Powerware 9135 HARDWARE INTRODUCTION

AND TROUBLESHOOTING
1. PCB And Wiring ........................................................................................................3
1.1 Power Module..................................................................................................6
1.1.1 Power Circuit ........................................................................................6
1.1.2 Control Circuit ......................................................................................9
(1) Driver Circuit of Rectifier SCR (SCRA1 & SCRA2)......................9
(2) Driver Circuit of Battery SCR........................................................10
(3) Driver Circuit of Inverter Output SCR........................................... 11
(4) Normal AC (Rectifier) Fuse Broken Detection..............................12
(5) Input Voltage Detection..................................................................13
(6) Input Frequency And Zero-Crossing Detection .............................14
(7) Inverter Voltage Detection..............................................................15
(8) Output Voltage Detection ...............................................................16
(9) Inverter Fuse Broken Detection .....................................................17
(10) Inverter Output Current Detection ...............................................18
(11) Inverter Control Circuit ................................................................19
(12) Output DC Offset Compensation Circuit .....................................20
(13) Inverter Ipk Protection Circuit .....................................................21
(14) DC-DC Control Circuit ................................................................22
(15) Driver Circuit for IGBT of DC-DC Converter.............................30
(16) Driver Circuit for IGBT of Inverter .............................................31
(17) Charger .........................................................................................32
(18) Auxiliary Power Circuit ...............................................................34
(19) Auxiliary Power For +/-5V ..........................................................35
(20) Watchdog for Power Module MCU .............................................36
(21) Communication Circuit ................................................................37
(22) Other Detection Circuit ................................................................39
1.2 System Frame.................................................................................................41
1.2.1 Power Circuit ......................................................................................41
1.2.2 Control Circuit ....................................................................................43
(1) Bypass SCR Short-Circuit Detection .............................................43
(2) Bypass SCR Driver ........................................................................44
(3) Output Current Detection ...............................................................46
(4) Input And Output Voltage Detection ..............................................47
(5) AC Auxiliary Power Circuit ...........................................................48
(6) DC Auxiliary Power Circuit...........................................................49
(7) Auxiliary Power Failure Detection.................................................50
(8) Battery Voltage Detection ..............................................................51
1

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(9) Battery Pack Detection...................................................................52
(10) Auxiliary Power For 5V ...............................................................53
(11) LCD And LED Driver ..................................................................54
(12) Watchdog For System MCU ........................................................55
(13) Communication Circuit for RS232 & USB..................................56
(14) Communication Circuit for Minislot............................................59
(15) Communication Circuit For Dry Contact.....................................61
(16) Communication For System and Power module..........................62
(17) EXB Detection Circuit (RJ45) And EPO Circuit (RJ12) .............65
(18) Other Detection Circuit ................................................................66
2. Troubleshooting .......................................................................................................67
2.1 Internal Fault..................................................................................................67
2.1.1 Alarm 34: CHARGER FAULT.............................................................67
2.1.2 Alarm 193: FAN FAULT......................................................................68
2.1.3 Alarm 004: UPS TEMPERATURE FAULT.........................................69
2.1.4 Alarm 701: INVERT FUSE BLOWN...................................................70
2.1.5 Alarm 100: NORM AC FUSE BLOWN...............................................71
2.1.6 Alarm 30: RECTIFIER FAULT ...........................................................72
2.1.7 Alarm 28: DC BUS +/- TOO HIGH/LOW ..........................................73
2.1.8 Alarm 31: INVERTER FAULT ............................................................74
2.1.9 Alarm 191: BATTERY FAULT.............................................................75
2.1.10 Alarm 36: AUTO BYPASS FAULT ....................................................76
2.1.11 Alarm 00A: DC POWER SUP FAULT..............................................77
2.1.12 Alarm 63: INTERNAL COM FAULT.................................................78
2.1.13 Alarm 006: COM FAULT BETW UPS ..............................................79

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
1. PCB And Wiring
Fig 1.1
B

LCD

WL1
#22 WL2
CNL2

WB2(P1)

WB4(P2)

CNA12(P2)

WB1(N1)

CNA10(N1)
CNA11(P3)

WB3(P3)

WB6(BATT+)

WB9(B-)

CNB1

26p

CNA9(P1)

CNA4(BATT+)
CNA5(B-)

34p

CNM1

#22

CNB4

20p CNM5

26p

21

WE6(O/L)

25

24
35

26p

CNP3

WG5
WG6
CNG4

32
31
22

CNG3(#10)

14p

CNP4

CNG1
(INV/L)

#18

CNG9 (O/L)
CNG8 (N1)

CNG7
(IP/L)

WE3(B-)
WE1(B+)

WE8(FG)
CNE2(FCI)
WE12(IP/L)
WE5(IP/N)

CNG2(#10)

CNE1

CNV7

23

PDU

#10
EXTB-

EXTB+

12
13

CNG10
(IP/N)

20p
CNV5

CNP9(B-)

CNP1(B+)

CNP8(B+)

CNP12(B-)
CNP2
WP1(G3)
WP2(+12VF)
WP3(-12VF)

#22

10
11

30

P
#10

WD11(ON)
WD14(G3)

WD3(B+)
WD4(B-)
WD1(IP/L)
WD2(IP/N)
WD5(FG)
WD6(O/L)
CND2(FCI) WD7(O/N)

CNS12
CNS6
CNS10
CNS11

CNS1

CNV3

CNS8

WD10(+12VF)

CND1

#12
#12
#12
#12

#22

CNB5

CNA1

CNA6(O/N)
CNA7(O/L)
CNA3(IP/N)
CNA2(IP/L)

15

CNS2

CNB3

CNB7(B-)

Minislot

CNP7

CNM3

CNB6(B+)

CNP14

CNB2

CNM4

Battery

efza

CNM2

EXT BAT

34

33

28
29

33

G N L
OUTPUT

G N L
INPUT

Terminal

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
WIRE LABEL

WIRE

COLOR

POSITION

AWG 10# BLACK B BOARD WB9 TO A BOARD CNA5

AWG 10#

AWG 10# BLACK B BOARD WB3 TO A BOARD CNA11

AWG 10# BLACK B BOARD WB1 TO A BOARD CNA10

AWG 10# BLACK B BOARD WB4 TO A BOARD CNA12

AWG 10# BLACK B BOARD WB2 TO A BOARD CNA9

AWG 10#

AWG 10# BLACK D BOARD WD4 TO B BOARD CNB7

10

AWG 10# BLACK D BOARD WD1 TO A BOARD CNA2

11

AWG 10# WHITE D BOARD WD2 TO A BOARD CNA3

12

AWG 10# BLACK D BOARD WD6 TO A BOARD CNA7

13

AWG 10# WHITE D BOARD WD7 TO A BOARD CNA6

15

AWG 10#

Y/G

D BOARD WD5 TO CASE G

21

AWG 10#

Y/G

E BOARD WE8 TO CASE G

22

AWG 10# BLACK E BOARD WE3 TO P BOARD CNP9

23

AWG 10#

24

AWG 10# BLACK E BOARD WE12 TO G BOARD CNG7

25

AWG 10# BLACK E BOARD WE6 TO G BOARD CNG1

28

G BOARD CNG3 TO TERMINAL BLOCK


AWG 10# WHITE NORMAL AC SOURCE N

29

G BOARD CNG2 TO TERMINAL BLOCK


AWG 10# BLACK NORMAL AC SOURCE L

30

AWG 18#

31

G BOARD CNG8 TO TERMINAL BLOCK


AWG 10# WHITE OUTPUT N

32

G BOARD CNG9 TO TERMINAL BLOCK


AWG 10# BLACK OUTPUT L

33

AWG 10#

RED

RED

RED

Y/G

B BOARD WB6 TO A BOARD CNA4

D BOARD WD3 TO B BOARD CNB6

E BOARD WE1 TO P BOARD CNP1

G BOARD WG7 TO P BOARD NUT

Y/G

TERMINAL BLOCK OUTPUT G TO CASE

33

AWG 10#

Y/G

TERMINAL BLOCK NORMAL AC SOURCE


G TO CASE

34

AWG 10#

Y/G

BATTERY CONNECTOR 3PIN G TO CASE

35

AWG 10# WHITE E BOARD WE5 TO G BOARD CNG10

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
1.1 Power Module
Power Module includes :
A board: Input and Output EMI Filter, Rectifier, Inductance of DC-DC Converter,
Inductance of Inverter, Output SCRs and Battery SCR Circuit
B board: Switching Devices of DC-DC Converter, Bus Capacitors, Switching Devices
of Inverter, Auxiliary Power and Charger
M board: MCU of Power module and Control Circuit
D board: External Connector of power module

1.1.1 Power Circuit


The power circuit of power module is showed as Fig 1.2. The function of main
components are described as below:
CA1, LA1, LA2, CA6/CA7/CA8: Input EMI Filter
FUA1: Normal AC (Rectifier) Fuse
CTA1: Input (Rectifier) Current Feedback
SCRA1, SCRA2: Rectifier
DA3, DA6: Freewheeling Diode During Battery Mode
LA8/LA9, LA10/LA11: Inductance of DC-DC Converter
Q10/Q11/Q12, Q14/Q15/Q16: IGBT of DC-DC Converter
DB1, DB2: Freewheeling Diode of DC-DC Converter
C17/C19/C21/C23/C25/C27: DC BUS + Capacitors
C18/C20/C22/C24/C26/C28: DC BUS Capacitors
QB18/QB19/QB20, QB22/QB23/QB24: IBGT of Half-Bridge Inverter
CTB1: Inverter Inductance Current Feedback
LA4/LA5/LA6/LA7: Inductance of Inverter
FUA4: Inverter Fuse
CA25/CA26: Output Capacitor of Inverter
SCRA6/SCRA7: Output SCR of Inverter
CTA3: Inverter Output Current Feedback
CA34, LA3, CA27: Output EMI Filter
QB47, QB50: MOSFET of Flyback Charger
6

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
DB41, DB42: Freewheeling diode of charger
TB3: Charger Transformer
DB44: Output Diode of Charger
CB111: Output Capacitor of Charger
DB46: Isolative Diode Between Charger and Battery
FUB2: Output Fuse of Charger
FUB3, FUB4: Battery Fuse
CA18: Battery Capacitor
SCRA3, SCRA4: Battery SCR
RA12/RA13, SCRA5: Soft-Start Circuit During Cold Start
CTA2: Battery Current Feedback
TB1: Auxiliary Power Transformer
QB44: MOSFET of Auxiliary Power
RB191: Inductance Current Detection Resistor of Auxiliary Power
RLB1, RB201, DB47: Start Circuit of Auxiliary Power

CNA7
(O/L)

CNA6
(O/N)

CNA3
(IP/N)

CNA2
(IP/L)

