Beruflich Dokumente
Kultur Dokumente
CITATIONS
READS
46
746
3 AUTHORS, INCLUDING:
Indrika Rajapaksha
University of Moratuwa
19 PUBLICATIONS 95 CITATIONS
SEE PROFILE
Abstract
The paper investigates the potential of a courtyard for passive cooling in a single storey
high mass building in a warm humid climate. The inclusion of an internal courtyard in building
design is attributed to the optimization of natural ventilation in order to minimize indoor
overheating conditions. However, the efficiency of this strategy greatly depends on the design
details of the building composition in providing appropriate airflow pattern to the courtyard.
From the results of thermal measurements, a significant correlation between wall surface temperatures and indoor air temperatures is evident. A reduction of indoor air temperature below
the levels of ambient is seen as a function of heat exchange between the indoor air and high
thermal mass of the building fabric. However, this behavior is affected by indoor airflow
patterns, which are controlled through the composition between envelope openings and the
courtyard of the building.
From a computational analysis, several airflow patterns are identified. A relatively better
indoor thermal modification is seen when the courtyard acts as an air funnel discharging indoor
air into the sky, than the courtyard acts as a suction zone inducing air from its sky opening.
The earlier pattern is promoted when the courtyard is ventilated through openings found in
the building envelope. The computational simulation utilizing the standard k- turbulent model
with isothermal condition agrees closely with the measurements taken from the field investigation.
2003 Elsevier Science Ltd. All rights reserved.
Corresponding author. Fax: +81-617-3219-6629.
E-mail addresses: indrikaFr@hotmail.com (I.
Rajapaksha).
Rajapaksha);
upendraindi@hotmail.com
0960-1481/03/$ - see front matter 2003 Elsevier Science Ltd. All rights reserved.
doi:10.1016/S0960-1481(03)00012-0
(I.
1756
Keywords: Airflow pattern; Opening composition; Passive cooling; Tropical courtyard; Warm humid
climate
1. Introduction
The concerns over global warming and the need for reduction of high emissions
of greenhouse gases demand the utilization of passive strategies for indoor climate
modification in promoting comfortable indoor environments. In such systems, the
energy required for indoor climate modification is obtained from natural renewable
sources but limitations for its applicability arrive through the prevailing climate [1].
In warm humid tropics, overheated building interiors are common due to solar
penetration through the buildings envelope and windows. Under these conditions,
and with the presence of high levels of relative humidity, the utilization of natural
ventilation is recommended as a suitable cooling option for the prevention of
overheating and indoor climate modification. Thus, design strategies to optimize
natural ventilation and maximize its effect with the thermal mass in reducing the
maximum of indoor temperature in buildings is of great importance.
In high-mass buildings with windows open and in the shade all day, the indoor
daytime temperature is consistently below that of outdoors [2]. Given the properties
of thermal mass of the building fabric with effectively shaded windows, the airflow
pattern to and within the building has an impact on indoor air temperature reduction.
Effectiveness of this process is dependent on the optimum exposure of the building
to the air movement that can enhance a greater surfaceair contact [3]. Thus, dealing
Nomenclature
Uin(z)
A
Uh
Ut
z
n
h
a
r
Cm
L
y
k
1757
with wind driven ventilation behavior and its effects on indoor air temperature
becomes important in such climates. This study aims to illustrate a passive cooling
approach that has been used to exploit the optimum use of wind-driven natural ventilation in preventing indoor overheating conditions and lowering maximum indoor
temperature below the ambient level. The illustration is focused on a particular building type that has an internal courtyard by investigating the performance and effectiveness of design strategies used in a single-storey high mass courtyard house found in
a suburb of Colombo, Sri Lanka.
The study investigates the effects of the airflow pattern to the courtyard on the
exposure of the building interior to the air movement in enhancing optimum surface
air contact and thus indoor climate modification. The goal is to provide some guidelines for manipulating courtyard-building compositions to improve indoor air movement and lower the maximum indoor air temperatures in warm humid climates.
