REG-PE Quick Guide


For Start-Up and Installation
of the Telecontrol Interface REG-PE using IEC61850 and IEC 60870-5-104
in connection with Eberle devices
Version: 1.4

Creation Date:
Release Date:

12-05-2004
24-07-2007

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

a-eberle

- 2/10 -

www.TELE-DATA.de www.a-eberle.de

Author

Department

Changes

Version

Date

www.tele-data.de

Draft

1.0

05-12-2004

Wolfgang Borchers

www.tele-data.de

Chapter 5 pin out

1.1

01-12-2005

Wolfgang Borchers

www.tele-data.de

19-version amendment

1.2

02-02-2005

Bernd Klein

www.tele-data.de

Chapter 4 FTP

1.3

03-18-2005

Wolfgang Borchers

www.tele-data.de

netmask amendment

1.4

24-07-2006

Distribution:
Name

Department

Location

Telephone

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

- 3/10 -

www.TELE-DATA.de www.a-eberle.de

a-eberle

1. Content
1.
2.
3.

Content...............................................................................................................3
Introduction .......................................................................................................4
Operating in Boot Loader Mode.......................................................................5
3.1
Load of Firmware ....................................................................................... 5
3.1.1
REG-PE version for 19 racks ............................................................... 5
3.1.2
REG-PE version for REG-DA ................................................................ 6
4.
Pin Out ...............................................................................................................8
4.1
Internal RS232 (COM 2) of REG-D/DA....................................................... 9
4.2
Graphic view of REG-DA.......................................................................... 10

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

- 4/10 -

www.TELE-DATA.de www.a-eberle.de

a-eberle

2. Introduction
This document is especially designed for the IEC61850 and IEC 60870-5-104
protocol using the REG-PE device. It is describing the primal, initial Configuration of
the REG-PE telecontrol device. The configuration is done by setting up the desired
IP-addresses.
There are 2 REG-PE versions available: for internal use in REG-DA and for external
use in a 19 rack. Please have a look in the fitting section according to the version
you got.

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

- 5/10 -

www.TELE-DATA.de www.a-eberle.de

a-eberle

3. Operating in Boot Loader Mode


3.1 Load of Firmware
3.1.1 REG-PE version for 19 racks
At the front plate, the REG-PE device has a DSUB-9 connector labeled PARAM.
Connect it to a COM interface of your PC using a null modem cable as explained in
section 3.1.2. Now you can control the boot loader (PPCBoot). PPCBoot stays active
for 5 seconds since resetting device (you can reset the REG-PE if you press the red
reset button on REG-PE). Afterwards, it will automatically restart the operating
system and the application (as far as loaded). Connect a terminal program with the
following settings, to control PPCBoot

Baud:
Bit:
Parity:
Stop:

115200
8
none
1

If any key on PC keyboard is pressed in the first 5 seconds after entering boot mode
of REG-PE, PPCBoot will stay active.
Please enter the following if you want to enter the IP-address 192.168.1.1:
setenv ipaddr 192.168.1.1
saveenv
Then reset ( press red REG-PE reset button) the REG-PE and you can start working
with it.

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

a-eberle

- 6/10 -

www.TELE-DATA.de www.a-eberle.de

3.1.2 REG-PE version for REG-DA


Please open the door of the REG-DA and connect to COM1 of REG-PE.
Note: The REG-PE comes with all firmware for IEC operation pre loaded, only
the IP address is required to be set up.
1. Make up a lead:
Male DB9 connector: (shown assignment of RXD, TXD is for a standard PC-COM)
Pin 2
Pin 3
Pin 5
Screen
2. Terminate
Pin out

RXD
TXD
GND
GND-SCR Screen Wire
these wires to the Com 1 port on the REG-PE card as shown in section

COM 1REG-DA Terminal 87


88
89
90

RXD
TXD
GND
GND-SCR Screen Wire

3. Connect this lead via a null modem cable to a PC COM port


4. Start a terminal session (i.e Hyperterminal) using the settings>
Baudrate:
Bit:
Parity:
Stop:
Handshake:

115200
8
none
1
None or Xon/Xoff

5.Note at this stage you will still be unable to talk with the REG-DA
6. Place REG-DA in boot mode with menu Setup 6 F5 F1 depressed for 5
seconds or just restart the REG-DA ( restart means just power OFF and ON REGDA).
Please note, the loader mode with menu Setup 6 F5 F1 depressed for 5
seconds is only necessary to reset the internal REG-PE, the internal version got no
separate reset button. After REG-DA has been switched on one time in the loader
mode the REG-PE is in the reset mode. REG-PE is then able for IP address setting
via terminal program. Please press reset button F4 in REG-DA loader mode to
continue normal voltage regulator mode on REG-DA again.

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

- 7/10 -

www.TELE-DATA.de www.a-eberle.de

a-eberle

7. Within 5secs hit any key on the keyboard of your PC. This will stop the timer and
bring up an arrow on the screen.
The screen will look like the following example:
PPCBoot 1.2.0 (Oct 29 2004 - 15:38:39)
CPU: XPC860xxZPnnD4 at 50 MHz: 16 kB I-Cache 8 kB D-Cache FEC present
Watchdog enabled
Board: ### No HW ID - assuming TQM8xxL
DRAM: 64 MB
FLASH: 8 MB
In: serial
Out: serial
Err: serial
PCMCIA: No Card found
Net: FEC ETHERNET [PRIME]
Type "run flash_nfs" to mount root filesystem over NFS
Hit any key to stop autoboot: 0
=>
8. You are now in the PPCBoot mode.
9. To set the IP address Enter "setenv ipaddr ???.???.???.???" and hit enter.
10 If a gateway is required then enter "setenv gatewayip ???.???.???.???" and hit
enter. If a netmask is required then enter "setenv netmask ???.???.???.???" and hit
enter.
11. To save the new IP address and gateway enter "saveenv" and hit enter.
Example:
=> setenv ipaddr 192.168.1.64
=> setenv netmask 255.255.0.0
=> saveenv
12. Reset the REG-DA by pressing F4 or restart the REG-DA. From here you will be
able to access the device via the Web server or over the IEC61850 connection.

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

- 8/10 -

www.TELE-DATA.de www.a-eberle.de

a-eberle

4. Pin Out
Pin out is done customer specific. Please refer to the according wiring scheme.
Here is an example of the pin out for the external REG-PE for 19 racks:

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

a-eberle

- 9/10 -

www.TELE-DATA.de www.a-eberle.de

Pin out of REG-DA with internal REG-PE:

87 88 89 90

91 92 93 94

RXD TXD GND GND-SCR

RXD TXD GND GND-SCR

COM1

COM2

Ethernet

For setting up the IP-address please use COM1 with RXD, TXD and GND connected.
For details please see chapter 3.1 firmware loading.

4.1 Internal RS232 (COM 2) of REG-D/DA


For communication between REG-Sys device and REG-P or REG-PE the com 2 of
the REG-Sys device must be set correctly.
Note: Dont change default COM2 settings (Setup 6/ RS-232/ COM2)!
In case parameters are accidentally set wrong, adjust them please accordingly:
COM 2 Parameter:
MODE:
BAUDRATE:
PARITY:
HANDSHAKE:

ECL
57600
Even
Xon/Xoff

Version 1.4 07-24-2006


Copying of this document and giving it to others and the use of communication of the contents thereof are forbidden without express authority
Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.

REG-PE Quick Guide

- 10/10 -

www.TELE-DATA.de www.a-eberle.de

a-eberle

4.2 Graphic view of REG-DA

COM1

COM2

Ethernet