CA37

CA1

LA3

LA1

CTA3

CA34

LA2

CTA2

SCRA5

SINLA4/LA5/
LA6/LA7

LA10/LA11

DA6

DA3

LA8/LA9

SCRA4

CA18

SCRA3

SIN+

FUA4

RA12/RA
13

CA25/CA
26

A Board

SIN-

SIN+

SCRA7

SCRA6

SCRA2

CTA1

CA6/CA7/CA8

FUA1

SCRA1

CNA5
(B-)

CNA4
(BATT+)

CNA11
(P3)

CNA12
(P2)

CNA10
(N1)

CNA9
(P1)

WB9
(B-)

CNB7
(B-)

WB6
(BATT+)

WB3
(P3)
CNB6
(B+)

WB4
(P2)

WB1
(N1)

WB2
(P1)
BUS+

DB2

CB111

DB44

BATT+

BUS-

CB18/CB2
0/CB22/C
B24/CB26/
CB28

CB17/CB1
9/CB21/C
B23/CB25/
CB27

FUB2 DB46

FUB4

FUB3

QB14
/QB1
5/QB
16

QB10/
QB11/
QB12

DB1

DB42

BUS-

QB47

BUS+

BATT+

To UC3845P7

DB10

RB186

DB47

RB201

RLB1

DB41

QB50

RB191

QB44

DB48 NTCB1

B Board

TB3

QB22/QB
23/QB24

CTB1

QB18/QB
19/QB20

CNB5

BATT+

TB1

To -V1
To V3+/V3- (INV Driver)

To V6+/V6- (PFC
Driver)

To V5+/V5- (PFC
Driver)
DB19

To V3
(Fan)
TB2 DB18

To V1

20V to
UC3854

DB24 To V4+/V4- (INV Driver)

DB23

DB14

DB12

DB4

DB13

DB20

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Fig 1.2

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
1.1.2 Control Circuit
(1) Driver Circuit of Rectifier SCR (SCRA1 & SCRA2)
Located at A board
TVSA1

SIN+

CA10 RA6

RA3

V3

1
2

RECT+'

SCRA1

DA2

RA7

DA4

JPA1

UA1

CA11
K

DA1

RA4

V3

JPA2

1
2

UA2

RA8
CA13

TVSA2
CA14

SCRA2

RECT-'

RA9

DA5

SIN-

Located at M board
8

(20)

RECT+

(21)
(65)
(66)
(67)

RECTBATSOFT
BATSCR1
BATSCR2

7
6
5
4
3
2
1

UM11
ULN2003A
GND COM
7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

V1
9
10
11
12
13
14
15
16

RECT+'
RECT-'
Bs'
Bon1'
Bon2'

(a) SCRA1 will become a diode if RECT+ becomes low


(b) SCRA2 will become a diode if RECT- becomes low
(c) Test JUMP:
JPA1: SCRA1 will become a diode no matter what RECT+ is if JPA1 is shorted.
JPA2: SCRA2 will become a diode no matter what RECT- is if JPA2 is shorted.

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(2) Driver Circuit of Battery SCR
Located at A board
RA13

V3

TVSA4

RA18

DA10
1

JPA3 1
2

UA3

CA22

RA15

CA21

DA9

SCRA5

CA20

DA8

RA14

CA19

SCRA3

TVSA3

RA12

DA11

RA16
RA17

Bon1'
V3

RA19

JPA4 12

Bs'

UA4

(a) During the soft-start process of cold start, Bs will be low to turn on SCRA5. The
Bus capacitor will be charged by battery through RA12 and RA13.
(b) After soft-start, Bs will be high to turn off SCRA5 and Bon1 will be low to turn
on SCRA3. Then the input of DC-DC converter will be supplied by battery
through SCRA3.
(c) Test JUMP:
JPA3: SCRA3 will be off no matter what Bon1 is if JPA3 is shorted
JPA4: SCRA5 will be off no matter what Bs is if JPA4 is shorted

10

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(3) Driver Circuit of Inverter Output SCR
Located at A board

DA15

TA1

SCRA7

CA31

SCRA6

QA1

37KHz

RA35

CA29

2
D

INVSTS'

V3

RA39

10

CA27

DA16

RA36

RA34

CA28

RA38

HSA1

CA30

RA37
7

DA14

Located at M board
CM144

5V

5V

RM3
UM36A

UC33-3
5

2
2V5

INVSTS

LM339

12
11

UM15D
CD4066B
C
IN

OUT

10

UC10-3

12

(32)
-5V
CM131
V1

UC10-3

7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

10
11
12
13
14
15
16

RM35

7
6
5
4
3
2
1

V1
9

RM34

UM10
ULN2003A
GND COM

INVSTS'

(a) The driver signal is generated by MCU (Pin32). The frequency is 37Hz.
(b) The output of driver signal is control by Watchdog (UC33-3). If Watchdog is
active low, then UM15D is disable and inverter output SCR cant be turned on.
Refer to Watchdog for Power Module MCU for UC33-3 signal.

11

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(4) Normal AC (Rectifier) Fuse Broken Detection
Located at A board
FUA1
LA2

CTA1
2

DA18
DA17

RA44

RA28

RA45

FB

RA29
FA

Located at M board
RM122
5V
V1

CM148

RM235

RM124
RM117

RM212

QM25

IP_FUSE

FA

(4)
2

CM130

FB

RM170

12

RM64
CM149

UM3A
LM339

DM24

ZDM2
5V

RM234

RM45
V1

(a) If fuse (FUA1) is not broken, then FA should be equal to FB and IP_Fuse (4) will
be active high.
(b) If fuse (FUA1) is broken, then FA > FB then IP_Fuse (4) will be active low.

12

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(5) Input Voltage Detection
Located at A board
RA1

Vi1

RA2

FUA1
LA2

CTA1
2

Located at B board
CB41

RB65
DB25

RB67

-V1

RB68

11

Vi1

RB66

CB64

DB26

Vin
1

RB69

RB70
CB42

UB14A
TL084
CB65

V1

Located at M board
5V
DM2

Vin

RM115
CM9

RM177

VinR
(81)

(a) Vin is full rectified sine wave


(b) MCU detects the RMS voltage of input through VinR(81)

13

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(6) Input Frequency And Zero-Crossing Detection
Located at A board

RA40

RA41
Vi2

FUA1
LA2

CTA1
2

Located at M board

Vi2
5V
DM1
1N4148

RM87
10K

CM84
223

RM161
10K

QM13
MMMBT2222A

RM176
100K

RM141

INPZO
(24)

1K
CM91
102

(a) The waveform at INPZO (24) is square wave


(b) MCU detection the zero-crossing through the falling edge of square wave

14

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(7) Inverter Voltage Detection
Located at A board

CA26

FUA4

CA25

LA7

RA26

RA27

Vinv2

Located at M board
CM90

Vinv2

RM104

RM147

13
RM193

RM194

(75)
14

RM103

12
CM89

RM146

Vinv_R

UM5D

2V5

(a) The waveform at Vinv_R (75) is full sine wave with 2V5 DC offset
(b) MCU detects the RMS voltage of inverter output through Vinv_R (75)

15

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(8) Output Voltage Detection
Located at A board
CTo+RA32 CToLA3

CA34

RA33

CTA3
W2

RA30

RA31

Vout

Located at M board
CM87
RM143

Vout
RM94
9

RM191

UM5C
8

RM93

10

Vout_R

(78)

TL084

RM192
CM85

RM142
2V5

(a) The waveform of Vout_R (78) is the rescale of output voltage with 2V5 DC offset.
(b) MCU detects the RMS value of output voltage through Vout_R (78)

16

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(9) Inverter Fuse Broken Detection
Located at A board

Vinv3

RA47

RA48

CA26

FUA4

CA25

LA7

Located at M board

-V1
RM236
RM220
9
Vinv3

RM238

11

UM40C
LM324
8

13

UM40D
LM324
14

12

10
CM22

RM237

RM239
V1

5V
RM233

DM25

RM221

ZDM1
3V9

QM24

OP_FUSE
(11)
CM25

CM24

RM232

(a) If inverter fuse (FUA4) is not broken, the waveform of Vinv3 is full sine wave.
The line frequency signal cant go through the high-pass filter (UM40D), so
OP_FUSE (11) will be active high
(b) If inverter fuse (FUA4) is broken, then the waveform of Vinv3 will be PWM
waveform. This high frequency signal can go through high-pass filter (UM40D)
and OP_FUSE (11) will be active low.

17

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(10) Inverter Output Current Detection
Located at A board

CTo+RA32 CToLA3

RA33
CA34

SCRA7

CTA3
SCRA6

Located at M board
5V
DM19
RM75

CM88
IOUT
RM96

5V

CM60
11

-V1

RM158
6

CTo+

RM95
RM44

RM173

UM5B
TL084

Iout_R

5
4

RM172
CM86

CTo-

RM61

7
RM43

RM62
RM131

UM5A
TL084

(77)

V1

DM23

RM157

CM59

CM105

-5V

(a) The waveform of Iout_R (77) is rescale of inverter output current with 2V5 dc
offset.
(b) MCU detect the RMS value of inverter output current through Iout_R (77).

18

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(11) Inverter Control Circuit
Located at A board
LA7
RA24

RA25

Vinv1

CA26

FUA4

CA25

RA23

Located at M board
(112)
SPWM_R

CM114

CM116

RM186

9
RM205

RM200
RM97

UM6D
13

CM119

RM98

14

IN
C

OUT

8
6

IOUT

IOUT

RM206

5V

UM15C
CD4066B

RM179

RM199

12
RM187

CM101

TL084
CM117

UM36B
7
1
6

RM189
Vinv1

CM118

RM119

-V1
CM10

11

RM144

V1

TPM1
RM100

UM6A
TL084

DM18

4
RM174

UM4A
LM339

V1
CM75
RM188

1
2

CM79

INVCLK

-V1

-V1
V1
CM103
RM99

QM17

UM4B

UM6B
TL084
6

RM155

6
1
7

RM101

14

INV-L

8
LM339

RM106

TPM2
RM121

CM69

INV-H

QM20

V1
TPM4

(33)

UM4D
LM339

CM64

RM190
CM100

RM203

11
CM102

V1

RM120

13

RM102

2
5

DM17

QM16

10

DC OFFSET Compensator

CM63

(63)

RM154

RM202

DIS_DROOP

V1

CM65 -V1

CM95

12

RM162

JPM4

2V5

TPM3

RM204

17KHz

DM11

UM4C
LM339

DM13

Inverter Ipk Protection

1
2
-V1

QM21

JPM1
-V1

(a) The waveform of UM6D-P14 is the reference sine wave generated by SPWM_R
(112) through band-pass filter (UM6D)
(b) Vinv1 is the feedback of inverter output
(c) The waveform of UM6B-P7 is the triangle waveform generated by INVCLK (33)
through integrator (UM6B) and the frequency is 17kHz
(d) DIS_DROOP (63) is used to enable or disable the current feedback. DIS_DROOP
(63) is high to disable the current feedback during standalone operation.
DIS_DROOP (63) is low to enable the current feedback during parallel operation.
(e) Test JUMP:
JPM1: Inverter is disabled if JPM1 is shorted
JPM4: DC offset compensation circuit is disable if JPM4 is shorted
(f) Test Point:
TPM4: Triangle wave
TPM3: Inverter driver command (output of error amplifier)
TPM1: Driver signal of top leg of half-bridge inverter
TPM2: Driver signal of bottom leg of half-bridge inverter
Refer to Output DC Offset Compensator Circuit for DC OFFSET Compensator
signal.
19

