Sie sind auf Seite 1von 50

Electric Motor Protection

Gunawan # 119452
Electrical/Maintenance

Agenda
1 Introduction
2 Motor Electric Failures
3 Relay Protection

4 Agenda 4

1 Introduction

1. Introduction
Costs Associated with Motor Failures
Costs Associated with Motor Failures

Equipment downtime
Loss of production
Collateral equipment damage
Equipment replacement
Work in process damage
Overtime for repair crews
4

1. Introduction
Thermal Breakdown

Electric Motor Failures causes


Thermal
Mechanical
Environmental

Thermal Breakdown

1. Introduction

2 Motor Electrical Failures

2. Motor Electrical failures

2. Motor electrical failures

Thermal breakdown causes


Thermal Breakdown
Over load
Voltage variations
Single Phasing

Short Circuits

Thermal Breakdown

Lightning and Surges


Improper Ventilation / Cooling
Dirt / Dust Accumulation
10

Over load
Thermal Breakdown
Process Cause (Excessive load)
High Ambient Condition

Thermal Breakdown

Power supply ( Voltage / Current unbalance)

11

Voltage
Voltage Variations
Phase unbalance
Thermal Breakdown

Phase loss (Single Phasing)

12

Low Voltage..cause
Demand for power is greater than the
supply
Long cable runs
Overloaded transformers
Thermal Breakdown
Distribution system

13

Low Voltage Effect


Reduced efficiency

Reduced life expectancy


Increased temperatures
Increased currentThermal Breakdown
Lower torque

14

High Voltage Effect


Reduced efficiency
Reduced power factor
Increased power consumption
Increased current Thermal Breakdown
Increased temperature

15

Voltage Unbalance
Percent voltage unbalance

= 100 x Maximum voltage deviation from average voltage


average voltage

Thermal Breakdown

example:
Assume voltages to a motor are 228 V to Phase A, 220V to
Phase B and 236 V to Phase C. The average voltage is
228 V. The voltage unbalance is as follows:
Voltage imbalance = 236-228 x 100 = 3.5%
228

16

Cause of Voltage Unbalance


Unequal loading of a three phase system
Unequal tap settings on transformers
Loose connections in the power system
Damaged starter contacts
Thermal Breakdown
Open delta transformer systems
Storms (lightning)
Poor regulation by utility

17

Voltage unbalance Effect


Horsepower Derating

Thermal Breakdown

18

Single Phasing

Thermal Breakdown

19

Causes of Single Phasing


Damaged motor starter contact
Burned open overload relay
Damaged switch or circuit breaker
Blown fuse
Thermal Breakdown
Open cable or bus on transformer
secondary
Open motor winding
Open transformer winding

20

Mechanical breakdown causes


Thermal Breakdown
Bearing failure
Vibration
Improper alignment

21

Thermal Breakdown

Bearing failure causes


Thermal Breakdown
Improper Lubrication
Excessive Belt Tension
Misalignment

22

Thermal Breakdown

Environmental breakdown causes


Thermal Breakdown
Moisture / Water
Corrosion / Chemical
Age

23

Thermal Breakdown

% Causes of Motor Failures


Thermal Breakdown

Thermal Breakdown

24

Causes of Motor Failures


Thermal Breakdown
Bearing

Rotor Failures

Failures

5%

Overload

13%

30%

Thermal Breakdown

Contaminants
19%

Single Phasing

Misc
9%

Old Age
10%

25

14%

3 Relay Protection

3.1 Thermal overload relay


Thermal Breakdown

27

Thermal over load function :


Thermal Breakdown

Over load
Application : Low Voltage motor 480 V

28

Thermal O/L curve


Thermal Breakdown

Thermal Breakdown

29

Thermal O/L operation


Thermal Breakdown

Thermal Breakdown

30

Thermal O/L connection


Thermal Breakdown

31

Thermal Over load installation

Thermal Breakdown

32

3.2 Time Over current relay


Thermal Breakdown

33

Time Over current Function


Thermal Breakdown

Over load
Instantaneous Over current
Stall time
Application : Medium Voltage motor
4160 V

34

Time Over current relay connection

Thermal Breakdown

35

Time Over current relay operation


Thermal Breakdown

36

3.3 Lodtrak IV relay

Thermal Breakdown

37

Lodtrak IV Function

Thermal Breakdown

Over load
Over Temperature
Instantaneous Over current
Phase Unbalance
Stall time
Under current
Load jam

Application : Medium Voltage motor


4160 V
38

Lodtrak IV Function connection

Thermal
Breakdown

39

3.4 Differential relay

Thermal Breakdown

40

Differential Relay functions


Thermal Breakdown
Internal fault

Application : High Voltage motor


13800 V

41

Differential relay connection


Thermal Breakdown

42

Differential relay operation


Thermal Breakdown

43

3.5 Digital Relay


Thermal n

44

Motor Management Relay functions


Thermal Breakdown
Over load

45

Over Temperature
Instantaneous Over current
Phase Unbalance
Stall time
Under current
Load jam
Under / Over Voltage
Ground fault

Application : Medium Voltage motor


4160 V

Motor Management relay Connection


Thermal n

46

3.5 Digital Relay


Thermal n

47

48

M 60 Motor Relay functions


Thermal Breakdown
Over load
Over Temperature
Instantaneous Over current
Phase Unbalance
Stall time
Under current
Load jam
Differential
Under / Over Voltage
Ground fault
Application : High Voltage motor
13800 V

M 60 Motor Relay connection

49

Thank you

Copyright 2013 PT Badak NGL. All Rights Reserved.

Das könnte Ihnen auch gefallen