SOPforChangeoverfromUPStoMaintenancebypass&VICEVERSA

ApplicableonHipulseModelonly

S.No

Action

Impact
LoadTransferonMaintenanceBypass

1
2
3
4
5
6
7
8
9
10
11
12

SwitchOFFinverterOFFbuttonfromfrontpanelmimicdisplayofUPS1
SwitchOFFinverterOFFbuttonfromfrontpanelmimicdisplayofUPS2
SwitchonMaintenancebypassisolator(Q3)ofUPS1
SwitchonMaintenancebypassisolator(Q3)ofUPS2
SwitchOFFoutputisolator(Q4)ofUPS1
SwitchOFFoutputisolator(Q4)ofUPS2
SwitchOFFbatterybreakerofUPS1
SwitchOFFbatterybreakerofUPS2
SwitchOFFinputsupplyisolator(Q1)ofUPS1
SwitchOFFinputsupplyisolator(Q1)ofUPS2
SwitchOFFbypasssupplyisolator(Q2)ofUPS1
SwitchOFFbypasssupplyisolator(Q2)ofUPS2

S.No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

SwitchONoutputisolator(Q4)ofUPS1
SwitchONoutputisolator(Q4)ofUPS2
SwitchONbypassisolator(Q2)ofUPS1
Confirm"loadonbypass"messageonfrontLCDdisplayofUPS1
SwitchONbypassisolator(Q2)ofUPS2
Confirm"loadonbypass"messageonfrontLCDdisplayofUPS2
SwitchOFFMaintenancebypassisolator(Q3)ofUPS1
SwitchOFFMaintenancebypassisolator(Q3)ofUPS2
SwitchONinputsupplyisolator(Q1)ofUPS1
SwitchONinputsupplyisolator(Q1)ofUPS2
Waitfor03minutestodevelopDCbusVoltageabove425VDC
SwitchONbatterybreakerofUPS1
SwitchONbatterybreakerofUPS2
SwitchONInverterONbuttonfromfrontpanelmimicdisplayofUPS1
SwitchONInverterONbuttonfromfrontpanelmimicdisplayofUPS2

LoadshallbetransferredonUPS2
Loadshallbetransferredonbypasssupply(SVR)
LoadshallbetransferredonMaintenancebypass
LoadshallbetransferredonMaintenancebypass
UPS1internalPowerpartsshallbeisolatedfromload
UPS2internalPowerpartsshallbeisolatedfromload
BatterybankshallbeisolatedfromUPS1
BatterybankshallbeisolatedfromUPS1
MainsinputpowershallbeisolatedfromUPS1
MainsinputpowershallbeisolatedfromUPS2
BypasssupplyshallbeisolatedfromUPS1&itiscompletelyinpowerOFFcondition
BypasssupplyshallbeisolatedfromUPS2&itiscompletelyinpowerOFFcondition

LoadtransferfrommaintenanceBypasstoUPS
Loadshallonmaintenancebypassmode
Loadshallonmaintenancebypassmode
Bypasssupply(SVR)shallbeconnectedtoUPS1
Bypasssupply(SVR)shallbeconnectedtoUPS2
Loadshallbetransferredonbypasssupply(SVR)ofUPS1
Loadshallbesharedbybypasssupply(SVR)ofbothUPS
RectifierofUPS1shallbeturnedON
RectifierofUPS2shallbeturnedON
DevelopmentofDCbusvoltage
BatterybankshallbeconnectedtoUPS1
BatterybankshallbeconnectedtoUPS2
InverterofUPS1shallbeswitchedON
InverterofUPS2shallbeswitchedON

Note:BeforeproceedingforanytransferensurethatBothUPSaresynschornised&sharingload.Noalarmrelatedtosynchronisingshallbepresentinanyofthe
UPS,otherwiseProceedingfortransfer/changeovermaycausebreakinoutputvoltage.otherwisestatedIftheinverterisnotsynchronisedANDissupplyingtheload,orifthe
Reservesupplyisnotok,donotproceedbecausethesupplyoftheloadcouldbeinterrupted.