The monitoring of thermal behavior within the case study building utilized five
different boundary configurations (shown in Table 1). The monitoring was conducted
on site from the 12 April to 3 May 2001. Boundary configurations of the building
were changed through closing and opening the major airflow access points found
within the building envelope. Each boundary configuration (opening composition)
showed different levels of indoor air temperature modifications and indoor airflow
rates. This paper discusses the results of the thermal performance of the building. It
was investigated using two identified different boundary configurations that resulted
in minimum and maximum indoor air temperature modifications and corresponding
airflow rates out of five boundary configurations as mentioned above. Later, the
airflow patterns and airflow rates were simulated using computational analysis (CFD)
Table 1
Different boundary configurations and corresponding values
Opening composition
Courtyard (case 1)
Op1,2 and Cy (case 2)
Op3,4 and Cy (case 3)
Op1,2,3 and Cy (case 4)
Op1,2,3,4 and Cy (case 5)
Interior zone
Day
Night
day
0.34
1.04
0.68
0.96
0.74
1.38
0.92
1.18
0.91
1.6
0.42
1.4
0.52
1.5
0.62
i=1
(1)
1758
and simulated airflow rates were compared with the calculated values obtained from
field investigations.
2. Ambient climate
The building investigated in this study is built within a suburb located 20 km from
Colombo, Sri Lanka (then Ceylon), at 6.5 N latitude and about 15 m above sea level.
The ambient climate is characterized by high temperatures and relatively high levels
of humidity. The mean monthly temperatures range from 27.2 C in November to
30.3 C in April; relative humidity varies from 7080% during a typical year.
While seasonal variations through temperature do not exist, there are two recognizable seasons due to wind and rainfall. The northeast monsoon occurs from June to
August and southwest monsoon occurs from December to February. The remaining
inter-monsoon represents the dry season while heavy rainfall is observed in monsoon
periods. Clear and fine weather with tropical thunderstorms brings slight daytime
wind and rain in the late afternoons. Also, the daily pattern of the dry season has
diurnal temperature ranges of 78 C.
3. Comfort temperature and required design strategies
3.1. Ambient climatic conditions in relation to Givonis bioclimatic chart for
Colombo
Fig. 1 shows Givonis bio-climatic chart for Colombo. The chart represents the
typical mean daily maximum and mean daily minimum values of relative humidity
Fig. 1.
1759
and temperature for different months of the year, 2001. To extend the comfort zone
for higher humidity and higher temperatures, higher air velocities are required. This
is quiet extensive given the relative humidity around 7080%.
3.2. Neutrality temperatures in relation to dry bulb temperatures for a typical
year (2001)
The work of Humphreys [4] and its continuation by Auliciems [5] give the neutrality temperature as a function of monthly mean outdoor temperature. The neutrality
temperatures for Colombo are within 27.328.5 C for the year 2001. Fig. 2 gives
the neutrality temperature and comfort zone, which is defined as 2 C above and
below the neutrality temperature in relation to dry bulb temperature and still air conditions.
From the collective evidence of 11 different studies by others, Szokolay [6] confirms (taking into consideration of humidity, temperature, radiation balance, activity
level and clothing levels) that an air velocity of 1 m/s is capable of extending the
upper limits of comfort dry bulb temperatures by 3.7 C under warm humid conditions. This is applicable to situations where occupants wear light clothing (less
than 0.5 clo) for activity levels less than 1 met. The mean daytime wind velocities
in Colombo (still conditions during night) are around 0.9 m/s and thus the available
indoor air velocities are even below this value. At the highest level of applicability,
an air velocity of 0.9 m/s can extend the comfort zone up to 32.0 C.
3.3. Typical daily weather pattern in April (a month of the hottest period)
A closer look at the ambient climatic conditions during February to May in Colombo reveals that daytime dry bulb temperatures remain above the extended upper
limits of dry bulb temperature for most part of the daytime hours (refer Fig. 3).
Therefore, a strategy to reduce daytime maximum indoor air temperature, in addition
to the provision of indoor airflow, is required.
