CERTAMEN N 1:
SISTEMAS ELECTRICOS DE
POTENCIA
R 1=
=
A
0.0176
mm
m
304.03 [ mm
=0.0000579
[ ]
[ ]
=0.057889
m
km
A= r 2 r =
A
304.03
=
=9.837 [ mm ] =0.009837 [ m ] =9.837106 [ km ]
R 2=R
[ ]
1T +t 2 0.057889241.5+60
=
=0.06674
T +t 1
241.5+20
km
Luego tenemos un circuitos doble con por fase por lo tanto la resistencia en
corriente continua ser:
1
1
2
Rcct=
0.06674=0.016686
120 [ km ] =2.0023 [ ]
2
km
[ ]
r= 0.40.009837=0.062728 m
D1=
9.20215.5011.6021.80
=14.83728m
12.80
D 2=
9.20215.507.0020.20
=10.75865 m
13.20
D3=
11.6021.807.0020.20
=6.871865 m
27.20
)]
[ ]
1
10.31325
X L= 250 0.25+2ln
104 j
2
0.062728
km
X L=0.1642229 j
X c=
[ ]
120 [ km ] =19.70675 j [ ]
km
145898 j [km]
1
=
=1215.817 j [ ]
9
120 [ km ]
225055.6610
j
10.31325
ln
0.062728
Y=
1
1
4
=
=8.224910 j [ ]
X c 1215.817 j [ ]
Z =2.0023+19.706 j [ ] =19.80723<80.204o
Modelando en lnea larga
Y
tanh l
Y
2
o
=
=0.0004132< 89.963
2
l
'
l= YZ=00064596+0.1274744 j
Z c=
Z
=154.98597.853736 j=155.1848<2.9o
Y
cosh l=
[(
)(
)]
1 0.0064596 0.127474180
0.127474180
e
<
e0.0064596 <
2
)]
1 0.0064596 0.127474180
0.127474180
e
<
+ e0.0064596 <
2
cosh l=0.9919<0.047
senh l=
[(
)(
Como la carga 3
S
Q
P1
cos1 ( 0.93 )=
=21.56
P3
21.50o=
QR
Q1 =19.76 j MVAr
50 MW
tan
S R 1=I RV R I R =
S R 50 MW +19.76 j MVAr
=
VR
345 KV
3
I R=269.9136<21.56o I R =269.9136<21.56o [ A ]
V R=
345 KV
=199.185 [ KV ]
3
[ ][
cosh l
VT
= sinh l
IT
ZC
ZC sinh l
cosh l
][ ]
VR
IR
[ ][
][
VT
0.9919<0.0470
19.73951< 84.210
199.185103 <0 0
=
IT
0.0008197<90.010 0.9919< 0.0470
269.9136<21.56 0
V =3V T =346.547<1.4017 [ KV ]
I L =I R + I 1=269.9136<21.56o +82.3032<89.96 o
I L =251.6531<3.846 o
I1 =
[A]
Y'
V R =0.0004132< 89.96o199.185 [ KV ]
2
I 1 =82.3032< 89.96o [ A ]
Perdidas en la lnea son:
PL 3 =3I 2L * R = 3 (251.6531)22.0023
PL 3 =0.3804 [ MW ]
El rendimiento calculado con la potencia activa trifsica y las perdidas en la
lnea es:
( )=
150 MW
100 =99.74
150 MW +0.3804 MW
Reg ( )=
500346.547
100 =30.69
500
[ ]
VT
=
IT
[(
1
1+ YZ
2
1
Y 1+ YZ
4
1
1+ Y Z
2
][ ]
VR
IR
[ ][
][
VT
0.9959<0.0236 o
19.80723<84.204 o
199.185 K <0o
=
IT
4.104117104 <90.011 o 0.9959<0.0236 o
269.9136<21.56o
I L =I R + I 1=269.9136<84.204 o +81.9128 j
I L =351.505<85.55o [ A ]
Y
4
I 1 = V R=4.112410 j199.185 KV =81.9128 j [ A ]
2
PL 3 =0.74218 [ MW ]
( )=
150 MW
100 =99.507
150 MW +0.74218 MW
Reg ( )=
500347.94
100 =30.41
500
[ ][
][
VT
199.185 K
1 19.80723< 84.204o
=
0
1
IT
269.9136<21.56 o
V T =201697.6<1.348o [ V ] =201.1697<1.348o [ KV ]
I T =269.9136<21.56 o [ A ]
V = 3V T =349.35 KV <1.348 o [ KV ]
S T =3V T I T =150.44 MW +63.576 MV A r j
PT =150.44 [ MW ] QT =63.576 [ MV Ar ]
I L =I R=269.9136<21.56 o
PL 3 =3I 2LR=3269.913622.0023
PL 3 =0.437622 [ MW ]
El rendimiento tomando la potencia activa trifsica y las prdidas que
ocurren en la lnea es:
( )=
150 MW
100 =99.709
150 MW +0.437622 MW
Reg ( )=
500349.35
100 =30.13
500
Conclusin:
Ocupara para modelar la lnea de transmisin el modelo de lnea media ya
que hay menos reactivos en la lnea contaminando esta, y por la extensin
en kilmetros de 120 Km