
Electrical leakage
Inoperative
3P098803-6J
54
ED04-703
Operation Manual
Safety precautions
Keep this manual where the operator can easily find them.
Read this manual attentively before starting up the unit.
For safety reason the operator must read the following cautions carefully.
This manual classifies precautions into WARNING and CAUTION. Be sure to follow all precautions below: they are all
important for ensuring safety.
WARNING
CAUTION
If you do not follow these instructions exactly, the unit may If you do not follow these instructions exactly, the unit may
cause property damage, personal injury or loss of life.
cause minor or moderate property damage or personal injury.
Never do.
WARNING
In order to avoid fire, explosion or injury, do not operate the unit when harmful, among which flammable or
corrosive gases, are detected near the unit.
It is not good for health to expose your body to the air flow for a long time.
Do not put a finger, a rod or other objects into the air outlet or inlet. As the fan is rotating at a high speed, it will
cause injury.
Do not attempt to repair, relocate, modify or reinstall the air conditioner by yourself. Incorrect work will cause electric
shocks, fire etc.
For repairs and reinstallation, consult your Daikin dealer for advice and information.
The refrigerant used in the air conditioner is safe. Although leaks should not occur, if for
some reason any refrigerant happens to leak into the room, make sure it does not come in
contact with any flame as of gas heaters, kerosene heaters or gas range.
If the air conditioner is not cooling (heating) properly, the refrigerant may be leaking, so call your dealer.
When carrying out repairs accompanying adding refrigerant, check the content of the repairs with our service staff.
Do not attempt to install the air conditioner by your self. Incorrect work will result in water leakage, electric shocks or
fire. For installation, consult the dealer or a qualified technician.
In order to avoid electric shock, fire or injury, if you detect any abnormally such as smell of fire, stop the operation and
turn off the breaker. And call your dealer for instructions.
CAUTION
The air conditioner must be earthed. Incomplete earthing may result in electric shocks. Do not connect the
earth line to a gas pipe, water pipe, lightning rod, or a telephone earth line.
In order to avoid any quality deterioration, do not use the unit for cooling precision instruments, food, plants,
animals or works of art.
Never expose little children, plants or animals directly to the air flow.
Do not place appliances which produce open fire in places exposed to the air flow from the unit or under the
indoor unit. It may cause incomplete combustion or deformation of the unit due to the heat.
Do not block air inlets nor outlets. Impaired air flow may result in insufficient performance or trouble.
55
Operation Manual
ED04-703
Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid injury.
Do not place anything under the indoor or outdoor unit that must be kept away from moisture. In certain conditions,
moisture in the air may condense and drip.
After a long use, check the unit stand and fittings for damage.
Do not touch the air inlet and alminium fins of outdoor unit. It may cause injury.
The appliance is not intended for use by young children or infirm persons without supervision.
Young children should be supervised to ensure that they do not play with the appliance.
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the
air conditioner.
Before cleaning, be sure to stop the operation, turn the breaker off or pull out the supply cord.
Do not connect the air conditioner to a power supply different from the one as specified. It may cause
trouble or fire.
Depending on the environment, an earth leakage breaker must be installed. Lack of an earth leakage breaker may
result in electric shocks.
Arrange the drain hose to ensure smooth drainage. Incomplete draining may cause wetting of the building, furniture
etc.
Do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around
the unit.
Leaves are a hotbed for small animals which can enter the unit. Once in the unit, such animals can cause
malfunctions, smoke or fire when making contact with electrical parts.
Do not operate the air conditioner with wet hands.
Do not wash the indoor unit with excessive water, only use a slightly wet cloth.
Do not place things such as vessels containing water or anything else on top of the unit. Water may
penetrate into the unit and degrade electrical insulations, resulting in an electric shock.
Installation site.
To install the air conditioner in the following types of environments, consult the dealer.
Places with an oily ambient or where steam or soot occurs.
Salty environment such as coastal areas.
Places where sulfide gas occurs such as hot springs.
Places where snow may block the outdoor unit.
The drain from the outdoor unit must be discharged to a place of good drainage.
Electrical work.