Fig. 2. Seasonal pattern of neutrality temperature and comfort zone in relation to dry bulb temperature
of Colombo, Sri Lanka, 2001.
1760
Fig. 3. Daily pattern of dry bulb temperature and relative humidity of Colombo, Sri Lanka (during the
very hot month of April).
4. Field investigation
4.1. The investigated building
The case study building presented in this study employs a number of passive
design strategies to modify the warm ambient climate in order to minimize thermal
discomfort from overheating conditions. The inclusion of a courtyard, high mass
building fabric, high timber ceilings and wide roof eaves are of significant importance.
The 230m2 rectangular building form that is designed for a single family accommodates a central rectangular courtyard measuring 3.7 and 8.1 m as the main design
strategy. The use of an internal central courtyard is a dominating feature in traditional
buildings found in Sri Lanka. The courtyard occupies approximately one tenth of
the buildings footprint, is bounded by a living area to the west and bedrooms to
the east. It can be visually opened to the outdoor environment through two axes
passages, which are perpendicular to each other.
By locating the rectangular courtyard at the center, the plan depth of the surrounding indoor spaces is minimized for better cross ventilation potential. With four major
openings (Op1, Op2, Op3 and Op4 shown in Fig. 4A and Fig. 5) placed in the
envelope, the courtyard maintains direct contacts with the external environment. This
enhances cross ventilation to the building and thus the exposure of high mass brick
walls to the incoming air movement. Opening 1, which is located at the north end
of the longitudinal axis, acts as the main entrance to the house.
The louvered door measuring 4.3 m2 at this opening can promote slight ventilation
even if the door is closed during the night. The other opening on the south end of
the longitudinal axis is a large vertical grill measuring 3.6 m2 (opening 2), which
promotes permanent ventilation during the day. In addition, openings 3 and 4 (each
measuring 3.6 m2) are located on the east and west ends of the cross axis. One third
of the courtyard floor is covered with water. Though there are other openings on the
building envelope (doors and windows), they remained closed during the study period. The courtyard dominates within the building section and is the tallest space
1761
Fig. 4. The enclosed courtyard house and measurement points in the field investigation.
Fig. 5.
within it (Fig. 4B). Having introduced openings at relatively lower levels within the
envelope, the potential for airflow due to stack effect during the night is encouraged.
The high-mass brick building has high internal walls with low external walls (22cm thickness including cement and lime plaster) to the east and west. Through this
design, east and west orientations are provided with shaded verandahs. Wide roof
eaves on all four sides protect all the windows and doors (openings) from solar
radiation throughout the day. The floor of the building is finished with clay terracotta
tiles while the roof is covered with half round clay tiles (Thermal Conductivity:
8.6 105 Wcm1 C1, Absorptivity: 0.650.74, [7]) with a timber ceiling underneath. Insulation is not found throughout the building.
1762
1763
stated as 0.3 C from 545 C and 3% over 1090% relative humidity. Further,
sensors were shielded against direct and reflected solar radiation from surrounding
surfaces using Campbell Scientific Gill 41004, multi plate (12 plates) radiation shields.
Kanomax model 6511 Hot-wire anemometers were used for indoor air velocity
measurements. These were sensitive to air velocities down to 0.05 m/s. Campbell
Scientific 03001 cup anemometer and wind vane (Youngs wind sentry wind set)
coupled with CR 21X data logger was used for outdoor wind speed and direction
measurements. The outdoor cup anemometers were initially calibrated in the wind
tunnel using hot-wire anemometer probes. High correlation (r = 0.99) was observed.
Eto denki EF 5020A Thermodac data logger with type-T thermocouples (with an
accuracy of 0.2 C over 050 C range) was used for wall surface temperatures.
All equipments were recommended with research-grade accuracy.
4.6. Measurement locations
Measurements were recorded in the courtyard and selected indoor spaces. Air
temperature, relative humidity and wind velocities were measured at 1.1 m(Tcy1),
2.5 m(Tcy2) and 3.5 m(Tcy3) heights at the center of the courtyard (refer Fig. 4B).