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Refer to Inverter Ipk Protection Circuit for Inverter Ipk Protection signal
(12) Output DC Offset Compensation Circuit
Located at B board
BUS+

QB18
CB27

WB3
P3

CTB1

RB36

P3

RB37

RB171
*

QB22

RB38

CB67

OS

TVSB4
P6KE18CA

CB28

BUS-

Located at M board
5V
RM123
UM36C
LM339
14

2V5

(5) OFFSET
5V

UM15B
CD4066B

14

CM61

OUT

IN
C

4
5
UM15A
13
1

CM15

C
IN

-5V

CD4066B
2

OUT

CM115
CM113

OS

RM178

RM168

RM197
RM198

9
8

CM112

CM111

10

DC OFFSET Compensator

UM6C
TL084
CM68

RM105

RM208
HOLD

-V1

RM207
HOLD

VRM1
HOLD

RM209

V1

HOLD

(a) The feedback signal is from the central point of inverter leg (P3).
(b) UM6C is used to generate the output DC feedback signal by integral the signal
OS.
(c) OFFSET (5) is low to enable UM15B and UM15A to reset and disable the integral
circuit (UM6C) while inverter is off.

20

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(13) Inverter Ipk Protection Circuit
Located at B board
BUS+

QB18
CB27

WB3
P3

CTB1

CTp+

BDB1

QB22

CB28

AC

AC

RB32 RB33
Hold

1
4

CTp-

BUS-

Located at M board
Inverter Ipk Protection
V1

6
UM3B
LM339

V1
RM195

(29)
INVIPK

RM222

DM9

(75)
Vinv_R

9
14

S
RM148

CM123

3V9
CM5

RM107

RM226
11

13

8
QM1

RM149

V1

RM196

RM164
DM14

QM18

ZDM8

2V5

RM181

RM224

G
DM8

CM13

V1

CM72

RM159
RM223

INVEN
(30)

DM12

DM10

RM108

RM163

10

CM70
RM175

12

UM3C
LM339

CM92

RM225

UM3D
LM339

2V5

RM201

CM74

CM73

CTP+
CM12

RM180

-V1
CTP-

CM71

(a) UM3D is used to disable Inverter during the start period of auxiliary power
(b) If INVEN (30) is low then Inverter is disabled.
(c) UM3C is used for inverter Ipk protection. CTP+ is the current feedback of
inverter inductance.
(d) There are two level for Ipk protection:
1st

level is

2nd level is

RM 107
V1
RM 159 + RM 107
( RM 107 // RM 224)
V1
RM 159 + ( RM 107 // RM 224)

(e) INVIPK (29) will be high to keep the Ipk to 1st level during the start of inverter
(f) If Vinv_R (rescale of output voltage) is normal, then Ipk will keep at 1st level. If
Vinv_R is lower than a specific level (for example, output short circuit) then the
Ipk will change to 2nd level
(g) The inverter output short circuit protection is about 100A.

21

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(14) DC-DC Control Circuit
Enable/Disable Circuit
Located at B board

CB49

9 2

11
15

16

20V

CB54

UB5
UC3854

RB80

V1

10
QB40

12

14

13

RB129

PFC

RB119
CB56
CB55

RB128

Located at M board

(34)

PFCEN

RM135
1K

PFC

(a) If PFCEN (32) is low then the controller of DC-DC converter is enabled. If
PFCEN (32) is high, then the DC-DC converter is disabled.

22

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Bus voltage feedback circuit
Located at B board
Vselect 2

Vbus+

RB214

RB212

RB138

Hold

CB60
QB29

RB210
UB6D
10

OUT

RB122
CD4066B

V1

C
IN

12
11

RB139

Vselect

RB136

CB52

RB134

C
IN

RB145
BUS+

RB146

CB61

RB278

UB6C
OUT

RB144

QB41

RB135

RB143

10

UB14C
TL084

CB100
Hold

CB53

RB123

RB142

RB137

DB51

RB121

RB141

RB140

TPB5

6
8

CB128

UB17B
LM339

TPB4
Q

CB130

1
Vselect

CD4066B

RB150

DB52

RB274

RB275

CB95
Hold

RB277

V1

CB129

RB151
RB276
CB51

RB148

Vselect 2

9 2

CB63

QB42
RB152

RB120

RB149

15
16

UB5

QB30

CB66

14

RB157

RB158

RB159

RB153

RB166
CB96

RB167

13

12

12

RB156

Vbus-

10
1

RB155

BUS-

12

RB211

RB154
13
14

UB14D
TL084
RB147

Hold

RB213

11

RB215

CB97
V1

UB17A
LM339

RB165

RB161

CB80
CB101

V1

RB163

Located at M board
5V

5V
DM4

RM89

Vbus+

DM5

Vbus+' (88)

Vbus-

RM90

Vbus-'
(100)

RM183

RM184

CM53

(35)

BUSEL

(9)

BUSEL2

(89)

CM54

RM114

Vselect
Vselect2

RM139

(a) UB6C and UB6D are used to selectively feedback Bus+ or Bus- voltage to
23

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
UC3854 according to signal TPB5 and TPB4.
(b) MCU detects DC Bus + voltage through Vbus+ (88) and detects DC Bus- voltage
through Vbus- (89)
(c) If BUSEL (35) is high, then DC bus +/- will increase to about +/-395Vdc
(d) Net P & Q are used for Vpeak protection. The Vpeak is set at 420Vdc.
Refer to Positive And Negative Cycle Switching for TPB5 and TPB4 signals
Refer to Output driver Signal for P & Q signals.
AC mode and backup mode switching
Located at B board

V1

V1

RB73

RB91

AC

BC

RB88

backup

RB86
QB36
RB87

JPB2

QB35
RB169

1
2

Located at M board

(66) BATSCR1

RM136

backup

(a) If BATSCR1 (66) is high, then AC signal=low and BC=high, UPS is at


backup mode. If BATSCR1 (66) is low, then AC signal=high and BC=low,
UPS is at AC mode.
(b) TEST JUMP:
JPB2: Short JPB2 will change the DC-DC converter operating at backup mode

24

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Positive And Negative Cycle Switching
Located at B board
V1
Vi2

RB84

V1

RB82
RB133
HOLD

UB14B
6

RB34

QB38

V1

TPB4

RB35

RB93
QB39

TPB5

RB18

RB81 CB47
TL084

RB83
DB27

RB31

RB92

DB3

RB85

AC

RB89

p/n

DB30

DB29

RB90

QB37

BC

Located at A board

RA40

RA41
Vi2

FUA1
LA2

CTA1
2

Located at M board
(52)

PFCSQR

RM138

p/n

(a) During positive half cycle, TPB4=low and TPB5=high. During negative half cycle,
TPB4=high and TPB5=low.
(b) During AC mode, the positive and negative half cycle are decided by input voltage
(Vi2).
(c) During backup mode, the positive and negative half cycle are controlled by
PFCSQR (52).
Refer to AC mode and backup mode switching for AC and BC signal
25

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Vrms and Iac Feedback Circuit
Located at B board
CB41

RB65
DB25

RB67

-V1

RB68

11

Vi1

RB66

CB64

DB26

Vin
1

RB69

BAT+

RB70
CB42

AC

UB14A
TL084
CB65

RB74

RB72
CB44

V1

Vbatt

BC

V1

IN
C

OUT

UB6A
CD4066B
UB6B
4
5

IN
C

OUT

CD4066B

9 2

UB23A
TL0721

16

RB76
4

RB118

10

-V1

RB79

12

14

RB124
Hold

UB5
UC3854

CB45

RB78

11
15

CB43

13

Hold

RB263

RB75

RB77

1
13

RB71

RB125
CB57

RB126
V1

RB127

CB58

CB46

Located at A board
RA1

Vi1

RA2

FUA1
LA2

CTA1
2

(a) During AC mode, the feedback of Vrms (UC3854-P8) and Iac (UC3854-P6) is
from Vin
(b) During Backup mode, the feedback of Vrms (UC3854-P8) and Iac (UC3854-P6)
is from Vbatt
Refer to AC mode and backup mode switching for AC and BC signal

26

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Current Feedback Circuit
Located at B board
RB96

V1

RB97

DB33

V1

RB98

RB100

11
13

Ipeak

RB99
CTi-

RB115

RB101

10

RB113
UB17D
LM339

RB112
DZONE

DB40

RB111
RB114
RB110

ZDB10

CB59

CB50
RB116
RB117
DB39

9 2

CB48

11
15

16

UB5

8
10
1

12

14

13

Located at A board

Battery Discharge Current


CTA2

AC Input Current
CTA1
4

DA7

CTi3

BDA1
RA5

3
2

AC
AC

RA10 RA11
HOLD HOLD

-V1

CA17V3

Located at M board

(50)
D-ZONE

RM33

DM16
DZONE

(a) CTi- is the combination signal of AC input current and Battery discharge current.
27

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
During AC mode, CTi- will feedback the AC input current. During backup mode,
CTi- will feedback the battery discharge current.
(b) During AC mode, D-ZONE (50)=low. During backup mode, D-ZONE (50) will
provide 5V/550us pulse around zero crossing of inverter output voltage to disable
the gate signal of DC-DC converter. This function is used to prevent battery
short-circuit in common battery structure.
Refer to Output driver Signal to Ipeak signal

28

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Output Driver Signal
Located at B board
RB104
DB31

UB8B
D+

4071

RB94

D-

CB62

DB38

RB109

16

UB5
UC3854

13

RB95

11

RB108

12

JPB1

UB8D
4071

2
1

10

RB106

34KHz

12

14

13

DB37
RB103

BC

11
15

UB8C
4071

4071

RB105

DB32

UB8A

V1

10
V1

TPB5
DB34

4
5

RB102

Ipeak

RB107

TPB4

DB36
DB35

(a) During positive half cycle, TPB5=H and TPB4=L


During negative half cycle, TPB5=L and TPB4=H
(b) During AC mode, BC=L
During backup mode, BC=H
(c) During positive half cycle of AC mode, D+ is PWM control and D-=L
During negative half cycle of AC mode, D+=L and D- is PWM control
During positive half cycle of backup mode, D+ is PWM control and D-=H
During negative half cycle of backup mode, D+=H and D- is PWM control
(d) Test JUMP
JPB1: If JPB1 is shorted, then DC-DC converter is disabled.
Refer to AC mode and backup mode switching for BC signal
Refer to Positive And Negative Cycle Switching for TPB4 and TPB5 signals
Refer to Current Feedback Circuit for Ipeak signal

