Beruflich Dokumente
Kultur Dokumente
Document number/version:
SJ-20110104162043-001 / 2011-08-03 (R1.0)
Never install the equipment in the place where there is water vapors or liquid drops. Ensure that
no water drops, metal pieces or any other foreign object fall into the cabinet. Otherwise, short
circuits may occur and damage the equipment. Do not place heavy objects on top of the cabinet.
Unfasten the bolts
anticlockwise.
(1) Use batteries of the same type. Do not use old and new batteries together. (2) Battery packs
are the energy-storing equipment. Never short-circuit them in any way during the operation.
Always use an insulating tool for electrical connections. Make sure that the connecting terminals
and unnecessarily exposed parts are properly insulated.
Locked
(1) The cross-sectional area of cables should match the load. (2) When using cables in nonstandard colors, choose those in black and mark them with heat-shrinkable tubes or insulating
tapes in the corresponding colors to avoid confusion. If the local regulations have different
requirements for the cable colors, follow the local regulations.
Locked
Caution: While installing the rectifier or CSU, remove your figures under the handles
Dampproof
Sunproof
No stacking
N
AC INPUT
Installation hole
Nut
Spring washer
Flat washer
Prerequisites:
Steps:
Expansion bolt
Front
L2
Side
Rear
Left
L3
L4
Double AC Input
(Non-Standard Configuration)
Front
PE
3. Use ties to fix the cables to the cable binding holes inside the
cabinet.
AC INPUT 1
AC INPUT 2
L4
462
600
Steps:
1
PE N
Right
Front
L1 L2 L3
Properly connect the live and neutral cables, and make sure the
neutral cable connected in any case.
2. Lead the cables into the cabinet through sponge strips on top of
the cabinet. Then connect them to the specified breakers or
terminals. The connection sequence should be:
(Unit: mm)
276
OFF!
OFF!
Dust-proof cover plate:
Cables are led through
sponge strips into the
cabinet.
Cabinet dimensions:
1600 mm (Height) x 600 mm (Width) x 400 mm (Depth)
N N
L1 L2 L3
3 Mains
L1 L2 L3
4 Generator
When the system is configured with double AC input (AC INPUT 1 and AC INPUT 2),
The AC INPUT 1 connects to the mains, serving as the active power supply of the system.
The AC INPUT 2 connects to the generator, serving as the standby power supply of the system.
ZTE Corporation
Postcode: 518057
Website: http://ensupport.zte.com.cn
Email: 800@zte.com.cn
Preparation:
Flooding detection
Humidity detection
X15
X24
Battery temperature
sampling 1
Battery temperature
sampling 2
Battery temperature
sampling 3
Battery temperature
sampling 4
Environment
temperature sampling
Output relay 1, 2
X25
Output relay 3, 4
X26
Output relay 5, 6
X27
Color Codes of DC Cables
Working ground cables(GND/+): black
Negative cables (-48V): blue
Output relay 7, 8
Load
BATT2 (-48V)
BATT1 (-48V)
BLVD
F10E
Temperature sensor
Preparation:
Clean the side of
the battery.
X5
RS232
RS485
ZTE Corporation
X19
X20
7
3
6
2
RS485
X20
Interface on BACK
BACK-X15
BATT 2
BACK-X16
X16 X15
Dual-pin plug
BACK board
Postcode: 518057
Website: http://ensupport.zte.com.cn
BATT ST 4
X18
X14
BATT 1
X17
BATT ST 2
X16
BATT ST 1
X15
TEMP
X23
X12
Door ALM
HUM ALM
X24
X26
X11
Door
VCC
RLY Output
RLY Output
CSU Status
1
1
48VP
NO1
NO5
HUM
Normal
1
2
1
1
2
COM1
COM5
COM
GND
2
3
2
2
NC1
NC5
Fault
3
3
3
NO2
NO6
X10
X13
4
4
RLY Input
COM2
COM6
Water ALM
5
5
S1
NC2
NC6
VW
1
6
6
1
S2
+5V
2
2
48VP
X25
X27
AGND
3
3
RLY Output
RLY Output
S3
WT
4
NO7
4
NO3
S4
1
5
COM7 1
COM3
48VP 6
2
2
NC7
NC3
3
3
NO8
NO4
4
4
COM8
COM4
5
5
NC8
NC4
6
6
Email: 800@zte.com.cn
BATT ST 3
TE
Configuration
DC Output Branch
X5
+5V
DC output breakers
BATT +
RS232 serial
communication
Multiplexed
RS485 communication
Independent
RS485 communication
T1
X19
+5V
OFF!
Connect the
reserved plate
Ethernet
interface
T2
DC output breakers
Batt2 cables
BLVD
+5V
LLVD1
OFF!
