Sie sind auf Seite 1von 5

COMISIN FEDERAL

DE ELECTRICIDAD
Zalathiel Villamil
Peralta Adn Maya
Snchez

ZONA DE TRANSMISIN METROPOLITANA


TRANSFORMADOR T28A S.E.CERRO GORDO No. DE SERIE 5066908

TABLA RESUMEN

[PRUEBAS ELCTRICAS
A TRANSFORMADORES]
24/05/2012

DATOS DE PLACA

Company

ZONA DE TRANSMISION
METROPOLITANA

Serial Number

5066908

Location

S.E.CERRO GORDO

Special ID

T28A

Division

ZTM

Circuit Designation

T28A

Manufacturer

Configuration

FASE A

Year Mfg.

Tank Type

SEALED-CONSER

Mfr. Location

MEXICO

Coolant

OIL

Phases

Class

FOA

Oil Volume

190 IG

BIL

900 kV

Weight

157600 LB

Winding Config.

Single

kV

220, 85

VA Rating

33.33, , , MVA

Note
Test Date

24/05/2012

Test Time

10:12:35 AM

Weather

SUNNY

Air Temperature

26 C

Tank Temp.

25.7 C

RH.

4%

DATOS DE PLACA DE BOQUILLAS

Type

C1
%PF

C1 Cap

0.40

410

0.39

0.40

Dsg

Serial

Mfr

H0

11B7157

X1

X2
H1

C2
%PF

C2 Cap

kV

Amps

Year

15
115

1953

414

115

1953

857

230

1954

FACTOR DE POTENCIA
Meas.

Test kV

mA

Watts

%PF corr

Corr Fctr

Cap(pF)

CH + CHL

10.000

33.690

1.338

0.39

0.97

8936.4

CH

10.000

17.935

0.8110

0.44

0.97

4757.4

CHL(UST)

10.000

15.721

0.5250

0.32

0.97

4170.0

15.755

0.527

0.32

0.97

4179.000

CHL

IRauto

CL + CHL

10.000

33.308

1.303

0.38

0.97

8835.2

CL

10.000

17.556

0.7870

0.44

0.97

4656.9

CHL(UST)

10.000

15.718

0.5270

0.33

0.97

4169.2

CHL

15.752

0.516

0.32

0.97

4178.300

CH'

17.935

0.811

0.44

0.97

4757.400

CL'

17.556

0.787

0.44

0.97

4656.900

IRman

BOQUILLAS C1
ID

Serial

NP %PF

NP Cap

Test kV

mA

Watts

%PF corr

Corr Fctr

Cap(pF)

IRauto

H1

0.40

857

10.000

1.885

0.1180

0.66

1.04

499.96

X2

0.39

414

10.000

1.519

0.0880

0.60

1.04

402.97

X1

0.40

410

10.000

1.511

0.0770

0.53

1.04

400.79

IRman

BOQUILLAS C2
ID

Serial

Test kV

mA

Watts

%PF corr

Corr Fctr

Cap(pF)

IRauto

H1

0.4990

28.843

2.053

0.71

1.00

7650.5

X2

0.4990

12.335

0.8970

0.73

1.00

3272.0

X1

0.4990

11.785

0.7630

0.65

1.00

3126.2

NP %PF

NP Cap

IRman

NO CUENTA CON DATO DE PLACA PARA COMPARATIVA DE C2, LOS VALORES SE ENCUENTRAN EN EL
RANGO PERMISIBLE.

COLLAR CALIENTE A BOQUILLAS


Term ID

ID

Test Mode

Skirt #

Test kV

mA

Watts

IRauto

H1

GROUND

FAL1

10.000

0.1560

0.0350

H1

GROUND

FAL2

10.000

0.1640

0.0290

H1

GROUND

FAL3

10.000

0.1670

0.0320

H1

GROUND

FAL4

10.000

0.1700

0.0300

IRman

FACTOR DE POTENCIA AL ACEITE AISLANTE


Sample Location

Deg C

Test kV

mA

Watts

%PF corr.

Corr Fact

IRauto

valvula inf. muestreo

26

10.000

0.8880

0.0060

0.05

0.77

IRman

PRUEBA A BOQUILLA EN GND


Specimen and Connection

Test kV

mA

Watts

%PF corr.

Corr Fctr

Cap(pF)

BOQUILLA H0

10.000

26.213

1.266

0.48

1.00

6953.0

IRman

CORRIENTE DE EXCITACIN
Mfr. Type Steps

Boost %

Buck %

Position Found

Position Left

Oil Volume

De-Energized Tap Changer


On-Load Tap Changer
H1 - H0

LTC

Test kV

mA

Watts

10.001

45.282

292.65

10.001

45.960

297.62

9.992

46.732

303.33

10.002

47.519

309.23

10.001

48.339

315.37

9.995

49.051

320.90

10.000

49.921

327.58

10.000

50.772

334.26

9.989

51.274

341.30

mA

Watts

DETC

mA

Watts

IRauto

IRman

H1 - H0

mA

DETC

LTC

Test kV

mA

Watts

Watts

mA

Watts

IRauto

10

9.993

52.094

347.59

11

9.994

53.066

355.09

12

10.001

54.051

362.71

13

10.001

55.046

370.61

14

10.001

55.990

378.09

15

10.001

57.034

386.54

16

10.010

58.059

395.10

17

10.001

59.206

404.57

IRman

RELACIN DE TRANSFORMACIN (H-L) Tests


True Cap.

HV Winding

LV Winding

10115.9

L-N

L-L

H1 - H0

X1 - X2

Connections
Detc

Np Volt

Ltc

Np Volt

Cal

Ratio1

Min Lim

Max Lim

IRauto

146073

85000

1.719

1.7183

Ratio2

Ratio3

1.710

1.727

144486

85000

1.700

1.7012

1.691

1.708

142898

85000

1.681

1.6820

1.673

1.690

141310

85000

1.662

1.6627

1.654

1.671

139722

85000

1.644

1.6434

1.636

1.652

138135

85000

1.625

1.6263

1.617

1.633

136547

85000

1.606

1.6071

1.598

1.614

134959

85000

1.588

1.5879

1.580

1.596

133371

85000

1.569

1.5686

1.561

1.577

10

131784

85000

1.550

1.5514

1.543

1.558

11

130196

85000

1.532

1.5329

1.524

1.539

12

128608

85000

1.513

1.5136

1.505

1.521

13

127020

85000

1.494

1.4934

1.487

1.502

14

125433

85000

1.476

1.4774

1.468

1.483

15

123845

85000

1.457

1.4582

1.450

1.464

16

122257

85000

1.438

1.4391

1.431

1.446

17

120669

85000

1.420

1.4198

1.413

1.427

IRman

REACTANCIA DE DISPERSIN (Single Phase) [H-L]


Test Results
DETC LTC
1

Phase

Voltage Current

Watts

H1H0X1X2 277.0 V 2.806 A 21.729 W

PF meas

Ind.

Res.(Ohms)

Imp.(Ohms)

Reac.(Ohms)

2.795

0.261 H

2.759

98.555

98.516

% Impedance

% Reactance

DETC

LTC

Phase

%Imped.

Benchmark

Delta Bench.

%Reac.

Benchmark

Delta Bench.

H1H0X1X2

18.45

17.330

6.465

18.443

17.330

6.423

EL VALOR OBTENIDO SER TOMADO COMO REFERENCIA, YA QUE LA PLACA DE DATOS DEL
TRANSFORMADOR, LA IMPEDANCIA EST REFERIDA A 50 HZ.

Das könnte Ihnen auch gefallen