DEPOT DAILY REPORT

MIYAPUR DEPOT

Period From 00:00 Hrs To 23:59 Hrs

Prepared byDC:

A. PTW Approved / Issued

PTW Part - A issued


Part-B No.

B. PTW Burst Details

C. PTW Not executed

D. PTW Cancelled

Hanumantha rao

11

Date:

PTW Part - B issued

No's

Sch.
Closure

Company

PIC

Act. Closure

S2-P16-0017

THALES

Sameer

18:00

19:00

Part-A No.

Company

PIC

Sch. Start

Sch. Closure

Sl. No. in Plan

Company

PIC

Sch. Start

Sch. Closure

Start time

End Time

2. No. of Vehicle Movements


S.No.

Vehicle type

Movement Description

TS 13

00:12

18:51

DCS / CBTC - SAT on Stage-2.


Stabling : SBL-5.

II

TS 12

00:31

18:46

DCS / CBTC - SAT on Stage-2.


Stabling : IBL-1.

III

BT

12:04

16:02

TS 8 Shunting From IBL-2 to Test Track.


Stabling : WS.

IV

TS 8

12:33

16:49

Movement on Test track after floor modification


(Stabling : IBL-2).

TS 11

17:28

18:14

Exterior wash at ATWP.


Stabling : SBL-2.

VI

TS 14

20:27

20:44

Relocation from SBL-8 to SBL-13 (MTWP / HCL).

Time From

Hrs To

Hrs

Location:

Description:
Root Cause:
Resolution:
4. Miscellaneous Remarks
I

II

III

325172042.xlsx

ATS :
Shunt signals MD032S & 33S failed with unknown aspect. Route from MD037S to MD007S in transit lock (16-79866).

1. Since 11/04/2015 SS-125 is not operating through SCADA (AMS No: 16-41223)
2. Since 15/06/2015 SS-124 Isolator is showing unknown status in SCADA workstatio
No: 16-41224)
3. Since 15/06/2015 BS101 Interrupter when given close command goes to unknown state sometimes (AMS No: 16-41225)
4. Since 7/10/2015 SS-121 Isolator is showing OPEN status in SCADA workstation even though CLOSED
in field (AMS No: 16-41227)
5. Since 30/11/2015 Minor oil Leakage from Traction Transformer -2 at secondary bushings inspection chamber. (AMS No: 16-41228)
6. Since 16/2/2016 Battery charger displaying false alarm every time when any of the 25KV GIS breakers are operated. (AMS No: 16-41230)
7. HVAC Unit-1 is not working at MYP-RSS Building (AMS No.16-41231)
8. SCADA communication is intermittently failing in RSS & TSS RTU (AMS 16-31777)
9. 33KV I/C-1 & I/C-2 Circuit Breaker Face plate showing Ready to close indication in SCADA workstation even though closed in field (AMS 16-32
10. MYP-Depot ASS,HT Board-2 Trafo WTI fault operated showing TRUE status in SCADA workstation (AMS 16-32149)
11.MYP-Depot ASS, HT Board-1 Bus Voltage showing ZERO (0) in PINK colour value even though BUS charged in SCADA workstation. (AMS 16-3
12. MYP-Depot ASS Breakers (52-13,52-15,52-16) Face plate showing TRUE Status for both Service & Test position at the same time in SCADA w
(AMS 16-32151)
13. In detail view of 33KV RSS C.B (M B 52 010) is not showing MWH & MVAH readings in SCADA workstation (AMS 16-32152)
14. Since 26/04/2016 SS-113 is not operating through SCADA but when operated locally feedback is true (AMS 16-32156)
15. Since 01/05/2016 Isolators SS-111, SS-114 & SS-115 are showing Unknown status in SCADA workstation (AMS 16-32551).
16. MYP-TT2 abnormal sound observed at LT side (AMS 16-72566).

17. KPHB Circuit Breaker (52-33) not operating thru SCADA (AMS 16- 81626).
18. SR NAGAR Circuit Breaker (52-79) Showing Local Mode in SCADA, even it is in remote mode @ field (AMS 16-81635)
19. BS-103 is showing unknown status in SCADA workstation when given OPEN/CLOSE command through SCADA (AMS No. 16-82215)

R DEPOT
25-Jul-16
11
No's
Remarks
Work was in progress
Remarks
Reason
No's
Mutiple
Mutiple
Mutiple
Mutiple
2
2

tus in SCADA workstation (AMS

25)

o: 16-41228)
(AMS No: 16-41230)

osed in field (AMS 16-32145)

workstation. (AMS 16-32150)


e same time in SCADA workstation

2152)
6)
551).

5)
No. 16-82215)