Sie sind auf Seite 1von 5

1

1811P01

811

QAC...
FW-T1G

Outside Sensors

Passive sensors for acquiring the outside temperature and to a lesser


degree solar radiation, the wind effect and the temperature of the wall.
Range of use -40/50+70 C / 595 % r. F.
Use
The QAC outside sensors are for use in heating, ventilation and air conditioning
plants as:
Reference sensors for weather-compensated control
Measuring sensors, e.g. for optimization, measured value indication, or for connection to a building automation and control system
Type summary
Type reference Sensing element Range of use

Time constant

Approval

QAC22

LG-Ni 1000

50...+70 C

ca. 14 min

QAC32

NTC 575
(linearized)

50...+70 C

ca. 12 min

QAC2010

Pt 100

50...+70 C

ca. 14 min

UL, class 2

QAC2012

Pt 1000

50...+70 C

ca. 14 min

UL, class 2

QAC2030

NTC10k

40...+70 C

ca. 14 min

UL, class 2

FW-T1G

T1 (PTC)

50...+70 C

ca. 14 min

Ordering and delivery


When ordering, please give name and type reference, e.g.:
Outside sensor QAC22.

CE1N1811E
2014-07-30

Building Technologies

Equipment combinations
The outside sensors are suited for use with all types of controllers capable of acquiring
and handling the sensors measured value.
Function
The outside sensor acquires the outside temperature and to a lesser degree solar
radiation, the wind effect and the temperature of the wall. The sensing element
changes its resistance value as a function of the temperature.
Characteristic:

Accuracy:

R []

LG-Ni 1000

[K]
1400

2.0

1200

1.0

1000

0.0

800

1.0

600
50 40 30 20 10

10

[C]

20 30 40 50 60 70 80

1811D02

1811D01

2.0
50 40 30 20 10

R []

NTC 575

10 20 30 40 50 60 70 80 [C]

[K]
1811D03

700

3.0

1811D04

Sensing elements

2.0

650

1.0

600

0.0
550

1.0
500

2.0

450
50 40 30 20 10

10

20 30 40 50 60 70 80

[C]

3.0
50 40 30 20 10

10 20 30 40 50 60 70 80

10 20 30 40 50 60 70 80

10 20 30 40 50 60 70 80

[C]

140

120

[K]
1811D06

1811D05

R []

Pt 100 (class B)

0.8
0.4
0.0

100

0.4

80

0.8
60
50 40 30 20 10

10

20 30 40 50 60 70

80 [C]

50 40 30 20 10

[C]

1400

1200

[K]
1811D06

1811D07

R []

Pt 1000 (class B)

0.8
0.4
0.0

1000

0.4

800

0.8
600
50 40 30 20 10

10

20 30 40 50 60 70

80 [C]

50 40 30 20 10

[C]

2/5
Siemens
Building Technologies

Outside sensors QAC...

CE1N1811E
2014-07-30

R []

[K]
1811D09

1000000

100000

10000

1000
-40 -30 -20 -10

10 20 30 40 50 60 70 80

[C]

0 10 20 30 40 50 60 70 80

[C]

R []
1819D01

3200
3000

[K]
5.0
4.0

2800

3.0

2600

2.0

2400

1.0

2200

0.0
1.0

2000

2.0

1800

3.0
4.0

1600
1400
40 30 20 10

1819D02

T1 (PTC)

Legend

1.20
1.00
0.80
0.60
0.40
0.20
0.00
-0.20
-0.40
-0.60
-0.80
-1.00
-1.20
-40 -30 -20 -10

1811D08

NTC 10k

10

20 30 40 50 60 70

80 [C]

5.0
40 30 20 10

10 20 30 40 50 60 70 80 [C]

Resistance in Ohm
Temperature in degrees Celsius
Temperature differential in Kelvin

Mechanical design
The sensor has a plastic housing with a removable cover.
The connection terminals can be accessed after removal of the cover.
Cable entry is either from the rear (concealed wiring) or from below (surface-run wires).
A cable entry gland can be screwed into the bottom of the housing.
Engineering notes
The permissible cable lengths depend on the type of controller with which the sensor is
used. They are specified in the Data Sheet of the relevant controller.
Mounting notes
Depending on use, the outside sensor must be located as follows:
Mounting location

For control:
On the wall of the house or building that has the windows of the occupied rooms, but
the sensor must not be exposed to the morning sun. In case of doubt, it should be
mounted on the wall facing north or north-west
For optimization:
Always on the coldest wall of the house or building (normally the wall facing north).
The sensor must never be exposed to the morning sun

Mounting height

Preferably in the middle of the house or building or heating zone, but at least 2.5 m
above the ground.
The sensor must not be fitted at the following locations:
Above windows, doors, air extracts or other heat sources
Below balconies or the eave of the roof
To prevent measuring errors due to air circulation, the cable conduit at the sensor
should be sealed.
The sensor may not be painted over.
Mounting Instructions are printed on the packaging.

3/5
Siemens
Building Technologies

Outside sensors QAC...

CE1N1811E
2014-07-30

Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Functional data

Degree of protection

Electrical connections

Environmental conditions

Directives and Standards

Environmental compatibility

Range of use

refer to "Type summary"

Sensing element

refer to "Type summary"

Time constant

refer to "Type summary"

Accuracy

refer to "Function"

Type of measurement and output

passive

Protection class

III according to EN 60730

Protection degree of housing

IP54 according to EN 60529

Screw terminals for

2 x 1.5 mm2 or 1 x 2.5 mm2

Cable entry for

cable gland (e.g. M 16 x 1.5)

Perm. cable length

refer to "Engineering notes"

Operation
Climatic conditions
Temperature
Humidity

40...+ 70 C
0 . . . 1 0 0 % r. h.

Storage / transport to
Climatic conditions
Temperature
Humidity
Mechanical conditions

IEC 721-3-2
class 2K3
25...+ 65 C
< 95 % r. h.
class 2M2

Product standard

EN 60730-1
Automatic electrical controls for household and similar use

UL

UL873 http://ul.com/database

The product environmental declaration CE1E1701*) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental

Materials and colors

Weight

benefit, disposal).
Base

plastic (ASA)

Cover

plastic (ASA), RAL9003

Packaging

cardboard

Incl. packaging

approx. 0.093 kg

*) The documents can be downloaded from http://siemens.com/bt/download.

1811G01

Internal diagram

The internal diagram is identical for all types of outside sensors covered by this Data
Sheet.
The connecting wires are interchangeable.

4/5
Siemens
Building Technologies

Outside sensors QAC...

CE1N1811E
2014-07-30

Dimensions

20,7

92

5,5

5,5

16

50
25

24,5

49,5

1811M03

80

Drilling plan
Dimension in mm

5/5

2004 2014 Siemens Switzerland Ltd

Siemens
Building Technologies

Outside sensors QAC...

Subject to change
CE1N1811E
2014-07-30