29

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(15) Driver Circuit for IGBT of DC-DC Converter
Located at B board
V1

RB2

V5+

QB5

CB7
QB1

RB1

D+

RB5
CB5
UB1

1
2
3
4

RB62
TPB7

RB11 RB12

ZDB1
18V

8
7
6
5

QB10
QB6

QB48
RB6

D-

V1

V6+

CB6

RB3
1
2
3
4

TPB6

UB2

ZDB2
18V

CB8

V5-

RB4

RB13

RB9

TLP250

QB3

RB19

8
7
6
5

CB9 ZDB3
18V

QB7
RB14 RB15 RB20

RB7

RB16

RB10

RB63

QB8

TLP250
QB49
CB10RB8

QB14

ZDB4
18V

V6-

Refer to Output Driver Signal of DC-DC Control Circuit for D+ and D- signals

30

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(16) Driver Circuit for IGBT of Inverter
Located at B board
CB31
V3+

QB20

ZDB5
18V

RB47

QB25

CB33

RB39

RB45

RB44

RB43

UB3

8
7
6
5

RB46

1
2
3
4

INV-H

RB49

TLP250

QB26

ZDB9

RB48

-V1

ZDB6
18V

CB32

QB24

V3-

RB55
V4+

CB34
QB27
RB56

ZDB7
18V

RB59

RB57

CB36
RB58

RB51

QB28

8
7
6
5

UB4

TLP250
RB60

1
2
3
4

ZDB12
INV-L

RB50
-V1

ZDB8
18V
CB35

V4-

Refer to Inverter Control Circuit for INV-H and INV-L signals

31

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(17) Charger
Located at B board
CB116

RB244

RB245

RB251
UB23B
6

RB162

RB130
D QB50

RB231

6
5

DB49
CB107

RB64

10
9

3 TB315,16
BUS-

CB40

10

GND

Vin

ZDB13

DB43

+15V

RB237

12,13
RB238

CB103

RB264
8

1
2

BUS-

RB183

RB182

CB104

VFB

VCC

COMP

70KHz
RB185

CB105
BUS-

QB43

VREF

OUT

RB220

UB18

1
2

RB239

V1

B/T

NTCB2

CB113

RB17

UB22

VRB1

1
2

RB249

V1

B/C

RB267 RB242
Hold

UB20
R

BUS-

RB228

GND

RT/CT

ISEN

CB108 RB229
UC3845N

RB240
CB114

RB243

RB230

V1

UB16

RB235

RB221
CB106

UB19

CHi

UB24

RB181
4

4
3

JPB3

CB98

V1

UB9

F 4A/250V

CB111

D QB47

UB21

BATT+

FUB2

RB236

RB168

P6KE18CA
UA7815K
2

CB38

RB232

TVSB2

BUSDB8

DB46

DB41

RB131

CB115

CB109

DB44

Vcharge

RB250

RB52

TVSB1
P6KE18CA

TB4

RB247

DB42

RB164

RB246

BUS+

C/O

BUS-

Located at M board

B/T
QM2

RM6

(107) BTTEST

RM1
5V
UM10
ULN2003A
8

(68)
(96)
(95)

CHRGI
BCHG
DCHG

7
6
5
4
3
2
1

DM6
V1
GND COM
7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

9
10
11
12
13
14
15
16

Vcharge
CHi
B/C
C/O

RM91
RM185

Vchg
(90)

CM55

(a) If DCHG (95)=H, then charger will be off


(b) If BCHG (96)=H, then charger will go into boost charging mode. The charger
voltage will increase to around 210Vdc
(c) If BTTEST (107)=H, then charger voltage will decrease to around 160Vdc to
perform battery test
(d) If CHRGI (68) =L, then the charger current will be about 0,6A. If CHRGI (68)=H,
then the charger current will increase to 2A.
32

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(e) MCU detects the charger voltage through Vchg (90)
(f) Test JUMP:
JPB3: NTCB2 is used to compensate the charger voltage according to ambient
temperature. If JPB3 is shorted, the charger voltage should be 194,1Vdc by
adjusting VRB1.

33

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(18) Auxiliary Power Circuit
Located at B board
RB203
RB132

CNB10

BAT+

RLB1

CB37

G3

CNB11

BAT+
3

V1
20V

RB201

CB69

DB20

CB94

V3

RB202

RB40

4
Vx

CB74
CB71

7
2
1

CB70
2

RB197

DB11

70KHz

VREF

OUT

CB2

CB85

CB3

1
-12V

-V1

UB15
7912

D
G

Vin

QB44

TB2

RT/CT

ISEN

CB92

DB23

RB192

RB262

RB258

10

CB77

V5+

DB18

V3+

CB86

RB191

CB76

RB268

10

RB190
GND

RB189

CB75

UB13

HSB5

COMP

RB188

CB79

RB199

DB14
VFB

CB112

RB179

UB7
UC3845N

RB187
8

CB78

CB82

CB84

CB72

RB196
RB198

CB83

CB73

UB12

V1

LB10
DB13

14

UB11

RB204

DB4

TVSB3
NTCB1

VCC

RB184

Poff

VFAN'

QB45

GND

DB48

G
S

13

RB257

BATT+

CB99

DB10

RB186

G3

DB6

CB81

TB1

DB47
QB2
RB170

RB160

CB4

DB12

V1

RB266

BATT+
G3

V1

Fan'

DB61

3
2
1

DB21

CNB5

DB62

V1

+12VF

CB68

1
2
3

3
2
1

TO D

DB19
7

V3-

DB24

V5-

RB269
V6+

CB93

RB259

12
A

V4+
6

CB87
11

V6-

V4-

Located at M board
ZDM10

Fan'

5V(1/2W)"1206"

RM137

FAN

(54)
UM10
ULN2003A

UM11
ULN2003A
8

(31)

(a)
(b)
(c)
(d)

DAUX

7
6
5
4
3
2
1

V1
GND COM
7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

9
10
11
12
13
14
15
16

(51)
Poff

VFAN

7
6
5
4
3
2
1

V1
GND COM
7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

9
10
11
12
13
14
15
16

VFAN'

If DAUX (31)=H, then the auxiliary power will be off


The start of auxiliary power is controlled by System MCU through RLB1
VFAN (51) is PWM signal to control the speed of fans
MCU detects the fan failure through FAN (54)

34

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(19) Auxiliary Power For +/-5V
Located at M board
QM19
V1

5V
RM118

CM104

CM57

RM127

RM126

CM11

UM34
TL431(0.5%)

RM128
A

CM121

-V1

V1

-5V
3

RM145
DM7
CM122

CM39

2V5
K

UM14
79L05

-5V
GND

CM58

Vin

CM4

R
UM35
TL431(0.5%)

CM67

CM120

35

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(20) Watchdog for Power Module MCU
Located at M board
5V
POWER_RDY
(10)

2
5

JPM3

VCC

TRIG
CVolt

THR

DM20
A

3
7

RM108

A
RM215

CM13

5V

INVEN
(30)

RM181

6
RM4
CM129

CM6
DM15

UM33
NE555

DIS
GND

QM10

RM217

2
1

UC33-3

CM7

CM128

RM213

RM116

QM22
TPM5

(a) POWER_RDY (10) will send out pulse to reset CM129. And then CM129 will be
charged again by 5V through RM215. UC33-3 will keep high level. If
POWER_RDY (10) doesnt send out pulse for a specific period (for example:
MCU is crash) then UC33-3 will be low.
(b) Test JUMP:
JPM3: If JPM3 is shorted, then UC33-3 will be low or UC33-3 will keep high
during normal operation.

36

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(21) Communication Circuit
Part 1
Located at M board
5V
5V

RM240

RM218

TOMBYP

RM9
TOMBYP_I
UC33-3
1
RM130

UM16

(16)

UM39

RM219

+12VF

RM231

CM150

ID1OK

CM18

QM26
RM17

QM7
G3
5V

+12VF

G3
RX

+12VF

RM8
QM23
RM10

(53)

SYS_RDY
CM16

RM11
5V

UM17

CM17

1
RM46

RM230

UM18

RM12
INT_TX1
BYPOK

G3

RM14

QM3

(3)
RM229

5V

+12VF

+12VF

RM18
RM76
(108)
BYP_FAIL
CM8

RM77
4
3

UM38

DM21

1
2

5V

RM22

RM13
4

INT_RX1
(2)

CM19

UM20

TX
DM22

RM24
1
2

BYP-F
QM15

G3

(a) If Power MCU is operating normally, power module will send out ID1OK signal
(b) If System MCU is operating normally, SYS_RDY (53) will be low
(c) Power MCU can detect AC utility failure through BYP_FAIL (108). BYP_F
signal is send by System MCU.
(d) Power MCU can detect the switching of manual bypass switch from TOMBYP_I
(16). TOMBYP signal is the combination signal from auxiliary windings of
manual bypass switch.
(e) INT_TX1 (3) and INT_RX1 (2) are used to communicate with computer through
RS232 port for firmware upgrade purpose.
Refer to System Frame for RX and TX signals
Refer to Watchdog for Power Module MCU for UC33-3 signal.

37

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Part 2
Located at M board
5V

VS

RM31

QM9
RM65

RM29

5V

UM37

RM30

QM14

RM67

UM12D
1

G3
VS

SYNC_O

RM28

UC33-3

ZDM6

5V
RM69

CM35

(25)
5V

RM70

CM37

VS
QM4

RM16

ZDM3

RM19

UM12B
1
4

UM25

SYNC_I

TOBYP

CM21

UM19

CM26

3
RM20

5V

5V
RM21
4

TOBYP_I
CM20

(17)

RM49
1
5

TOINV_0

INT_TX
QM5

13

12

CM124

5
RM129

UM31

G3

CM33

CM97
5V

5V
+12VF

UM12C

TOINV_I
CM27

UM23

+12VF

RM132

INT_RX
CM31

(59)

CM125

RM210

RM54

3
UM32

CM126

G3

RM48

RM125

RM58

7
8

5V

INT_DATA
ZDM9

TOINV
ZDM4

UM22

RM214
CM98

(60)

VS

CM29 RM53

(13)

UM12F
CM23

RM52

5V

QM8
G3
1

UM21

VS

RM211

RM23

8
7

RM15

+12VF CM96

+12VF

G3

(12)

(18)

+12VF

G3
RM66

CM38

RM68

(26)

QM11
RM63

TOBYP_0

SYNC_BUS

CM36

UM24

(a) If Power MCU is operating normally, then VS is on. VS is the power source for
communication circuit: TOBYP_O, TOINV_O, SYNC_O and INT_TX. If Power
MCU is not operating normally (for example: MCU is crash), then VS is off to
prevent the parallel bus is locked
(b) TOBYP and TOINV signals are used to synchronize bypass mode and inverter
mode transfer
(c) SYNC_BUS signal is used synchronize the inverter and bypass voltage.
(d) INT_DATA signal is used to transfer information between Power MCU and
System MCU.
Refer to Watchdog for Power Module MCU for UC33-3 signal.