Indoor spaces were measured for air temperature and humidity at human body level:
1.1 m from the floor level (Fig. 4A).
Wall temperatures were measured at the center of the main exterior surfaces of
the building (W6 W10) and the five interior wall surfaces that surround the courtyard (W3, W4), longitudinal axis (W1, W2) and the family living (W5) at 1.1 m from
the ground (refer Fig. 4A).
Wind velocity measurements were recorded at 0.6 m(V1), 1.2 m(V2) and 1.8 m(V3)
heights at each exterior opening of the longitudinal axis (Op.1 and 2, refer Fig. 4C).
The weather station installed on the site recorded climatic conditions at three levels: 1.1, 5.5 and 10 m ensuring freeness from wind shadows due to built or natural
structures (refer Fig. 14A).
4.7. Criteria for the assessment of data
The assessment of measurements is mainly concerned with the effectiveness of
the courtyard in lowering the air temperatures of its own and surrounding indoor
spaces below the level of daytime ambient temperature.
4.8. Ambient site climate
The ambient weather pattern was observed as similar throughout the study period
and even several days before the study. The maximum ambient temperature of 32.8
C was recorded between 13:0015:00 h, while the minimum temperature of 25.5
C was recorded in the morning at 4:007:00 h. Daytime humidity remained between
6070% with nighttime humidity at 99%.
Prevailing winds were from the southwest during the daytime and from the nor-
1764
theast and east at nighttime. Mean daytime wind speeds were of 1.2 and 1.5 m/s at
5 and 10 m heights, respectively, with almost still wind conditions (or 0.2 m/s)
at night.
Fig. 6. Ambient temperatures and courtyard air temperatures (Tcy1) at 1.1 m in case 1 and case 2.
Daytime maximum temperature in case 2 is lower by 2 C and seen 2 h later the maximum ambient
recorded.
1765
Fig. 7. Vertical temperature profile in the courtyard in case 1 and case 2. Thermal stratification is shown
in both case 1 and 2. Maximum temperature at the top level is higher than the maximum ambient in case
1. Relatively lower levels of air temperatures recorded in the courtyard in case 2.
1766
2) are lower than the courtyard preventing the potential for stack effect during the
daytime.
Vertical temperature profile indicates a heat gain from the courtyards top in case
1 and 2. However, relatively lower levels of air temperatures at bottom, middle and
the top levels in case 2 indicate that the effect of heat gain from the top opening is
moderated due to the potential of upwind forced ventilation in the case 2, as compared to case 1 (refer Section 8 for the airflow pattern).
5.3. Wall surface temperature
The hourly internal wall surface temperatures in the three main areas (area next
to opening 1, courtyard and family living on the west) were compared against each
other and the external wall surface temperatures (north-W7, south-W10, east-W8 and
W9, and west-W6 walls) at the human body level.
All internal walls in each area were monitored and later averaged for a mean
value. Fig. 8, shows that mean surface temperatures of the courtyard walls (W3 and
W4) and the axis walls (W1 and W2) remained above against each other depending
on the airflow pattern. The mean surface temperatures in the living area remained
constant with the airflow patterns.
External surface temperatures remained constant on both days while daytime
internal wall surface temperatures (W5) decreased by 1 to 3.4 C well below the
external values. Nevertheless, relatively higher surface temperatures (W3 and W4) in
the courtyard in case 1 indicate heat absorption and thus the availability of incoming
outdoor air from the courtyard. On the other hand, higher surface temperatures in
the axis walls in case 2 exhibit heat absorption, and thus the availability of incoming
air through the axis.
In case 1, the maximum value of 29.8 C in the courtyard was recorded at 14:00
h without showing a time lag with the mean maximum of the external walls. Contrary
to this behavior, in case 2, a time lag for the courtyard surface temperature was seen.
The maximum courtyard surface temperature of 28.8 C was below the value
Fig. 8.
level.
Wall surface temperatures of three main areas (courtyard, axis and adjoining living) at body
1767
Fig. 9. Air temperatures of courtyard, internal zone and outdoor with internal wall surface temperature
in family living zone.
