INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Rd
Northford, CT 06472-1653
(203) 484-7161

FMM-1 Monitor Module


Specifications
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC wiring resistance:
Temperature Range:
Humidity:
Dimensions:
Accessories:

15 to 32 VDC
5.1 mA (LED on)
400A (LED flashing)
47K Ohms
1,500 Ohms
32F to 120F (0C to 49C)
10% to 93% Noncondensing
412 H x 4 W x 114 D (Mounts to a 4 square by 218 deep box.)
SMB500 Electrical Box

Before Installing
This information is included as a quick reference installation guide. Refer to the control panel installation manual
for detailed system information. If the modules will be
installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel
before installing the modules.

3. Secure module to electrical box (supplied by installer), as


shown in Figure 2A.
Figure 1. Removing
Rotary Switch Stop:

NOTICE: This manual should be left with the owner/user


of this equipment.

8
7
6

General Description
The FMM-1 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of
each module is selected using the built-in rotary switches.
It provides either a 2-wire or 4-wire fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm
and supervisory devices, or either normally open or normally closed security devices. The module has a panel controlled LED indicator. The FMM-1 can be used to replace an
MMX-1 module in existing systems.

5
LOOP

67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
8
7
6
9
5
4
3
2
10

ONES

0
1
2
3
4

ADDRESS

A78-2318-07

Figure 2A. Module mounting:


Note: For UL Listed security installations, the FMM-1 must
be mounted within the control panel enclosure.

Compatibility Requirements
To ensure proper operation, this module shall be connected
to a compatible Notifier system control panel (list available
from Notifier).
Mounting
The FMM-1 mounts directly to 4 square electrical boxes
(see Figure 2A). The box must have a minimum depth of
218. Surface mounted electrical boxes (SMB500) are available from Notifier.
Wiring
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Note: Some panels support extended addressing. In
order to set the module above address 99 on compatible
systems, carefully remove the stop on the upper rotary
switch with thumb in the direction shown in Figure 1.
N500-48-00

www.PDF-Zoo.com

Figure 2B:

4 5 67
8
3
9
2
10
TE
NS 1
11
0
4 5 6 7 15 1 1 12
3
8 4 3
2
9
1
0

4 5 67
8
3
9
2
10
TE
NS 1
11
0
4 5 6 7 15 1 1 12
3
8 4 3
2
9
1
0

NES

4
D
AD

SS
RE

S
ES

DR

AD

ES

ON

A78-2611-12

A78-2610-10

I56-1171-05

Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:


TO NEXT
DEVICE

)(

)(

)+(

)+(

FROM PANEL OR
PREVIOUS DEVICE

MONITOR
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.

MODULE

CONNECT MODULES TO LISTED COMPATIBLE


NOTIFIER CONTROL PANELS ONLY
9
8
7

47 K EOL
RESISTOR
ELR-47K

6
5

ONES

LOOP

67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
6789
5
4
3
2
10

)(

)+(

2
3

COMMUNICATION LINE

32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED

ADDRESS

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B


POWER LIMITED: 230A MAX @ 12 VDC MAX

COMMUNICATION LOSS (OPTIONAL CONNECTION FOR


PANELS WHICH SUPPORT THIS FEATURE)

INSTALL CONTACT CLOSURE DEVICES PER


MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

A78-2280-13

Figure 4. Typical 4-wire fault tolerant initiating circuit configuration, NFPA Style D:
TO NEXT
DEVICE

)(

)-(

)+(

)+(

ANY NUMBER OF UL LISTED CONTACT CLOSURE


DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.

FROM PANEL OR
PREVIOUS DEVICE

MONITOR
MODULE
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
9
8
7
6
5

EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9.

67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
6789
5
4

3
2

)(
)+(

2
3

COMMUNICATION LINE
32 VDC MAX
SHIELDED-TWISTED PAIR
IS RECOMMENDED

10

ONES

LOOP

0
1

ADDRESS

COMMUNICATION LOSS (OPTIONAL CONNECTION


FOR PANELS WHICH SUPPORT THIS FEATURE)

INSTALL CONTACT CLOSURE DEVICES PER


MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

A78-2281-58

Figure 5. Typical 2-wire initiating circuit configuration for security systems (with alarm versus short capability):
Note: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
TO NEXT
DEVICE
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.

)(

)(

)+(

)+(

MONITOR
MODULE

CONNECT MODULES TO LISTED COMPATIBLE


NOTIFIER CONTROL PANELS ONLY

14K SERIES RESISTOR

9
8
7

47 K EOL
RESISTOR
ELR-47K

6
5
LOOP

67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
6789
5
4
3
2
10

ONES

)(

)+(

2
3

COMMUNICATION LINE

32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED

ADDRESS

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B


POWER LIMITED: 230A MAX @ 12 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.

N500-48-00

www.PDF-Zoo.com

FROM PANEL OR
PREVIOUS DEVICE

COMMUNICATION LOSS (OPTIONAL CONNECTION FOR


PANELS WHICH SUPPORT THIS FEATURE)
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

A78-2281-59

I56-1171-05
2002 Notifier