38

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(22) Other Detection Circuit
Located at M board
5V

5V

RM7

RM2

JPM2

CNM1
1
2

1
2

PWR_RELS
CM145

REPAIR
(1)

CM14

(19)

5V
Vbatt

5V

V1
DM3

RM88

RM86
NTCM1

RM84

QM12
ZDM7

Vbat

(91)

TH2
CM62

RM182
CM52

RM85

TEMP

(93)

CM51

7V5
RM216

Located at B board
BAT+

RB74
CB44

Vbatt

V1
8

RB75

UB23A
TL0721

CB43

RB76
4

CB45
-V1

RB77

RB78

RB79
CB46

Located at B board

TH2

TH3

2
1

THB2

2
1

THB1

39

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Located at A board

WA2
#22
WA3
#22

TH3
1

(a) Power MCU detects the power module is released by PWR_RELS (19). CNM1 is
the switch at the front of power module beside the fan.
(b) MCU detects the battery voltage through Vbat (91)
(c) MCU detects the temperature inside power module through TEMP (93). TH2 is
connected to the thermal switches on B board and A board. THB2 is located on
Heatsink HSB2 and THB1 is located at Heatsink HSB1. TH3 is located at HSA2.
(d) Test JUMP:
JPM2: If JPM2 is shorted, MCU will go into repair mode
(e) CNM6 is used for programming the MCU by BDM
(f) CNM9 can connect to specific LCD to show the information of power module

40

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
1.2 System Frame
System frame includes:
G Board: Input EMI Filter and Bypass SCR
P Board: Auxiliary power for system
S Board: System MCU and control circuit. Circuit for RS-232, dry contact, RJ12 and
RJ45.
C Board: Extend board for S board
V Board: Circuit for USB, Parallel port and minislot
E Board: Connector to connect with power module

1.2.1 Power Circuit


The power circuit of system frame is showed as Fig 1.3. The function of main
components are described as below:
CG1, LG1: Input EMI Filter
CTG1: bypass SCR short-circuit detection and back-feed protection
CTG2: Output Current detection
CG4: Output EMI Filter
LP2: EMI filter of AC auxiliary power circuit
TP2: AC auxiliary power circuit. The input source is from AC utility.
TP1: DC auxiliary power circuit. The input source is from battery source.
DP23: Provide generated voltage from TP2 to TP1 input. With this diode, UPS can
start without battery
CNP14: On switch

41

N
G
INPUT

CNG10
(N1)

CG1

CNG1
(INV/L)

CNG8
(IP/N)

G Board

CG4

CTG2

CTG1

LG1

CNP9
(B-)

CNP12
(B-)

CNP1
4
1
2

CNP8
(B+)

CNP1
(B+)

1
2

FUP2

CNP3

RP15
4

RP15
5

DP8

FUP1

LP2

CP82

NTCP2

G2

G2

G2

RP160

DP27

CP148

DP23

CP147

DP22

To UC3845-P7
G2

DP28

P Board

RP179

QP12

RP2

RP1

RP180

QP22

CP146

NTCP3

To UC3845P7

DP14

G2

DP20
TP2

TP1

G2

CNG9
(INV/L)

CNG3

CNG2

CNG7
(IP/L)

WG6

WG5

CP15

CP12

CP7

CP13
DP7

DP3

DP32

CP88

CP86

DP31

DP15

DP5

DP33

CP89

CP90

DP34

DP17

G3

DP4

DP16

G1

DP1

DP18

G3

DP6

DP19

G1

DP2

To -12VF

RP39

To
+12VF

To -12VS

G3

RP38

Vi Vo
Adj

LM317

G1

LM7912
I
O
G

To
+12VS

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Fig 1.3

L N
G
OUTPUT

42

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
1.2.2 Control Circuit
(1) Bypass SCR Short-Circuit Detection
Located at G board
CTG1

CNG2

3
2

G1

WG1
#10
CT1

LG1

CG1

MOVG1

WG10
#10
*

DG2

2,3
1

SCR

CNG3

DG3

4,5
6

Located at S board

+12VS

RS234
9

US9C
TL084

5VS
DS4
8

CT1

QS4

RS227

RS235

(53)
SCRSD

RS34

10
QS5

RS231
RS228

RS229
+12VS

DS2
CS127

CS128

RS230

CS129

RS84

G1

(a) During battery mode, bypass SCR should be off and CT1 should be zero. If there
has current through CTG1 then SCRSD (53) will be Low. UPS will turn off the
inverter to prevent back-feed voltage.

43

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING

WG8
#22

WG11
#22

(2) Bypass SCR Driver


Located at G board
SCR
TG1
+12VS

THS1-1
QG1

CG9

DG3

4,5

THS1-1

RG15

DG2

2,3
1

RG1

CG6

D
BYPSTS

DG1

3
S

10

DG5

RG17

RG18

RG16

CG10

CG7

RG19

CG8
4

G1

7
G1
5

DG4

Located at S board
RS217

5VS
THS1

(91)
CPU-P91

RS67

RS162

CS24

RS163 QS24

G1

Located at S board
5VS
+12VS

RS18

5VS

CS10 5VS RS11

US36
QS15

CVolt

RS17

RS2
5VS
RS12

THR

US15B-P3

US5D
4081

G1

CS19

RS3

TO US36-P6

GND COM

7
6
5
4
3
2
1

7B
6B
5B
4B
3B
2B
1B

5VS

CS25

RS8
QS13
G1

RS74

TO US36-P4

(33)
BYPSTS

BYPSTS

9
5VS
CS32
1
US5A
2
4081

DS18
4

BYP_STS

B9

RS53

TOBYP_I

TO US36-P6
DS8

US5C
4081
(105) TOBYP_I

G1

RS118

5VS

US5B
4081

10

(49) TOBYP_O

G1

DS10

RS117

811

US15B-P3
G1

10
11
12
13
14
15
16

MM74HC14
US20B

DS11

G1
RS9

7C
6C
5C
4C
3C
2C
1C

ULN2003A
G1

US4
TLC555C

DS13

RS47

RS19

3
7

13

DIS
GND

TRIG

CS41

12

VCC

G1

G1
5VS

+12VS
9

TOBYP_I
(105)

RS114

B10
CS49

5
G1

44

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Located at V board
RV48

VS

QV2
5VS

RV33

UV14

ZDV2

4
CV13

B9

CV16

3
RV50
G3
RV62

+12VF
B10
G1

4
3

UV15

RV18

TO BYP

1
2

CV21

(a) THS1-1 is connected to the thermal switch located at heatsink of bypass SCR. If
the thermal switch is open due to over-temperature, the driver will be off
(b) MCU can detect over-temperature of bypass SCR through CPU-P91 (91)
(c) The bypass SCR driver signal will come from MCU or US4 according to the
signal TO US36-P4.
(d) TO US36-P4 is the output of MCU watchdog. If MCU is operating normally
then TO US36-P4 will be high and the bypass driver signal will come from
BYPSTS (33).
If MCU is not operating normally, TO US36-P4 will be low and then the bypass
driver signal will come from US4
(e) US4 is a 37kHz self-oscillator that can provide driver signal for bypass SCR.
(f) RS47/DS13/CS41 is used to disable the output of US4 during initialization of
auxiliary power
(g) The output of driver signal from US4 is also limited by TOBYP_I (105) signal
(h) US15B-P3 is the signal used to send out To bypass signal on parallel port no
matter the bypass SCR is driven by MCU or US4
Refer to Watchdog For System MCU for TO US36-P4 signal.

45

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(3) Output Current Detection
Located at G board

SCR
DG3

DG2

CNG10

N1
OP/CT+
OP/CTRG2

CG4

CG5
MOVG4

WG9
#10
1

2,3
1

WG10
#10

4,5
CTG2

MS-130125-2-01

CNG1
1

WG3
1
CG11
O/L

CNG9

TO T

Located at S board
CS16
RS33

5VS

CS96
11

-12VS
RS55

OP/CT-

G1

RS157

2
RS51

RS54
CS15

RS32
4

OP/CT+

(76)
Iout_R

RS21

3
US9A
TL084
CS97

+12VS

CS34
G1

G1
G1

(a) MCU detects output current through Iout_R (76). The output current could be
bypass current or inverter current according to operation mode

46

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(4) Input And Output Voltage Detection
Located at G board

CNG2
I/L

LG1
4

OP/CT+

RG2

OP/CT-

N1

MOVG1

CG4

CG1

CNG10

CTG2
1

CNG1

I/L

WG3

CNG3
RG3

RG7

RG11

RG4

RG8

RG12

I_N

O/L

O/L

I_L

RG5

RG9

RG13

RG6

RG10

RG14

CNG9

O_L
O_N

Located at S board
CS5

RS38

RS26

5VS
5VS

5VS

Vbyp_R

CS36
11
2

RS239

CS4

DS1

(25)
BYPZO_R

RS169
O_L

US16A

CS20

RS172

O_N

G1

RS25
RS244

6
7

RS245

RS22

RS190

QS1

G1
1

CS2

Vout_R
(77)
CS29

RS173

(80)

-12VS

RS238

RS156
RS29

RS30

RS24

+12VS

CS1

US16B
TL084

CS95 G1
G1

G1
CS56

I_L

5VS

RS100
RS240

13
14

RS241

RS102
RS101

12
CS17

RS99

G1

G1

5VS

I_N

VinR

RS192
(75)

RS196

INPZO_R

(24)

US16D
DS3

RS195

QS3

CS18

RS191

G1

(a) MCU detects RMS value of output voltage through Vout_R (77)
(b) MCU detects RMS value of bypass voltage through Vbyp_R (80) and RMS value
of input voltage through VinR (75).
(c) MCU detects the bypass frequency and zero crossing through BYPZO_R (25) at
falling edge. MCU detects the input frequency and zero crossing through
INPZO_R (24) at falling edge

47

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(5) AC Auxiliary Power Circuit
Located at P board
1
2

NTCP3
I/L

CNP3

DP20

FUP2

CP2

RP161

2
G2

7
VFB
COMP

G2

DP23
D

UP4

VREF

OUT

RP174

G2

4
CP103

RT/CT

GND

G2

ISEN

RP178

QP22 S
G2

RP50

G1
CP20

12
DP33

45KHz

CP34
NC

11
CP89

DP19
-12V

UP6
LM317

DP6

G2
RP29

B+

CP92

7
DP5

B1

8
CP15

CP21

Vin

+Vout

+12VF
2
RP39

G3
CP22

RP184

RP94

CP12
CP147

CP10

G2
DP22

DP30

UP14

CP30

VCC

18V

G'

4
5

+12VS
CP19

ADJ

ZDP2 G2
G2

VCC

CP90

CP78

LP2
I/N

G1

10

2
3

DP28

RP158

RP183

CP6

CP101

R
UP2
TL431AC

DP2

+12VP
CP146

CP100

CP5

RP26

DP34

I/N

RP27

RP25

TP2

RP157

RP28

RP181

+12VP

DP15
9

RP38

DP18
-12VF

RP180
UP5
UC3845

RP49
CP14

G3
G2

Located at S board

EPO
CNS5
1
2
3
4
5
6

VCC
G'
NC

RJ12

(a) The input of AC auxiliary power circuit is from AC input.