1768
ment, replacing the operating temperature (To) of Fangers comfort equation with
standard effective temperature (SET) is used in the assessment of thermal comfort.
Activity levels are taken as 1.1 met (Fig. 16) (55 W/m2 for sedentary activity),
with tropical clothing of 0.4 clo. Mean radiant wall surfaces and indoor air velocity at
human body height of the family living area was considered as parameters of PMV.
Case 1 with a PMV vote of 2.2 was found as having the worst thermal conditions
with warm unpleasant indoor environment throughout the daytime. Contrary, the best
thermal conditions with comfortable (PMV vote of 0.2) indoor environment were
found in case 2. More details are published elsewhere [10]. However, the real problem occurs when the relative humidity moves to higher levels during the early
nighttime where indoor air temperatures remain around 2829 C. This necessitates
the need for a slight breeze during night for comfort.
5.5. Airflow due to stack effect at night
Typical ambient weather data for Colombo indicates almost still wind conditions
during the night. Within this context, areas between the courtyard and axis openings
(1 and 2) were monitored for air movement. These measurements indicate the availability of ventilation between 0.20.4 m/s in areas close to the openings during night
hours in case 2, where the building was allowed to ventilate through the envelope
opening in addition to the courtyard. Air movement during the night was not
observed in case 1.
Fig. 10 presents the average air temperatures in the courtyard and areas close to
openings 1 and 2 in the envelope. A variation of pressure distribution due to temperature difference of more than 1 C is visible during the nighttime in case 2. Relatively
lower temperatures at the openings can enhance a slight breeze due to stack effect
only in the night. This is evident with indoor air velocities recorded against almost
still ambient wind conditions in the nighttime in case 2 (Fig. 11). The benefit of
such airflow is important for thermal comfort in the early night hours along with
relatively higher levels of humidity. It was also found that such differences of temperatures needed to activate stack airflow are not visible when the building is ventilated from the courtyard only. The indoor areas show an overheated condition minim-
1769
Fig. 11. Air velocities at openings 1 and 2 compared with ambient and courtyard at body level in case
1 and case 2.
izing the temperature differences with the courtyard and thus minimizing the
potential for stack effect.
5.6. Airflow rates during daytime
Table 2 shows airflow rates calculated for the daytime using measured daytime
air velocities at the openings of each opening composition, together with corresponding air volumes. The volumetric airflow rate is proportionate to the area of openings.
The airflow rate that corresponds with case 2 (the best thermal modification) is
around 1.5 air changes per h. Similar thermal behavior was evident in case 4, in
which the rectangular courtyard is ventilated through three openings including Op1
and Op 2 of the longitudinal axis. Thus, the effective airflow range is from 1.5 to
2.0 air changes h1 [11].
Relatively higher airflow rates and higher air volumes are visible when the building is ventilated through all four openings during the daytime. However, the air
temperature modification is relatively low in this case when compared to the cases
discussed above.
Table 2
Different boundary configurations with corresponding daytime mean airflow rates and air volumes
Opening composition
Courtyard (case 1)
Op1, 2 and Cy (case 2)
Op3 and 4 (case 3)
Op1, 2 and 3 (case 4)
Op1, 2, 3 and 4 (case 5)
84
630
535
714
1050
0.2
1.5
1.2
1.7
2.5
1770
1771
Fig. 12.
1772
Table 3
Grid and cell dimensions
Grid characteristics
Surrounding grid
Total No. of cells
Bldg model cells
Cell dimensions
Coordinate axes
x
350
119
88
Min. 0.11
Max. 0.3
350
129
102
Min. 0.15
Max. 0.3
60
60
40
Min. 0.12
Max. 0.16
Table 4
Boundary conditions
Inlet boundary
Outlet boundary
Sky
Wall boundary (log law)
L = h / 2; h = 5.0m; Uh = 1.5m/ s
Free slip
Free slip
U / Ut = 1 / log(Uty /n) + A
K = U2t / Cm1 / 2; e = U2t / y
Ut = (t / r)1 / 2; = 0.4; A = 5.5
Fig. 13. Simulated building model. (a) Plan with wind direction and specified Inlet and outlet boundaries;
(b) Three-dimensional form.