For power supply, be sure to use a separate power circuit dedicated to the air conditioner.
System relocation.
Relocating the air conditioner requires specialized knowledge and skills. Please consult the dealer if
relocation is necessary for moving or remodeling.
56
ED04-703
Operation Manual
Names of parts
Indoor Unit
3
2
5
6
10
11
7
8
12
16
13
15
14
57
Operation Manual
ED04-703
Outdoor Unit
17
19
20
21
18
Indoor Unit
1. Air filter
2. Titanium Apatite Photocatalytic
Air-Purifying Filter
3. Air inlet
4. Front panel
5. Panel tab
Temperature
setting
FTKD COOL
22C
25C
FTXD AUTO
Mode
Air flow
rate
AUTO
AUTO
Outdoor Unit
17. Air inlet: (Back and side)
58
ED04-703
Operation Manual
Remote Controller
1
5
3
6
9
11
7
8
13
ON
CANCEL
12
10
16
OFF
TIMER
18
17
15
14
59
Operation Manual
ED04-703
Position
and
correctly!
3
1
ATTENTION
About batteries
When replacing the batteries, use batteries of the same type, and replace the two old batteries
together.
When the system is not used for a long time, take the batteries out.
We recommend replacing once a year, although if the remote controller display begins to fade or if
reception deteriorates, please replace with new alkali batteries. Using manganese batteries reduces
the lifespan.
The attached batteries are provided for the initial use of the system.
The usable period of the batteries may be short depending on the manufactured date of the air
conditioner.
60
ED04-703
Operation Manual
Receiver
Remote controller
holder
Set.
ATTENTION
About remote controller
Never expose the remote controller to direct sunlight.
Dust on the signal transmitter or receiver will reduce the sensitivity. Wipe off dust with soft cloth.
Signal communication may be disabled if an electronic-starter-type fluorescent lamp (such as
inverter-type lamps) is in the room. Consult the shop if that is the case.
If the remote controller signals happen to operate another appliance, move that appliance to
somewhere else, or consult the shop.
61
Operation Manual
ED04-703
ON
CANCEL
1, 3
OFF
TIMER
NOTE
Tips for saving energy
Be careful not to cool (heat) the room too much.
Keeping the temperature setting at a moderate level helps save energy.
Cover windows with a blind or a curtain.
Blocking sunlight and air from outdoors increases the cooling (heating) effect.
Clogged air filters cause inefficient operation and waste energy. Clean them
once in about every two weeks.
Please note
The air conditioner always consumes 15-35 watts of electricity even while it is not operating.
If you are not going to use the air conditioner for a long period, for example in spring or autumn, turn the breaker OFF.
Use the air conditioner in the following conditions.
Mode
Operating conditions
COOL
HEAT
DRY
Operation outside this humidity or temperature range may cause a safety device to disable the system .
62
ED04-703
Operation Manual
To start operation
1. Press MODE selector button
and select a operation mode.
Each pressing of the button advances the
mode setting in sequence.
: AUTO
2, 3
1
: DRY
: COOL
: HEAT
: FAN
5
ON
CANCEL
<FTKD>
OFF
TIMER
<FTXD>
To stop operation
3. Press ON/OFF button again.
Then OPERATION lamp goes off.
10
63
Operation Manual
ED04-703
to
are available.
NOTE
Note on HEAT operation
Since this air conditioner heats the room by taking heat from outdoor air to indoors, the heating
capacity becomes smaller in lower outdoor temperatures. If the heating effect is insufficient, it is
recommended to use another heating appliance in combination with the air conditioner.
The heat pump system heats the room by circulating hot air around all parts of the room. After the
start of heating operation, it takes some time before the room gets warmer.
In heating operation, frost may occur on the outdoor unit and lower the heating capacity. In that case,
the system switches into defrosting operation to take away the frost.
During defrosting operation, hot air does not flow out of indoor unit.
Note on COOL operation
This air conditioner cools the room by blowing the hot air in the room outside, so if the
outside temperature is high, performance drops.
