Beruflich Dokumente
Kultur Dokumente
com
Introduction
Point to point method method of short circuit calculation is one of the basic method in finding
the short circuit current in any point in the system. Before an engineer use a computer software
to determine short circuit current it is recommended that he needs to understand the basic
principle and know how to do the manual calculation.
The example as shown in the figure above can describe the step by step procedure in calculating
the short circuit calculation. Before we begin the short circuit analysis let us first discuss the two
important formula, viz:
where:
Ixfr = Current rating of transformer (1p for single phase and 3p for three phase)
Ixfr-sc = short circuit current of transformer at the terminals
% Z = percent impedance of the transformer
2. f - factor (the impedance of the cable or busbar between two points where the fault is
calculated)
where:
f = f - factor
L = length of the conductor relative to the immediate upstream fault point.
Isc-x = fault current at any point in the circuit.
Email: circuitcity.phil@yahoo.com
www.electricalengineering.blogspot.com
C = conductor factor and the values are given in the table below.
n = number of parallel run of conductor.
VLL = Line to line voltage
3. M- factor (Multiplier to be used against the value of the fault current in the immediate
fault point)
M = 1/ (1 +f )
Email: circuitcity.phil@yahoo.com
www.electricalengineering.blogspot.com
Email: circuitcity.phil@yahoo.com
www.electricalengineering.blogspot.com
The short circuit that can be calculated at this point is coming from the transformer alone. The
fault current that we can get is a symmetrical 3 phase fault current. Imagine we will bolt the three
terminals of the secondary terminals altogether.
The 0.9 exist in the equation since the transformer has +/- 10% tolerance and we take the
negative value so that we can take the maximum fault current. Take note that the lesser
the impedance the higher the fault current.
If the tolerance is +/- 5% then the factor that will appear in our equation will be 0.95.
Fault at Point 2:
Point 2 has 400 ft. length conductor with 2 conductor per phase. We can apply formula number 3
and 4 at this point, thus:
Email: circuitcity.phil@yahoo.com
www.electricalengineering.blogspot.com
Therefore,
Isc-2 = 11 kA
Fault at Point 3:
Again we will use the same process and refer to the table given above for the value of conductor
factor C.
Isc-3 = 7.48 kA
Email: circuitcity.phil@yahoo.com
www.electricalengineering.blogspot.com
Fault Point 4:
In fault point 4 we can use the same process but we need to add the locked rotor current of the
motor during fault condition.
In this case the motor is rated 20 HP, operating at 480 Volts, thus:
Isc-4 = 8.1 kA
Email: circuitcity.phil@yahoo.com
www.electricalengineering.blogspot.com
Summary of Results:
After getting these values the next step to do is to find the appropriate KAIC rating of your
circuit breaker or fuse to withstand the mechanical and electrical stress as a result if ever a short
circuit happen.
And make sure we will perform the analysis for selective coordination in order to localized the
fault in case there is a short circuit.
References:
Schneider Electric
General Electric
Cooper Busman
Email: circuitcity.phil@yahoo.com