BEL/LAB/TT/15_1/2010
BEL/LAB/TT/15_1/2010
REPORT
on the tests of
Andrzej Pawlowski
-1-
Ordering party:
Date of tests:
Type of tests:
6 pages
-2-
Diameter (mm)
A
26
26,5
900
300
Visual examination
The clamps were found to have been made correctly; the surfaces of the products were
smooth, without sharp edges.
3.2.
With proper instruments, length and angle measurements were taken. Actual dimensions
were verified against the dimensions given in structural drawings.
No deviations above the limits provided in structural drawings were found.
3.3. Electrical type tests
3.3.1.
The corona and radio influence voltage (RIV) tests have been carried out according to
Nema CC1: Electric Power Connection for Substations.
An acceptance criteria are based on ESKOM Technical Specification: Distribution
Specification Part 7, Substation Connectors, No. 34-1974, Rev. B, Published date:
July 2010.
-3-
The difference in RIV levels between the normal operating gradient and a 15 %
higher gradient was less than 1 dB.
The RIV levels at 10 % higher gradient was less than 26 dB.
Voltage of visible Corona 262 kV.
The test were carried out in an independent laboratory Institute of Power Engineering
High Voltage Section in Warsaw. Detail report from the test contains appendix no. 3.
Based on the test results, it is found that the clamps mated with the Centipede
conductor meet the requirements with respect to the corona and radio influence
voltage (RIV) tests.
3.4. Mechanical tests
3.4.1. Measurement of distortion
Three EX-B clamps have been tightened with 54 Nm tightening torque, that is 20% above of
a nominal value - 45 Nm. Then the bolts were loosened The remaining elongation were
measured by using micrometer (see table 5).
Table 5. Elongation after tightening torque.
Sample no.
Clamp 1
Clamp 2
Clamp 3
Tightening
torque
[Nm]
54
Max.
elongation
[%]
0,15
The
elongation
[mm]
0
0
0
The
elongation
[%]
0
0
0
Result
Positive
Positive
Positive
Tightening
torque
[Nm]
The gap
[mm]
Result
49,5
2,7
2,3
2,5
Positive
Positive
Positive
After tests each clamp, screw and thread were inspected. There were no evidence of
mechanical distortion.
20% RTS
4%
RTS
t (s)
Gradual
increase
of the
load
Marking
of the
conducto
r
Gradual
increase
of the
load
60 s
Decrease
of the
load
Requirement for
maximum
breaking
No slipload
at 20 % of
the conductor
strength Centipede
( 12,6
kN)
No. of system
System 1
System 2
Result
No slip and damage at
13 kN
No slip and damage at
13 kN
Based on the test results, it is found that the EX-B clamps mated with the
Centipede conductor meet the requirements with respect to mechanical tests.
4. Conclusions
Following the tests, EX-B clamps SK-09097 mated with the Centipede conductor meet the
requirements of ESKOM Technical Specification: Distribution Specification Part 7,
Substation Connectors, No. 34-1974, Rev. B, Published date: July 2010.
.
APPENDIX No. 1
The drawing of the EX-B clamp (SK09097)
-1-
95
8
N
8xM12 Bolts
84
REVISIONS
C. LEGEND
~
UIU$S OTI[DI $[
SP[(IF I[D
. lI"e .1:
LABEL
On
PIETERMARTIZBURG 3200
www.preformedsa.co.za
SOUTH AFRICA
r;;l CIITICAL
11 1"
or
_Ir:
~
flllMl.
RU[I 10 LAI[SI
1[11$101OFrH[
.. _,
I. _,
.....
EX-B Clamp
EX - B
SK-09097
---~
L-.b==,,~v
PIOC[DUI[
lCALI
_II
..