Note on DRY operation
The computer chip works to rid the room of humidity while maintaining the temperature as
much as possible. It automatically controls temperature and fan strength, so manual
adjustment of these functions is unavailable.
Note on AUTO operation
In AUTO operation, the system selects a temperature setting and an appropriate operation mode
(COOL or HEAT) based on the room temperature at the start of the operation.
The system automatically reselects setting at a regular interval to bring the room temperature to
user-setting level.
If you do not like AUTO operation, you can manually select the operation mode and setting
you like.
Note on air flow rate setting
At smaller air flow rates, the cooling (heating) effect is also smaller.
11
64
ED04-703
Operation Manual
1, 2
3, 4
CANCEL
OFF
TIMER
4. When the louvers have reached the desired position, press the
SWING button
once more.
The louvers will stop moving.
disappears from the LCD.
12
65
Operation Manual
ED04-703
To 3-D Airflow
1. 3. Press the SWING button
and the SWING button
:
the and
display will light up and the flap and louvers will
move in turn.
STOP
COOL
approx. 10~40
DRY
approx. 5~35
STOP
HEAT
approx. 15~55
FAN
approx. 5~55
13
66
ED04-703
Operation Manual
POWERFUL Operation
POWERFUL operation quickly maximizes the cooling
(heating) effect in any operation mode. You can get the
maximum capacity.
To start POWERFUL
operation
1. Press POWERFUL button.
POWERFUL operation ends in 20 minutes.
Then the system automatically operates
again with the settings which were used
before POWERFUL operation.
When using Powerful operation, there are
some functions which are not available.
is displayed on the LCD.
To cancel POWERFUL
operation
2. Press POWERFUL button
again.
1, 2
ON
CANCEL
OFF
TIMER
NOTE
Notes on POWERFUL operation
POWERFUL Operation cannot be used together with QUIET Operation. Priority is given to
the function of whichever button is pressed last.
POWERFUL Operation can only be set when the unit is running. Pressing the operation stop button
causes the settings to be canceled, and the disappears from the LCD.
In COOL and HEAT mode
To maximize the cooling (heating) effect, the capacity of outdoor unit must be increased
and the air flow rate be fixed to the maximum setting.
The temperature and air flow settings are not variable.
In DRY mode
The temperature setting is lowered by 2.5C and the air flow rate is slightly increased.
In FAN mode
The air flow rate is fixed to the maximum setting.
14
67
Operation Manual
ED04-703
1, 2
ON
CANCEL
OFF
TIMER
NOTE
Note on OUTDOOR UNIT QUIET operation
This function is available in COOL, HEAT, and AUTO modes.
(This is not available in FAN and DRY mode.)
POWERFUL operation and OUTDOOR UNIT QUIET operation cannot be used at the
same time.
Priority is given to the function of whichever button is pressed last.
If operation is stopped using the remote controller or the main unit ON/OFF switch when
using OUTDOOR UNIT QUIET operation,
will remain on the remote controller
display.
15
68
ED04-703
Operation Manual
1, 2
CANCEL
OFF
TIMER
Selectable range
temperature
Cooling
25C
18-32C
5 step,
and
Heating
25C
10-30C
5 step,
and
16
69
Operation Manual
ED04-703
Before bed...
NOTE
Once the temperature and air flow rate for HOME LEAVE operation are set, those settings will be
used whenever HOME LEAVE operation is used in the future. To change these settings, please refer
to the Before using HOME LEAVE operation section above.
HOME LEAVE operation is only available in COOL and HEAT mode. Cannot be used in AUTO, DRY,
and FAN mode.
HOME LEAVE operation runs in accordance with the previous operation mode (COOL or HEAT)
before using HOME LEAVE operation.
HOME LEAVE operation and POWERFUL operation cannot be used at the same time.
Last button that was pressed has priority.
The operation mode cannot be changed while HOME LEAVE operation is being used.
When operation is shut off during HOME LEAVE operation, using the remote controller or the indoor
unit ON/OFF switch, will remain on the remote controller display.
17
70
ED04-703
Operation Manual
To start INTELLIGENT
EYE operation
1. Press SENSOR button.
To cancel the
INTELLIGENT EYE
operation
2. Press SENSOR button again.
[EX.]