X23
Connecting Cables:
Batt1 cables
X18
Extractor
Fuse
T3
X17
Grounding busbar in the
equipment room
X16
+5V
Red detection
cables
X14
GND
X13
GND
T4
14
+5V
16
18
X12
A0
20
X11
22
24
Primary
load
Secondary
load
On the CSU
Description
4 branches, supporting alarm
customization
Generating alarms for the CSU faults
RXD
Secondary
load
Interface Nam e
X10
Input relay
TXD
B0
11
A1
B1
Reserved
The X10 interface provides 4 input relays (default state: closed). Users can set the
alarm grades of these input relays through the CSU, which is described in section 13
Setting Attributes of Input Relays.
While using IP/SNMP networking, connect the network cable to the Ethernet
interface of the CSU.
The X24, X25, X26 and X27 interfaces provide 8 output relays together. Each output
relay has two kinds of contacts, normally open (NO) and normally closed (NC). Pay
attention to their differentiation during the cable connection. The output relays (A1 to
A6) support alarm customization, which is described in section 12 Setting Output
Relays of Alarms.
Install 24 battery cells (2 V/cell) onto the battery rack and connect plates between
two adjacent cells. Reserve one plate for later connection (connect this reserved
plate after the battery cables are connected to the system). Use the same
method to install the other battery pack.
On the BACK board are the various signal interfaces (as shown below).
Connect signal cables to the corresponding interfaces according to the
monitoring and remote networking requirements.
GN
D
/4
http://www.zte.com.cn
System Commissioning:
GND
Power
Running
Alarm
OFF!
- 48V
(This image is for reference only. The actual product may differ.)
1. Ensure that all fuses are unplugged from their holders.
2. Ensure that the external AC input breaker of the system and the breakers inside
the cabinet are all off.
3. Referring to the image above, turn the knob of the multimeter to the buzzer scale to
check for short circuit.
Criteria:
Maintenance Suggestion:
QUY button
the LCD displays the main menu interface, which means the CSU
is running properly. Because the load branches are not
connected, the CSU generates the DCBreaker Alm. alarm.
This is normal.
Real Msg
Criteria:
Maintenance Suggestion:
2. Verify that the battery cables are connected properly, and then
reinstall the CSU. (see ZXDU68 T601 (V5.0R01M01) DC Power
System User Guide for further details on status indication and
troubleshooting).
Main Menu Interface
System Commissioning:
Steps:
2# battery
cable
+ -
1# battery
cable
- +
Maintenance Suggestion:
Fault
OFF!
ON
Red
A probe
GND
2. According to the images below, set the Device Addr. of the rectifier.
L1 L2
L3
AC input cable
PE
Turn the knob of the multimeter to the buzzer scale to check whether
short circuit exists between AC input cables. The above image shows
the terminals to be tested. The A-B terminal to be tested include L1-L2,
L1-L3, L2-L3, L1-N, L2-N, L3-N, and N-PE.
BATT 2
Steps:
BATT 1
Steps:
BATT 1
BATT 2
System Commissioning:
To avoid equipment damage caused by cable connection errors, check
electrical connections before system commissioning.
7.2
/4
http://www.zte.com.cn
(2) When rectifiers are not installed according to the slot sequence, it is necessary to re-allocate
addresses for these rectifiers.
For example, when slots SMR 1 and SMR 3 are installed with rectifiers while the slot SMR 2 is not
because it is damaged, to avoid alarm errors, set the addresses of the rectifiers in slots SMR 1 and
SMR 3 to 1 and 2.
Critera
Maintenance Suggestion
Phase v oltage:
L1-N, L2-N, L3-N
Each phase v oltage should range If the AC input phase v oltages are not within this range, the
f rom 80 V to 300 V, and the
rectif iers do not work. Start the generator f or power supply .
three phases should be balanced
each other.
Neutral-to-ground
v oltage:
N-PE
10 V
Item
Voltage of
battery pack 1
Voltage of
battery pack 2
(1) The default value is 1. When a rectifier is installed in the slot SMR 2, change its Device Addr.
into 2, likewise the other rectifiers.
Criteria
The voltage of each
battery pack should
be positive and not
low er than 43.2 V
(this value is for
reference only).
ZTE Corporation
SMR-1#
Real Msg
Real Alm.
Para. Set
Ctrl.
Edit
Ent
Postcode: 518057
Website: http://ensupport.zte.com.cn
Email: 800@zte.com.cn
Password:
0000
Ent
Press
twice
Initial password:
0000
SMR Addr.-1#
02
MAX: 40
MIN: 1
Ent
Save
Press
or
Press
or
System Commissioning:
System Commissioning:
Setting Parameters
The table below describes setting requirements for the basic parameters. Set these
parameters correctly according to the actual use of the equipment. Wrong settings will
affect the CSU management of the system including the batteries and cause alarm errors.