(b) Battery winding of TP2 is used to provide input voltage to DC auxiliary power
circuit once battery pack is not connected.
(c) If EPO is active (NC is released) through RJ12, then AC auxiliary power circuit is
disabled.

48

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(6) DC Auxiliary Power Circuit
Located at P board
FUP1

B+ DP14

NTCP2

RP23

RP163

CNP14
CON(2.5)

UP10

K-ON

QP17

1
2

G1

BATTERY

ON_A
ON_B

RP162

ON_B
RP155

ON_A

RP24
CP82
TP1
1

RP160
DP8
ZDP1
18V

CP8

2
1

8
+12VS
RP132

CP28

VREF

OUT

RT/CT

CP102
5

DAUX

QP21

RP21

ISEN
UP3
UC3845

OUT

UP6
LM317

DP4

11
S

-12VS

3
G3

Vin

+Vout

QP12

+12VF
2
RP39

CP18

RP47

DP7
RP79

RP46

DP3

CP7
CP17

D
G

RP171

3
RP131

R
UP37
TL431

UP13

1
2

RP170

HSP1
45KHz

IN

UP1
LM7912CT

10

COMP

RP177

2
-12V

DP29

RP19
CP27

VFB

DP16

DP32
9

12

UP12

G1
CP16

RP145

RP182

VCC

CP9
RP175

CP4

CP88

CP87

RP2
+12VB

CP86

ADJ

CP79

CP29

GND

B1

+12VS

DP12

RP1

CP1

RP30

4
5

DP1

GND

RP154

ON_B

+12VB

DP31
7

2
3

DP27

CP13
DP17

CP11

-12VF

RP38

RP179

G1

G1

G3

G1

Located at S board
5VS
RS164
RS139

K-ON

CS26

KEY_ON
(4)

DAUX_BAT
(31)

RS13

DAUX

G1

(a) B+ is the source from AC auxiliary power circuit


(b) MCU detects the on key through KEY_ON (4)
(c) If DAUX_BAT (31) is high during battery mode, DC auxiliary power will be off
Refer to AC Auxiliary Power Circuit for B+ and B1 signals

49

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(7) Auxiliary Power Failure Detection
Located at P board
+12VB
+12VS
RP31
RP33
DP24
ZDP3

9V
G1

RP37
QP1

+12VP

G1
+12VS

RP32
AUX-F
RP35
DP25
ZDP4

9V
G1

RP36

RP34

QP3
QP2
G1
G1

Located at S board

5VS
RS10

AUX-F

RS138

(61)
AUX_Fail

(a) +12VP is from AC auxiliary power and +12VB is from DC auxiliary power.
During AC mode, +12VP and +12VB should be both alive. If one of them is fail,
MCU can detect auxiliary power failure through AUX_Fail (Low active).

50

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(8) Battery Voltage Detection
Located at P board

B+

RP7

RP8

RP9

RP10

RP11

RP12

BATTBATT+

Located at S board
CS6
RS27
BATTBATT+

RS242

RS243

10

RS23

CS3

RS31

US16C
TL084

Vbat

(87)
CS28

RS15

G1
G1

(a) MCU detect the voltage through Vbat (87)

51

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(9) Battery Pack Detection
Located at P board

INTBNO

D+
CP3
CNP7

1
2
RP22

D-

G1

Located at S board

5VS
DS20

RS20
RS137

INTBNO

INTB_NO

(89)
INTB_NO

CS31
DS21
G1
G1

(a) MCU detects the internal battery pack through A/D INTB_NO (89).

52

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(10) Auxiliary Power For 5V
Located at S board
+12VF
RS155
QS19
+5VF
RS150
RS153
CS7
1

Vin

Vout

3
R
CS107

US6
TL431 0.5%

CS136

RS154

CS37

VLED
GND

+12VS

US38

G1

RS151

CS8

G3

QS23
CS106
+12VS

5VS
RS80 RS81

RS82

+12VS

RS160

QS22

5V8

CS33

RS158

CS35

CS12

US10

CS94
A

CS105

G1

(a)
(b)
(c)
(d)

US26
RS83

RS161

G1

RS159

G1

5VS is the power source for MCU


VLED is the power source for LCD and LEDs
5V8 is the power source for blue backlight of LCD
+5VF is the power source for USB MCU and Minislot.

53

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(11) LCD And LED Driver
Located at S board
BKLIT
VLED

CS85
VLED

16

11
10

SRCLK
SRCLR

12
13

RCLK
E

16

CS88

G1

15
1
2
3
4
5
6
7

LED0
LED1
LED2
LED3
LED4
LED5
LED6
LED7

LED_STB
(64)

O0
O1
O2
O3
O4
O5
O6
O7

G1

Q7

VCC

VCC

14

SER

G1

SER
SRCLK
SRCLR
RCLK
E

G1
G1
CS84

16

VLED

15
1
2
3
4
5
6
7

Q7

G1
SER
SRCLK
SRCLR
RCLK
E

O0
O1
O2
O3
O4
O5
O6
O7

GND

LCD0
LCD1
LCD2
LCD3
LCD4
LCD5
LCD6
LCD7

VCC

US23
74HC595
LCD0
LCD1
LCD2
LCD3
LCD4
LCD5
LCD6
LCD7

14

RTCDO (7)

11
10

RTCSCK (8)
LCD_STB (63)

12
13
G1

LCD7
LCD5
LCD3
LCD1
(20) LCDE
(21) LCDRS

CS87
G1

LCD7

14
11
10

RS62
QS6

CS21
RS201
G1
RS128

ENT

KEY_ENT

G1

(97)
KEY_ENT

RS143

(64)
LED_STB

12
13

ESC

RS105

KEY_ESC

CS76

KEY_ESC (98)

RS142
CS65

G1
CS93

CS90

G1
G1
CNS8
LED0
LED2
LED4
LED6
LED8
LED10
LED12
DOWN
ENT
BKLIT

34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2

LCD5
LCD3
LCD1
LCDE
LCDRS
CS67

CS66

(62)
LCD_BKLIT

RS70

(7)
RTCDO
(8)
RTCSCK

CS89

(100)
KEY_DOWN

CS91

GND

Q7

DOWN
G1

US25
74HC595

O0
O1
O2
O3
O4
O5
O6
O7

GND

15
1
2
3
4
5
6
7

KEY_DOWN

RS35

G1
G1

US24
74HC595
LED8
LED9
LED10
LED11
LED12

CS86

VLED
CS68

33
31
29
27
25
23
21
19
17
15
13
11
9
7
5
3
1

G1
RS36
UP
TO DISPLAY
5VS
LED1
LED3
LED5
RS237
LED7
LED9
LED11
TEMP
CS116
UP
ESC
G1
OFF
LCD6
LCD4
LCD2
LCD0

KEY_UP
RS71 (99) OFF

CS71
CS73

KEY_OFF

(5)
KEY_OFF

CS23
G1

(88)

LCD6
LCD4
LCD2
LCD0
RS205

G1

G1
RS37

RS72

G1

5V8

CS70

CS69

KEY_UP
CS22

VLED

CS72
RS206

-12VS

(61)
G1

G1

(a) MCU detects the ambient temperature through TEMP (88). The thermal sensor is
located on the LED board at the front panel.
(b) LCD_BKLIT (62) can adjust the intensity of LCD backlight by PWM control

54

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(12) Watchdog For System MCU
Located at S board
5VS
8

CS9
G1

5VS

RS7
2
5
SYS_RDY

CVolt

RS4
TO US36-P4

3
5VS

THR

RS1
CS27

CS14

CS11

G1
RS6

US3
TLC555C
RS14

G1

G1

QS14

JS6
1
2

Q
DIS

(29)
SYS_RDY

TRIG
GND

VCC

5VS

RS63

QS12
DS5
G1
G1

(a) SYS_RDY (29) will send out pulse to reset CS27. And then CS27 will be charged
again by 5V through RS1. TO US36-P4 will keep high level. If SYS_RDY (29)
doesnt send out pulse for a specific period (for example: MCU is crash) then TO
US36-P4 will be low.
(b) Test JUMP:
JPS6: If JPS6 is shorted, then TO US36-P4 will be low or TO US36-P4 will
keep high during normal operation.

55

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(13) Communication Circuit for RS232 & USB
Switching between RS232 and USB port
Located at S board
5VS
D_RS232

RS182
US27C
C
IN

OUT

2
RS232_RX

RXD

13
1

CD4066B
RS177

(59)
RS232_RX

6
8

(60)
RS232_TX
RS232_TX

US27A
RS181

C
IN

OUT

TXD

CD4066B
US19A

US27D
QS25

12
11

US27B
5
4

B2

RS178

G1

C
IN

OUT

C
IN
CD4066B

OUT

10

B1

MM74HC14

CD4066B

Located at V board
+12VF
RV88

5VS

VBUS

UV24

D_RS232

RV85

RV86
QV11
RV87
G1
G3

(a) If D_RS232=high, MCU (RS232_RX, RS232_TX) will communicate with USB


port (B1, B2).
If D_RS232=low, MCU (RS232_RX, RS232_TX) will communicate with RS232
port (RXD, TXD).
(b) VBUS is voltage of USB-P1 from computer. USB port has the higher priority than
RS232 port

56

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Communication for USB port
Located at V board
+5VF
CV42

+5VF

G3

CV8
5VS

CV1

G3

XTALV1

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

UV3

8
7

1
2

RV16

+5VF
CV7

5
G3
CV3

RV5

G3

G3

5VS

G1
+5VF

UV5

+5VF

7
8

RV6
6

5VS

RV4

RV27
5

B2

G3

CV10

UV7
CV6

B1

CV9
G3

+5VF
RV2

CV11

VDD
OSCOUT
OSCIN
VSS
PC2/USBOE
PC1/TDO
PC0/RDI
RESET
NC
PB7/AIN7/IT8 (10mA)
PB6/AIN6/IT7 (10mA)
Vpp/TEST
PB5/AIN5/IT6 (10mA)
PB4/AIN4/IT5 (10mA)
PB3/AIN3 (10mA)
PB2/AIN2 (10mA)
PB1/AIN1 (10mA)

G3
VDDA
USBVCC
USBDM
USBDP
VSSA
PA0/CPUCLK
(25mA) PA1/SDA
NC
NC
NC
(25mA) PA2/SCL
PA3/EXTCLK
PA4/ICAP1/IT1
PA5/ICAP2/IT2
PA6/OCMP1/IT3
PA7/OCMP2/IT4
(10mA) PB0/AIN0