1, 2
ON
CANCEL
OFF
TIMER
Normal operation
saving
operation.
18
71
Operation Manual
ED04-703
90
7m
55 55
7m
Sensor may not detect moving objects further than 7m away. (Check the application range)
Sensor detection sensitivity changes according to indoor unit location, the speed of
passersby, temperature range, etc.
The sensor also mistakenly detects pets, sunlight, fluttering curtains and light reflected off of
mirrors as passersby.
INTELLIGENT EYE operation will not go on during powerful operation.
Night set mode (page 20.) will not go on during you use INTELLIGENT EYE operation.
CAUTION
Do not place large objects near the sensor.
Also keep heating units or humidifiers outside the sensors detection area. This sensor can
detect objects it shouldnt as well as not detect objects it should.
Do not hit or violently push the INTELLIGENT EYE sensor. This can lead to damage and
malfunction.
19
72
ED04-703
Operation Manual
TIMER Operation
Timer functions are useful for automatically switching the
air conditioner on or off at night or in the morning. You can
also use OFF TIMER and ON TIMER in combination.
ON
CANCEL
2
4
OFF
TIMER
1, 3
NOTE
When TIMER is set, the present time is not displayed.
Once you set ON, OFF TIMER, the time setting is kept in the memory. (The memory is canceled when
remote controller batteries are replaced.)
When operating the unit via the ON/OFF Timer, the actual length of operation may vary from the time
entered by the user. (Maximum approx. 10 minutes)
NIGHT SET MODE
When the OFF TIMER is set, the air conditioner automatically adjusts the temperature setting (0.5C
up in COOL, 2.0C down in HEAT) to prevent excessive cooling (heating) for your pleasant sleep.
20
73
Operation Manual
ED04-703
1, 3
ON
CANCEL
4
OFF
TIMER
Display
(Example)
Present time: 11:00 p.m.
(The unit operating)
OFF TIMER at 0:00 a.m.
ON TIMER at 7:00 a.m.
Combined
ATTENTION
In the following cases, set the timer again.
After a breaker has turned OFF.
After a power failure.
After replacing batteries in the remote controller.
21
74
ED04-703
Operation Manual
Units
Indoor unit, Outdoor unit and Remote controller
1. Wipe them with dry soft cloth.
Front panel
1. Open the front panel.
Hold the panel by the tabs on the two
sides and lift it until it stops with a
click.
CAUTION
Dont touch the metal parts of the indoor unit. If you touch those parts, this may cause an injury.
When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
When removing or attaching the front panel, support the panel securely with hand to prevent it from falling.
For cleaning, do not use hot water above 40C, benzine, gasoline, thinner, nor other volatile oils,
polishing compound, scrubbing brushes, nor other hand stuff.
After cleaning, make sure that the front panel is securely fixed.
24
75
Operation Manual
ED04-703
Filters
1. Open the front panel.
(page 24.)
2. Pull out the air filters.
Push a little upwards the tab at the
center of each air filter, then pull it
down.
tabs (3 at bottom)
Air Filter
1. Wash the air filters with water or clean them with
vacuum cleaner.
If the dust does not come off easily, wash them with neutral
detergent thinned with lukewarm water, then dry them up in the
shade.
It is recommended to clean the air filters every two weeks.
[ Maintenance ]
1.
2.
3.
4.
Remove dust with a vacuum cleaner and wash lightly with water.
If it is very dirty, soak it for 10 to 15 minutes in water mixed with a neutral cleaning agent.
After washing, shake off remaining water and dry in the shade.
Since the material is made out of polyester, do not wring out the filter when removing water
from it.
[ Replacement ]
1. Remove the tabs on the filter frame and replace with a new filter.
Dispose of the old filter as non-flammable waste.
25
76
ED04-703
Operation Manual
NOTE
Operation with dirty filters:
(1) cannot deodorize the air.
(2) cannot clean the air.
(3) results in poor heating or cooling.
(4) may cause odour.
To order Titanium Apatite Photocatalytic Air-Purifying Filter contact to the service shop
there you bought the air conditioner.