The ZXDU68 T601 (V5.0R01M01) DC Power System User Guide provides more
parameters. Please inquire your engineering supervisor about the necessity to modify these
parameters.
Refer to the ZXDU58/ZXDU68 CSU500 (V1.0) Centralized Supervision Unit Alarm List to check
the default output relays of alarms and modify them based on the actual requirements.
Record the used output relays and the corresponding alarms in the ZXDU58/ZXDU68 CSU500
(V1.0) Centralized Supervision Unit Alarm List and keep this record for the future tracing of
historical data during the CSU maintenance.
Record the modified parameter values in the ZXDU68 T601 (V5.0R01M01) DC Power
System User Guide and keep this record properly for the future tracing of historical
parameters during the CSU maintenance.
Press the keys on the CSU or use the U flash drive to set parameters. (For the operations
of U flash drive, refer to the ZXDU68 T601 (V5.0R01M01) DC Power System User Guide.)
System Para.
Default
Batt.Cap.1 (Ah)
300
Batt.Cap.2 (Ah)
300
Batt.Cap.3 (Ah)
Batt.Cap.4 (Ah)
SMR Qty.
11
Requirem ent
Set this parameter according to the capacity of the installed
batteries. For example, if the battery pack is composed of 24
battery cells (200 AH/cell), the parameter should be set to 200.
Battery Para.
Default
53.5
56.4
0.15
Device Set
System Time
Default
-
Password:
0000
Ent
Select Batt.Cap.1.
Ent
Ent
Grade
Relay
Relay
Critical
Ent
A2
LVD1 Alm.
Grade
No
A1
A2
A3
A4
Ent
Relay
Critical
Esc
A3
Exit
Save
Select A3.
Select Relay.
Select an alarm
(Not all alarms are given in
this image).
MAX: 9900
MIN: 0
Ent
Save
Press
or
Press
or
System Commissioning:
The default state of each input relay is Close, and the default alarm grade
is Mask (All alarms will be masked). Modify the attributes of the input relays
based on the actual requirements.
Para.Set
System Para.
Batt.Para.
SMR Para.
Alm.Attr.
In-Relay Attr.
SNMP Para.
Para.Set
System Para.
Batt.Para.
SMR Para.
Alm.Attr.
In-Relay Attr.
SNMP Para.
System Para.
Batt.Cap.1#
0200AH
System Commissioning:
The X10 interface on the BACK board provide 4 input relays that can be
customized.
Edit
Ent
Common Alm.
Batt.Test Fail
LVD1 Alm.
Edit
For example, perform the following steps to change the output relay of the LVD1 Alm. alarm
from A2 to A3:
1. Enter the [Para.Set (Password) Alm.Attr.] interface, and select LVD1 Alm.
2. Press Ent to enter the modification interface and adjust the parameter using the direction
keys.
3. Press Ent to save the modification (or press Esc to cancel it).
Reset this system time according to the local time of the area
w here the equipment is installed, to ensure the coorectness of
the periodical management and time information of the system.
Para.Set
Batt.Cap.1#
300AH
Batt.Cap.2#
300AH
Batt.Cap.3#
0AH
System Para.
Batt.Para.
SMR Para.
Alm.Attr.
In-Relay Attr.
SNMP Para.
LVD1 Alm.
Requirem ent
3. Press Ent to save the modification (or press Esc to cancel it).
Ent
Alm.Attr.
Step:
Requirem ent
For example, perform the following steps to set the parameter Batt.Cap.1 to change the
capacity of battery pack 1 from 300 AH to 200 AH:
1. Enter the [Para.Set (Password) System Para.] interface, and select Batt.Cap.1.
2. Press Ent to enter the modification interface and adjust the value using the direction keys.
System Para.
Para.Set
Select Alm.Attr.
Steps:
Ent
/4
http://www.zte.com.cn
Batt.Cap.1#
200AH
Batt.Cap.2#
300AH
Batt.Cap.3#
0AH
Follow-up
or
Modify other
parameters
Ent
In-Relay Attr.
In-Relay Attr.1
In-Relay Attr.2
In-Relay Attr.3
In-Relay Attr.4
Ent
Grade
State
State
Ent
Close
Open
Save
Grade
Open
Mask
Name
In-Relay 2
Close
Mask
Name
In-Relay 2
In-Relay Attr. 2
Esc
3. Use the multimeter to check the DC power supply for the loads. The
terminals to be tested are as shown in the image below.
Criteria: The measured value should be positive, 42 VDC to 58 VDC.
State
Edit
Ent
In-Relay Attr. 2
Return to the
upper-level
interface to select
the other input
relays.
Select Open.
ZTE Corporation
Postcode: 518057
Website: http://ensupport.zte.com.cn
Black
probe
attributes of the
input relay.
DC Load
DC INPUT
Email: 800@zte.com.cn