RV17

34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18

VBUS
G3

RV34

G3

G3 G3
CV23 CV29

G
RV89

CV12

RV26

G3

G3
QV12
RV32
CV46

CV44

C1- SHDN
C1+ GND
C2- VOUT
C2+ VCC

G3

G3

8
7
6
5

RV9

CNV2

G3
UV2
1
2
3
4

RV80

CV2
VBUS

G3

CV43

CNV4
1
2
3
4

G3

CV17

+5VF
+5VF

1
3
5
7
9

2
4
6
8
10

HEADER 5X2

RV10
DV5

G1

QV5
S

G3
DD+

D
RV25

CV15

+5VF

G3
G3

RV28 RV8

CV45
QV1
G3

(a) UV2 is boost supply for self-programming purpose


(b) CNV2 is used to USB chip programming

57

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Communication for RS232
Located at S board
US19CTO TXD
6

TXD

MM74HC14

Located at C board
+12VF
+12VF
+12VF
CC4
RC21

RC19

G3

RC11
3

8
7

UC7A G3
LM393

RX

UC5

2
D

CC5

RC24

G3
4

TO TXD

CNS3-P2

QC3

RC22

CC6

+12VF
8

5VS

RC10
CC3 5VS

G3

RC12
-12VF
RC18

G3

RXD

7
8

G1
UC6

RC20 5

TX

RC23

DC6

3
G3

RC13

G1

DC7

5VS

CC9

G3

D
QC4

G
S RC25

-12VF

QC5

CNS3-P6

CC8

CC7

Located at S board

RS232
+12VF
CNS3

RS57

RS149

G3

TX
CNS3-P2
CNS3-P6

5
9
4
8
3
7
2
6
1

(a) CNS3-P6 is used for plug & play function


(b) RX and TX signals are also connected to power module for firmware upgrade
purpose
Refer to Power Module for RX and TX signals
58

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(14) Communication Circuit for Minislot
Communication Circuit
Located at S board
US19B
(58)
DATA_TX
DATA_TX

5VS
(57)
DATA_RX

DATA_RX

B3

RS127
RS133

B4

CS78

G1

Located at V board
5VS
RV12

CV5

UV4

G3
RV42

8
7

RV3

B3

+12VF

+12VF

RV82

5
4

-12VF
5VS
CV4

1
UV6

RV21

3
D

+12VF

RV7
G3

G1

B4

+5VF

CNV3

7
8

G1

S
QV6

G3

RV41

INPUT 1
INPUT 2
G1
INPUT 3

1
3
5
7
9
11
13
15
17
19
21
23
25

2
4
6
8
10
12
14
16
18
20
22
24
26

CV14
CV33 G3

G3

INPUT 4
RSD
INPUT 5

To Minislot

59

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Dry Contact Circuit
Located at S board
US36
8

G1

GND COM

7
6
5
4
3
2
1

(38) DRY A
(37) DRY B
(30) DRY C

7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

Bat fault

+12VS
9
10
11
12
13
14
15
16

ULN2003A

(95)

BAT-F

RS180
RS44

QS11

G1

Dry Contact

on line/backup
low-batt
load protect
On bypass

G1 CNS4-P5
5VS
CNS4-P3

BYPL
DRY D

(103)

BYPL

RS73
QS18

RS87

(52)
RMTSD

RS146

RS236

CNS4

5
9
4
8
3
7
2
6
1

RSD

G1

Located at C board
CNS4-P3

RC16

RSD

RC17

CC2
G1
CNS4-P5
UC4

Located at V board
+12VS

+12VS

load protect
RV49
INPUT 1

QV19
on line/backup

RV45

INPUT 2

+12VS

INPUT 4

Bat fault
RV46
INPUT 3

RV29
RV81

QV10

+12VS

RV39
RV79

RV30
QV13

RV40

RV61

On Bypass

+12VS
RV14

RV11

RV20

low-batt
QV20
INPUT 5

RV47

QV18

RV78

(a) INPUT 1: Load protected


INPUT 2: Operation on battery
INPUT 3: Battery fault
INPUT 4: Operation on automatic-bypass
INPUT 5: Low battery
OUTPUT (RSD): Remote power off

60

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(15) Communication Circuit For Dry Contact
Located at S board

Dry Contact
US36
8

G1

GND COM

7
6
5
4
3
2
1

(38) DRY A
(37) DRY B
(30) DRY C

7B
6B
5B
4B
3B
2B
1B

CNS4-P5
CNS4-P9
CNS4-P4
CNS4-P8
CNS4-P3
CNS4-P7

+12VS
9
10
11
12
13
14
15
16

7C
6C
5C
4C
3C
2C
1C

CNS4-P6
on line/backup
low-batt
load protect
On bypass

ULN2003A

DRY D

CNS4
DB9

5VS
BYPL

(103)

5
9
4
8
3
7
2
6
1

BYPL
RS73

QS18

RS87

(52)
RMTSD

RS146

RS236

RSD

G1

Located at C board
CNS4-P3

RC16

RSD

RC17

CC2
G1
CNS4-P5
UC4

+12VS

RLC10
+12VS

CNS4-P9
NO

NC

CNS4-P4

RLC11
NO

CNS4-P8
NC

DC3

DC1

+12VS

+12VS DC4

RLC12

RLC13
NO

CNS4-P7
NO

NC

DC2

low-batt

COM

load protect

COM

on line/backup

CNS4-P6
NC

DC5
COM

On bypass

COM
CNS4-P5

(a) CNS4-P3: Remote power off


CNS4-P5: Common
CNS4-P7: Battery low
CNS4-P9: On battery

CNS4-P4: On utility
CNS4-P6: On bypass
CNS4-P8: System (load) protected / UPS On

61

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(16) Communication For System and Power module
Part 1
Located at V board
+12VF
RV55
RV38

5VS

UV20

B6

RV54

SYNC_BUS
G3

3
G3

1
2

CNV6

QV9
VS

RV52

VS
5VS

RV36

UV18

B13

SYNC_BUS

QV3
ZDV4

CV19

RV48

VS

QV2

CV26

RV33

5VS

UV14

ZDV2

4
CV13

RV58

B9

CV16

3
RV50

G3
RV64

+12VF
UV21

B14

G3

G1

RV22

+12VF
CV27

2
VS
+12VF

RV59
G3

8
7

UV10

CV30

RV35

UV16

ZDV3
CV20

3
RV53

RV60
4

G3
G3

UV11

+12VF

CV37

7
8

G1

RV66

+12VF

RV24

B12

G1

CV32

UV17

RV63

RV19
CV22

1
2

G1

TOINV
QV4

CV18
4

5
5VS

B18

TO BYP

CV21

ZDV6

B11
B17

RV18

RV51

VS
5VS

RV62

1
2

CV31
INT_DATA

UV15

G1
QV8

CV38
2

B10

Located at S board
US20C
US19B
5

TOINV_O
(50)

B11

(58)
DATA_TX DATA_TX

RS89

5VS

5VS

RS116

TOINV_I
(106)

B12

(57)
DATA_RX

DATA_RX

B3

US15B-P3

US20B
4

RS127

B6

RS133

CS51

B4

CS78

G1

B9

To US36-P4

RS122

G1

RS94

QS20

US20F
SYNC_O
(27)

B13

13

INT_TX
(3)

G1

12

B17

US20D
5VS
SYNC_I
(26)

RS90

5VS

RS119

B14

INT_RX
(2)

RS91
RS120

B18
CS54

CS52
G1

G1

(a) If System MCU is operating normally, then VS is on. VS is the power source for
communication circuit: US15B-P3 (B9), TOINV_O (B11), SYNC_O (B13) and
INT_TX (B17). If System MCU is not operating normally (for example: MCU is
crash), then VS is off to prevent the communication bus is locked
62

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(e) TOBYP and TOINV signals are used to synchronize bypass mode and inverter
mode transfer
(f) SYNC_BUS signal is used synchronize the inverter and bypass voltage
(g) INT_DATA signal is used to transfer information between Power MCU and
System MCU.
Refer to Watchdog for System Module MCU for TO US36-P4 signal.
Refer to Bypass SCR driver for US15B-P3 signal

63

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
Part 2
Located at V board
5VS

RV1

UV1

ON

RV31

+12VF

ON1
RV71

5VS
4

ID1_RDY
CV39

UV22

RV72

+12VF

1
RV70

BYPOK
4

UV23

CV40 2

DV7

DV8

G3

ID1RDY
G1

+12VF

BYP_OK

RV77

+12VF
B8
G1

UV13

+12VF

RV43

TOMBYP(B)
RV13

TOMBYP(N)

TOMBYP
RV15

B7

UV12

QV14

RV74

QV15

RV37

5VS

B5

G3

RV83

RV84

RV75

RV76

QV17

QV16

G1
RV73

TOMBYP

RV44

BYP-F
4

UV19

3
G3

G3

Located at S board
5VS

ON

US36

QS2
G1

RS104

RS39
(34)
POWER_ON

RS216

ID1_RDY
(54)

CS43

TO US36-P4

G1
5VS

8
7
6
5
4
3
2
1

G1

GND COM
7B
6B
5B
4B
3B
2B
1B

7C
6C
5C
4C
3C
2C
1C

+12VS
9
10
11
12
13
14
15
16

BYP_OK

ULN2003A
RS86

TOMBYP_B
(104)

RS115

5VS
B8

CS50

TOMBYP_N
(35)

RS144

TOMBYP_N RS145

CS55
G1

B5

B7
BYP-Fail
(22)

RS123
QS21
RS113

G1

G1

(a) If POWER_ON (34)=high, the auxiliary power of power module is powered on.
ON1 is connected to power module.
(b) If ID1_RDY (54)=Low, the Power MCU is operating normally
(c) BYPOK is connected to power module to inform that System MCU is operating
normally
(d) TOMBYP(B) is connected to the bypass auxiliary winding of manual bypass
switch. MCU detects that manual bypass switch is at bypass position by
TOMBYP_B (104) (low active)
(e) TOMBYP(N) is connected to the normal auxiliary winding of manual bypass
switch. MCU detects that manual bypass switch is at normal position by
TOMBYP_N (35) (low active)
(f) BYP-F is connected to power module. If utility is fail, BYP-Fail (22) will be high.
(g) TOMBYP is connected to power module to detect the switch of manual bypass
switch.
Refer to Watchdog for System Module MCU for TO US36-P4 signal.
64

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(17) EXB Detection Circuit (RJ45) And EPO Circuit (RJ12)
Located at S Board
RS211

EXTBNO

EXTB_NO
(90)

RS210

EMPO1

EPO
(108)
CNS9
CNS5

EXTBNO
DS6

RS79

DS19

1
2
3
4
5
6
7
8

CS44
CNS9-P5
CNS9-P6
CNS9-P7
CNS9-P8

5VS
G1

1
2
3
4
5
6

VCC

CNS5-P2

G'
NC

CNS5-P4
CNS5-P5

EPO

EXT. BAT. DET.