Dispose of old filters as non-flammable waste.
Item
Titanium Apatite Photocatalytic Air-Purifying Filter
(without frame) 1 set
Part No.
KAF952B42
Check
Check that the base, stand and other fittings of the outdoor unit are not decayed or corroded.
Check that nothing blocks the air inlets and the outlets of the indoor unit and the outdoor unit.
Check that the drain comes smoothly out of the drain hose during COOL or DRY operation.
If no drain water is seen, water may be leaking from the indoor unit. Stop operation and consult the
service shop if this is the case.
2. After operation stops, turn off the breaker for the room air conditioner.
3. Clean the air filters and set them again.
4. Take out batteries from the remote controller.
26
77
Operation Manual
ED04-703
Trouble Shooting
These cases are not troubles.
The following cases are not air conditioner troubles but have some reasons. You may just continue using it.
Case
Explanation
In HEAT mode
The frost on the outdoor unit melts into water or steam
when the air conditioner is in defrost operation.
In COOL or DRY mode
Moisture in the air condenses into water on the cool
surface of outdoor unit piping and drips.
This happens when the air in the room is cooled into mist by
the cold air flow during cooling operation.
This is because the air in the room is cooled by the heat
exchanger and becomes mist during defrost operation.
27
78
ED04-703
Operation Manual
Check again.
Please check again before calling a repair person.
Case
The air conditioner does not
operate.
(OPERATION lamp is off.)
Check
An abnormal functioning
happens during operation.
28
79
Operation Manual
ED04-703
WARNING
When an abnormality (such as a burning smell) occurs, stop operation and turn the breaker OFF.
Continued operation in an abnormal condition may result in troubles, electric shocks or fire.
Consult the service shop where you bought the air conditioner.
Do not attempt to repair or modify the air conditioner by yourself.
Incorrect work may result in electric shocks or fire.
Consult the service shop where you bought the air conditioner.
If one of the following symptoms takes place, call the service shop immediately.
Lightning
If lightning may strike the neighboring area,
stop operation and turn the breaker OFF for
system protection.
29
3P192025-2
80
ED04-703
Optional Accessories
Note:
Indoor Units
DCS302CA61
DCS301BA61
DST301BA61
KRP928B2S
KAF952B42
KKF917A4
KRC72
KRP413A1S
Outdoor Units
Drain Plug
KKP937A4
KPW945A4
81
Optional Accessories
ED04-703
CAUTION
WARNING
Installation should be left to the dealer from whom you purchased the unit, or
another qualified professionals.
Install the unit securely according to the installation manual. Faulty installation
may lead to electric shock or fire.
Be sure to use the supplied or specified parts. Using other parts may lead to
electric shock or fire.
Install the unit securely in a location that will support its weight. If installed in a
poor location or improperly installed, the unit may not work as intended.
For electrical work, follow local electric standards and the installation manual.
Faulty installation may lead to fire or electric shock.
Do not bundle the power cord, or attempt to extend it by splicing it with another
cord or by using an extension cord. Do not place any other load on the power
circuit used for the unit. Improper wiring may lead to electric shock, heat
generation or fire.
Use dedicated wiring for all electrical connections, and be sure to arrange the
wiring so that force applied to the wiring will not damage the terminals. Poor
wiring or installation may cause electric shock, heat generation or fire.
2. Field Wiring
For interconnecting wiring, use Daikin KDC100A12 cable (not supplied) or
other similar cable. The cable should have the specifications shown below.
Optional cable KDC100A12 (without connectors)
Specifications:
0.2 mm2 4 core (sheathed)
Outer diameter: 5.3
Length:
100 m
Colour:
Grey
Other cable (commercially available)
Outer dia.
Remarks
7.2 mm
Hard sheath
8.0 mm
6.5 mm
4.8 mm
Item
Shielded
Not sheathed
Note 1: Keep any wiring for the control unit away from the power cord to prevent
electrical noise.
Note 2: Do not use cables shown above for power cord, inter-unit cord/cable or
power cord for lamps.