1773
Fig. 14. (a) Vertical profile of wind speed at inlet boundary in relation to the building model with
surrounding boundary condition. (b) Wind velocity measurement points of the field investigation.
and west sides act as inlet boundaries. The corresponding wind profile was derived
from power-law formula. Log-law was used to model the wall boundary conditions.
6.3. Building model
Fig. 13 illustrates the plan and 3D form of the simulated building model. The
geometry of the building was realistically modeled, utilizing the dimensions of the
experimented building (refer Fig. 4A). The 3D model incorporates an open central
courtyard, internal layout with two axes perpendicular to each other, floor levels,
gable roofs and main axial openings. The dimensions of the building were, length:
18.6 m, width: 12.2 m and height: 4.8 m. Opening 1 was 4.3 m2 and other axial
openings (Op.2, 3,4) had an area of 3.6 m2 each, the courtyard opening was 18 m2.
The internal spaces were arranged at two ground levels differed by 0.9 m. Thus,
openings 2 and 4 are placed at 0.9 m above the ground level where openings 1 and
3 are found. For simulation purposes, walls, roofs and the ground of the building
were considered as impermeable.
6.3.1. Simulated cases
The building was simulated for indoor airflow behavior under five different boundary-opening compositions as shown in Table 1. This paper presents the airflow rates
of all cases and detailed airflow analysis of the two cases related to the thermal
investigation presented above.
6.4. Natural wind profile
Turbulence characteristics and vertical profile of wind speed are influenced by the
type of terrain and are a function of terrain roughness. The measurements taken with
respect to ambient wind during the field investigation (Fig. 14B) were used in deriv-
1774
ing the terrain roughness. Average velocity was recorded at 5 and 10 m heights from
the ground and was 1.5 and 1.8 m/s, respectively. The vertical profile of wind speed
was given by power law according to the following formula (refer Fig. 14A):
Uin (z) / Uh (Z / h)a
(2)
Thus, the investigated site represents a terrain roughness (a) of 0.25 with a turbulent intensity of 5%. In the presence of different boundary conditions from open flat
country to cities, the terrain roughness varies from 0.16 to 0.33, respectively. Terrain
roughness of 0.25 represents an urban characteristic [17]. Daytime wind direction
was observed from the southwest direction at an angle of 45 to the building facade
(Fig. 13A).
Fig. 16.
1775
Simulated airflow patterns (horizontal distribution) at human body height (1.1 m).
the openings 1 and 2 travels through the indoor spaces and finally discharges into
the sky through the courtyard (Fig. 17, case 2). It is also seen that a portion of air
travels into the adjoining living space before it discharges through the courtyard.
The results show that the courtyard does not admit any airflow from its sky opening
but acts as an upwind air funnel to discharge the indoor airflow into the sky.
When the 3D building model is allowed to ventilate from the courtyard while
other openings in the envelope remain closed, the courtyard acts as a suction zone
and admits airflow from the free flow above the building model (Fig. 17, case 1).
Detailed results indicate that air entering through the courtyard tries to get discharged
back into the sky through the same opening, creating a vortex within its top section.
A part of the air travels into the adjoining spaces but stagnates as openings in the
envelope are closed. However, intensity of this airflow within the indoor spaces is
lower than that of the previous case.
The above results clearly indicate two different airflow patterns within the
courtyard/building and the differences are correlated to the opening compositions.
A detailed presentation of airflow patterns can be found elsewhere [18].
Fig. 17. Vertical distribution of the simulated airflow patterns, case 1 with A top vortex; case 2 with
an Up wind air funnel.
1776
Fig. 18.
and 2.
Simulated and measured daytime vertical wind velocity profile within the courtyard for case 1
Fig. 19.
1777
vortex type airflow from the courtyards top opening. However, its effect on middle
and lower levels is relatively low.