Located at C board
RC8
+12VF
(1)
BTEST

UC2

RC2

CNS9-P5
CNS9-P6
CNS9-P7
CNS9-P8

5VS
2

QC2

QC1

RC3

D
G1

G3
2

RC6

5VS

RC4

S
RC7

UC1
RC1
RC14

EMPO1
4
CC1
G1

UC3

1
2

G3
VCC

CNS5-P2

GND
NC

CNS5-P4
CNS5-P5

RC15

(a) MCU detects the number of External battery cabinet by EXTB_NO (90)
(b) Normal Close setup for EPO (RJ12): Short CNS5-P5 (NC) to CNS5-P4 (G). If
remove the short pin, EPO will be active
(c) MCU detects EPO signal by EPO (108)
(d) CNS9-P8 & CNS9-P7 is used to trip the circuit breaker (if the breaker has external
trip function) on EXB when EPO is active.
(e) CNS9-P5 & CNS9-P6 is used to disable the CLA during performing battery test

65

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
(18) Other Detection Circuit
Located at S board

5VS
RS167
CNS7
JS5
1
2

REPAIR
(96)

BKGD
BKGD(23)

BKGD

CS118

1
3
5

2
4
6

G1
/RES

(42)
/RES

5VS

(BDM)
G1
CNS6
#22

DS22

+12VS

CNS10
1

OL1

DS23
+12VS

#22
OUTLET1

(110) CPU-P110

QS16

G1
RS147

OL2

#22
OUTLET2

RS85

CNS11

QS17
RS136

(111) CPU-P111

G1

RS148

OUTLET2

OUTLET1

(a) If JS5 is shorted, UPS will go into test mode


(b) CNS6, CNS10 and CNS11 are connected to outlet board for outlet control
(c) CNS7 is used for MCU programming by BDM

66

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2. Troubleshooting
2.1 Internal Fault
2.1.1 Alarm 34: CHARGER FAULT
START

Disconnect Battery
And Check Charger Voltage
200Vdc<Vbat<214Vdc
?
N

Check Voltage at
UB23-P7 On B Board
0V?

Charger Detection Circuit


On B Board Fail
Replace B board

N
END

Check Rectifier
And PFC Circuit
(refer to flow chart for
alarm 305)

N
Check Bus Voltage
Around 375V/-375V?

Charger Detection Circuit


On M Board Fail
Replace M board

END
Charger Circuit On B
Board Fail
Replace B Board

END

67

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.2 Alarm 193: FAN FAULT
START

Fans At Front And Rear Of


Power Module are rolling?

Fan Fail
Replace Fan Which Is Not
Rolling

Fan Fail Detection Circuit


On B Board Fail
Replace B Board

Restart UPS and No


AN FAULT ALARM

Y
END

END

68

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.3 Alarm 004: UPS TEMPERATURE FAULT
START

Remove Power
Module and
No Output At Bypass
Mode?

OTP At System Frame

OTP
At Power Module

Output Load=0 And


Output Is Recovered?

Check Wiring
CNG4-P11 ~CNG4-P8 ~
CNP4-P8 ~ CNP2-P10~
CNS2-P10
OK?

Temperature Detection
Circuit On S Board Fail
Replace S Board

END
Replace Fan

END

Turn On UPS
And Check Fan Is Rolling
Or Not?

Turn On UPS
Output Load=0
No OTP Alarm

Check Wiring
CNA1-P13~CNA1-P22
~CNB1-P22 ~ CNB3-P10 ~
CNM4-P9
OK?

Check the Ambient


T < 40 C

Flat Cable Fail


Change Flat Cable

END

END

1. Check Path of Air Flow


And Clean Dust Or Barrier
2. Check the Ambient
T<40 C

END

Temperature Detection
Circuit On M Board Fail
Replace M Board

END

Flat Cable Fail


Change Flat Cable

END

69

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.4 Alarm 701: INVERT FUSE BLOWN
START

Check FUA4
Is Open ?

Check Wiring
CNA1-P11~CNB1-P11
~CNB2-P15~CNM2~P16
OK?

Flat Cable Fail


Replace Cable

END

Inverter Fuse Open


Detection Circuit On M
Board Fail
Replace M Board

END

Check
QB18/QB19/QB20
and QB22/QB23/QB24
Damaged ?

Inverter Circuit On B
Board Fail
Replace B Board
Replace FUA4

N
Inverter Current Limit
Circuit Fail
Replace M Board
Replace FUA4

Check Inverter
Control Circuit On M Board
TPM1 & TPM2
Ok?

Inverter Control Circuit On


M Board Fail
Replace M Board

Y
END

END

END

70

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.5 Alarm 100: NORM AC FUSE BLOWN
START

Check FUA1 Is Open ?

Check Wiring
CNA1-P25~CNB1-P25
~CNB2-P13~CNM2~P14
OK?

Flat Cable Fail


Replace Cable

END

Flat Cable Fail


Replace Cable

END

Rectifier Fuse Open


Detection Circuit On M
Board Fail
Replace M Board

END

Check Wiring
CNA1-P26~CNB1-P26
~CNB2-P14~CNM2~P13
OK?

Check
QB10/QB11/QB12
And QB14/QB15/QB16
Damaged?

PFC Circuit On B Board


Fail
Replace B Board
Replace FUA1

END

Rectifier SCR Control


Circuit On M Board Fail
Replace M Board

END

N
Check
SCR Driver Signal
On A Board (JPA1-P1 and
JPA2-P1)
OK?

Rectifier Circuit On A
Board Fail
Replace A Board

END

71

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.6 Alarm 30: RECTIFIER FAULT
START

Short JPB1
And Input Voltage=230Vac
Check Bus Voltage Around
300/-300Vdc ?

Remove JPB1
And Turn On UPS Check
Bus Voltage Around
375/-375V?

Check
SCR Driver Signal
On A Board (JPA1-P1 and
JPA2-P1)
OK?

Rectifier SCR Control


Circuit On M Board Fail
Replace M Board

END

Rectifier Circuit On A
Board Fail
Replace A Board

END

Bus Detection Circuit On


M Board Fail
Replace M Board

END

PFC Circuit On B Board


Fail
Replace B Board

END

72

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.7 Alarm 28: DC BUS +/- TOO HIGH/LOW
START

Output Is
Half-Wave Load

Reduce The Load

END

Output Is
Inductive Load (Ex.
Transformer) And Short
JPM4. No Alarm
Again?

DC Offset Compensation
Circuit On M Board Fail
Replace M Board

END

Short JPB1
And Input Voltage=230Vac
Check Bus Voltage Around
300/-300Vdc ?

Check
SCR Driver Signal
On A Board (JPA1-P1 and
JPA2-P1)
OK?

Rectifier Circuit On A
Board Fail
Replace A Board

Remove JPB1
And Turn On UPS Check
Bus Voltage Around
375/-375V?

PFC Circuit On B Board


Fail
Replace B Board

Rectifier SCR Control


Circuit On M Board Fail
Replace M Board

Check Voltage
At UB14-P8
Around 8Vdc?

END

BUS Voltage Detection


Circuit On B Board Fail
Replace B Board

END

BUS Voltage Detection


Circuit On B Board Fail
Replace B Board

END

Check Voltage
At UB14-P14
Around 8Vdc?

Y
END
BUS Voltage Detection
Circuit On M Board Fail
Replace M Board

END

73

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.8 Alarm 31: INVERTER FAULT
START

Check Bus Voltage


Around 375/-375Vdc?

Check Rectifier And PFC


Circuit
(Refer to Flow Chart For
Alarm 305)

Turn On UPS and


Check Voltage On CA25
Preset Voltage
(ex. 230Vac) ?

Check Wiring
CNA1-P8~ CNB1-P8~
CNB2-8~ CNM2-P7
Ok?

Flat Cable Fail


Replace Flat Cable

Inverter Voltage Detection


Circuit On M Board Fail
Replace M Board

END

END

Check Inverter
Driver Signal On M Board
(TPM1 & TPM2)
Ok?

Inverter Control Circuit On


M Board Fail
Replace M Board

END

Inverter Circuit On B
Board Fail
Replace B Board

END

74

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.9 Alarm 191: BATTERY FAULT
START

Switch On
Top Chassis is showed
Connected ?

Battery Is Not Connected


Turn On The Switch

END

Battery End Of Its Life


Replace With New Battery
Tray

END

Fuse Is Broken
Replace FUB3 & FUB4

END

Measure The
Battery Voltage Through
EXB Connector
>150Vdc

Check FUB3 & FUB4 are


Open ?

Battery Voltage Detection


Circuit On M Board Fail
Replace M Board

END

75

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.10 Alarm 36: AUTO BYPASS FAULT
START

Check SCR On G Board Is


Shorted ?

Bypass SCR Damaged


Replace G Board

END

Flat Cable Fail


Change Flat Cable

END

Check Wiring
CNG4-P6 ~CNP4-P6 ~
CNP2-P4 ~CNS2-P4
Ok?

Bypass SCR Short Short


Detection On S Board Fail
Replace S Board

END

76

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.11 Alarm 00A: DC POWER SUP FAULT
START

Check Voltage
At CP86 On P Board
Around +12Vdc ?

Battery Aux Power Fail


Replace P Board

END

AC Aux Power Fail


Replace P Board

END

Auxiliary Power Fail


Detection Circuit On S
Board Fail
Replace S Board

END

Check Voltage
At CP90 On P Board
Around +12Vdc ?

Check
QP3 C-E on P Board
0V?

Y
Auxiliary Power Fail
Detection Circuit On P
Board Fail
Replace P Board

END

77

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.12 Alarm 63: INTERNAL COM FAULT
START

Check Wiring
CND1-P3 ~ CNM5-P3
Ok?

Flat Cable Fail


Replace Flat Cable

END

Flat Cable Fail


Replace Flat Cable

END

Check Wiring
CNE1-P3 ~ CNV5-P3
Ok?

Communication Circuit On
M Board Or S/V Board
Fail
Replace M Board Or
Replace S/V Board

END

78

Powerware 9135 HARDWARE INTRODUCTION


AND TROUBLESHOOTING
2.1.13 Alarm 006: COM FAULT BETW UPS
START

Check Wiring
DB15-P7 Of Two UPS
Ok?

Parallel Cables Are Open


Or PCB On ModularEasy
Fail
Replace Parallel Cable or
PCB On Modular Easy

END

Flat Cable Fail


Replace Flat Cable

END

Flat Cable Fail


Replace Flat Cable

END

Check Wiring
CND1-P5~ CNM5-P5
Ok?

Check Wiring
CNE1-P5~ CNV5-P5
Ok?

Y
Communication Circuit On
M Board Or S/V Board
Fail
Replace M Board Or
Replace S/V Board

END

79