CAUTION
Before installation, unplug the air conditioner to ensure safety. Failure to do so
may cause electric shock.
Static electricity may damage electric components. Before connecting cables
and communication lines, and operating the switches, be sure to discharge any
electrical charge from your body (by, for example, touching the earth line)
Do not install the unit in a location where it may be exposed to flammable
gases. If gas leaks and build up around the unit, it may catch fire.
Do not place the wiring close to the power cord, inter-unit cable, or pipes which
generate noise. Treat the wiring with care.
82
ED04-703
Optional Accessories
Installation
This product is available in two types. The KRP413A1S KRP413AA1S is for installation in a case independent of the indoor unit, and
the KRP413A1 is for installation within the indoor unit.
1. KRP413A1S KRP413AA1S
1
Installation diagram
1
Adaptor case
Adaptor case
S21
Indoor unit
wiring
Local wiring or
power cord, etc.
Install the adaptor case assy as close to the indoor unit as possible.
Removing case front
Case front
Components
Screw
Adaptor PCB
Screw cover
Accessories
Binding band (4 pcs.)
Securing tape for attaching to the indoor unit (2 sets)
Screws for attaching the adaptor case (4 pcs.)
Screws for attaching to the wall (3 pcs.)
Installation manual
Wiring
2. KRP413A1
For this type, install the adaptor PCB within the indoor unit. The method of
installation and connection vary depending on the model of the air
conditioner. See your air conditioner installation manual for details.
Screw
Screw cover
Components
Adaptor PCB
Installation manual
Securing tape
Hook side (loop side)
Securing tape
Loop side (hook side)
Indoor unit
To prevent the adaptor case assy from falling, do not use the securing
tape for attaching it to a wall or other surface.
83
Optional Accessories
ED04-703
Wiring
1. Wiring
Connect one end of the wiring to connector S21 of the PCB in the
indoor unit.
Connect the other end of the wiring to connector S6 of the adaptor
PCB.
Connect field wiring according to the functions assigned to each
connection terminal of the adaptor PCB.
Secure all wires.
ON
OFF
Fasten with a tie-wrap so that wires will not come loose even if pulled.
If the wire protrudes from
this side, cut the cut-off
section of the case front.
<Instantaneous Contact>
1
On/Off
2
1
Off
Inter unit
cable (field wiring)
Tie-wrap
(to prevent the wires from coming loose)
1
2
1
On
This PCB stores the following data in the event of a power failure
(common features).
On/Off (see Note 1)
Operation modes
Temperature setting
Air flow rate
On/Off status of remote controller
Operation
S
1
S
2
Five-room central
controller
(Note 1 When SW1-2 is in Off mode, the unit will not be activated.)
OFF
1
Terminal
blocks A to E
1 S
2 4
3
2
1 S
2 1
R
D
LED
Item Manufacturer
S
4
Max 100 m
S
2
<Normal Contact>
The method for securing wire varies depending on the model of the air
conditioner. See your air conditioner installation manual for details.
S
1
LED
Toshiba
Rohm
Type
TLG208 (green)
TLR208 (red)
1S2473
510 ohm 1/4W
S
8
DC12V
S
5
L1
2
3
L2
OFF
: Operation light
: Malfunction light
S
1
H M L OFF
(+)
MR1
()
L1
MR1
MR2
()
MR2
External power
supply for light
L2
1
2
Max 100 m
Manufacturer
84
1 S
3
Omron
MY relay
12 V DC
HC relay
12 V DC
Coil resistance
Matsushita
S
2
Off
(When cooling)
Cooling/heating switch
ED04-703
Optional Accessories
START
No
Yes
Is 12 V DC being supplied
to No. 4 and No. 5 on S6 of the
remote controllers PCB?
No
Yes
Is 12 V DC being supplied
to No. 4 and No. 5 on S21
of the indoor unit?