8. Conclusion
The computational simulation utilizing the standard k- turbulent model with isothermal condition agrees closely with the measurements taken from the field investigation.
The results obtained from the thermal investigation and the computational (CFD)
analysis explores the potential of a courtyard for passive cooling in a single storey
high mass residential building located in a warm humid climate. The effect of the
courtyard for mass-air heat exchange and thus lowering the daytime indoor air temperatures below the corresponding levels of shade ambient temperature is correlated
with the indoor airflow pattern. This correlation indicates that the potential of the
courtyard to act as a passive cooling strategy is a function of the indoor airflow
pattern. Thus, relatively better indoor thermal modification is seen when the courtyard acts as an air funnel discharging indoor air into the sky, rather than the courtyard
acts as a suction zone inducing air from its sky opening, as suggested by conventional knowledge.
Although the airflow rates are proportionate to the opening areas, the levels of
indoor thermal modifications are not proportionate to airflow rates. The maximum
airflow rate does not give the optimum thermal modification. The optimum airflow
rate that corresponds with the best thermal modification of more than 1 C below
1778
the ambient level is found between 1.52.0 ACH. Given the ambient wind climate,
and when the measured effective ventilation rate is established, CFD simulations
could be used as an appropriate design tool in deriving the corresponding opening
composition.
The implication of this conclusion on architectural design gives useful guidelines
in designing naturally ventilated high mass residential buildings with internal courtyards in warm humid climates. Thus, the potential of courtyards to act as passive
cooling can be correlated with a building composition in terms of airflow rate and
pattern.
References
[1] Givoni B. Passive and low energy cooling of buildings. New York: Van Nostrand Reinhold, 1994.
[2] Givoni B. Effectiveness of mass and night ventilation in lowering the indoor daytime temperatures
Part I: 1993 experimental periods. Energy and Building 1993;1993(28):2532.
[3] Boutet T. Controlling air movement. USA: McGraw Hill, 1987.
[4] Humphreys MH. Outdoor temperatures and comfort indoors. Building Research and Practice
1978;6(2):92105.
[5] Auliciemes A. In: ANZAAS Conference. Global differences in indoor thermal requirements. 1997.
[6] Szokolay SU. Thermal comfort in warm humid tropics. ANZAScA 1997:711.
[7] Haccoun A, Barcohen A. Thermal properties of building materials: A compilation. Division of Desert
Engineering, Ben-Gurion University of the Negev, Research and Development Authority, 1974.
[8] Fanger PO, Melikov AK, Hanazawa H et al. Turbulence and draft: the turbulence of airflow has a
significant impact on the sensation of draft. ASHRAE Journal 1989;31(7):1823.
[9] Kindangen J. Window and roof configurations for comfort ventilation. Building Research and Information 1997;25(4):21825.
[10] Rajapaksha I, Nagai H, Okumiya M. Indoor airflow behavior for thermal comfort in a courtyard
house in warm humid tropics. In: Proceedings Indoor Air 2002, Monterey, USA. 2002. p. 10727.
[11] Rajapaksha I, Nagai H, Okumiya M. Indoor thermal modification of a ventilated courtyard house
in the tropics. International Journal of Architectural Institute of Japan, Journal of Asian Architecture
and Building Engineering 2002;1(1):8497.
[12] Launder BE, Spalding JL. Mathematical models of turbulence. New York: Academic Press, 1972.
[13] Heiselberg P, Murakami S, Roulet C. Ventilation of large enclosures in buildings, Energy conservation in buildings and community systems: Annex 26. Denmark: Kolding, 1998.
[14] Alfa flow users guide, Fujitsu Corporation, Japan, 1992
[15] Givoni B. Man climate and architecture. London: Applied Science Publishers, 1976.
[16] Aynsley RM. Tropical housing comfort by natural airflow. Building Research and Practice
1980;8(4):24252.
[17] Awbi HB. Ventilation of buildings. London: Spon, 1991.
[18] Rajapaksha I. Passive cooling design strategies for tropical courtyard buildings, Doctoral thesis,
Department of Architecture, Nagoya University, Japan.