No
Yes
No
Yes
OR
1
2
1
2
1
2
1
2
S
4
S
1
S
2
S
3
S
8
S
5
OFF
ON
OFF
Always Off
SW1-2
ON
Off if operation was in Off mode before power failure; On if operation was in
On mode before power failure
1
2
1
2
3
Instantaneous contact
SW1-1: OFF
(Operation mode 1)
SW1
1
2
OFF ON
S6
Normal contact
S1 (1) - S2 (1)
OPEN
CLOSE
S1 (1) - S1 (2)
Pulse input
On/Off switching
S1
S2 (2), S3
S2
S1, S2 OPEN
S3
CLOSE, Heating
SW1-1: ON
(Operation mode 2)
Operation mode 1 (Used with the exception of fan coil remote controller settings)
SW1-1
S4
S5
(1) - (2)
Not activated
OPEN, Cooling
(1) - (2)
(1) - (3)
S6 connector
S8
Not used
(+) - ()
2P031616-1B
85
Optional Accessories
ED04-703
14.2.2 KRP928B2S
1.Overview, Features and Compatible Models
Safety Precautions
This kit is the interface required when connecting the central controller and a Daikin Room Air
Conditioner. Use of the central controller makes it possible to perform the following monitoring
and operations. It is compatible with room air conditioners which have an HA connector S21.
1.Run / stop for the central controller and wired remote controller, operating mode
selection, and temperature can be set.
2.The operating status, any errors, and the content of those errors can be monitored
from the central controller and wired remote controller.
3.Run / stop for the central controller and wireless remote controller, operating mode
selection, and the temperature setting can be limited by the central controller.
4.Zone control can be performed from the central controller.
5.The unit can remember the operating status of the air conditioner before a power
outage and then start operating in the same status when the power comes back
on.
6.Card keys, operating control panels, and other constant / instantaneous
connection-compatible equipment can be connected.
7.The Operating / error signals can be read.
8.HA JEM-A-compatible equipment can be connected.
9.The indoor temperature can be monitored from the Ve-up controller.
Be sure to follow all the precautions below ; they are all important for
ensuring safety.
WARNING
Installation should be left to the dealer or another qualified professional.
Improper installation by yourself may cause malfunction, electrical shock, or fire.
Precaution
1.When reading the Operating / error signals, a separate external power source
(DC 12V) is needed.
2.A separate timer power source (DC 16V) is needed when using the schedule
timer independently, and not in conjunction with other central controllers.
3.The range of temperatures that can be set from the central controller is 18C to
32C in cooling and 14C to 28C in heating.
4.Fan operation cannot be selected from the central controller or wired remote controller.
5.Group control (i.e., control of multiple indoor units with a single remote controller) is
not available.
6.Monitoring is not available of the thermo status, compressor operating status,
indoor fan operating status, electric heater, or humidifier operating status.
7.Forced thermo off, filter sign display and reset, fan direction and speed settings,
air conditioning fee management, energy savings instructions, low-noise
instructions, and demand instructions cannot be made.
CAUTION
An earth leakage circuit breaker should be installed.
If the breaker is not installed, electrical shock may occur.
This kit includes the following components. Check to ensure that none of
these are missing.
Qty
Parts
Kit assy
PCB is in the housing.
Lay this cable separately from other power cables to avoid external
electrical noises.
After installation is complete, test the operation of the PCB set to check
for problems, and explain how to use the set to the end-user.
Screw cover
Parts
Qty
1set
Mounting screws
3pcs.
Binding band
1pc.
Installation manual
1set
DAIKIN
OFF
SW1
SW2
LED1
SW3
S6
Tes1
S1
S16
F1
S8
86
S5
Forced stop
Settings switch (SW3-1)
Power supply terminal (S8)
Connect an external DC 12V power
supply only when reading the
Operating / error display.
S19
F2
Non polarity
Included in the Drain
Up Kit.
OFF
1234
1 2 3 4 ON
ON
1 1234
To HA connector (S21)
Remote controller
BRC944 Series
Card key
(Field supply)
Operating control panel
(Field supply)
Operating monitoring
equipment
(Field supply)
Connecting a Wired
Remote Controller
ED04-703
Optional Accessories
5.Control Codes
Turn the power on after all the switches have been set.
Settings made while the power is on are invalid.
When using a central remote controller, the operating codes can be used to limit
operation from wireless remote controllers.
: permitted; : prohibited
ON
However, these settings do not need to be made when using the schedule timer
independently.
(The settings are needed when used in conjunction with another DCS Series
central controller.)
In this case, the schedule timer performs an auto address after the power is turned
on, so new group numbers are automatically set. Settings made using the switches
will be overwritten.
SW2 Upper
setting group NO.
1 1 2 3
Lower
SW1
setting group NO.
1 1 2 3 4
1
0
Lower
SW1
setting group NO.
1 2 3 4
0 0
0 8
0
1 2 3
1 2 3 4
2
1 2 3
1 2 3 4
1 2 3
1 2 3 4
1 2 3 4
1 2 3
1 2 3 4
1 2 3 4
1 2 3 4
1 2
1 2 3 4
0 5
1 2 3 4
7
1 2 3
1 1
0 4
6
1 2 3
1 0
1 2 3 4
0 3
5
1 2 3
0 9
0 2
1 3
0 6
1 5
Fan direction
and fan speed
Operating mode
temperaturet
Fan direction
and fan speed
permitted
Only OFF
Constant control is permitted prohibited
contact mode accepted
prohibited permitted
Instantaneous
contact mode
Constant
contact mode
prohibited
permitted
permitted
prohibited
prohibited permitted
Last command
prohibited
priority
permitted
permitted
prohibited
prohibited permitted
prohibited
Does not affect settings
Stop
Operations from
central controller,
contact input and
HA JEM-A input
S5
M1
M2
What Happens
(+)
()
()
MR1
MR1
MR2
CB
D-BIPS
S1
Schedule timer
KRP928B2S
7.Combining Equipment
CA
Abnormality display
MR2
Schedule timer
Power source
for display
Operating Display
Control mode
ON
S8
S1
SW3-1 SW3-2
operating mode setting setting
OFF
What Happens
Instantaneous contact
input (factory setting)
ON
S1 pin
operating mode
Forced stop
NOTE also that a separate timer power source is needed when using the
schedule timer independently.
Power source specs: DC 16V, +10%, -15%, 200mA.
Recommended power source: Omron S82J-01015A. (Should be used with the
output voltage adjusted to the center, DC 16V.)
The remote controller permission / prohibition settings using the Ve-up controller are as
follows.
: permitted; : prohibited
1 4
1 2 3 4
0 7
Constant
contact mode
Forced stop
1 2 3 4
1 2 3 4
Timer operation
is accepted by
remote controller
1 2 3 4
0 1
Operations from
central controller,
contact input and
HA JEM-A input
HA JEM-A-compatible equipment
Overseas
0,1,3
10,11
2
1219
4
5
6,7
Stop
OFF
(Factory setting)
Run / timer
Japan
ON / OFF control
is rejected
Only OFF control
is accepted
What Happens
Stop
SW3-3 setting
Control mode
Control
code
ON / OFF controller
Destination
S1
operating
mode
Open the Kits case and set the switches on the circuit board.
(1) For Overseas / Japanese unit setting (SW3-3)
Room air conditioners, different methods are used for setting the temperature in
automatic mode, so this switch needs to be set.
Run / timer
NOTE
4.Switch Settings
3P157704-2A
87
Optional Accessories
ED04-703
14.2.3 KPW945A4
Before installation
Check the following parts
Name
Louver
Installation manual
1piece
M4x4screws(max.7.5kW class)
M5x4screws(8.0/9.0kW class)
1piece
Shape
Quantity
Installation Procedure
Selection of Installation Location
Use when installing in a location that meets the following conditions.
O When installing near the border to a neighbor's house
O If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
O If exhaust blows directly on vegetation
100
han
t
ore
Installation of Louvers
Caution
Attach the louvers overlapping the standard grill.
Installing the louvers without the grill would allow hands to enter the fan area,
which is dangerous, so be sure to install the standard grill.
When pointing up
O
O
3P089958-2C
88
Specifications, designs and other content appearing in this brochure are current as of January 2007 but subject to change without notice.
ED 04-703
Printed in Japan 01/2007 B AK