Beruflich Dokumente
Kultur Dokumente
- 1/10 -
www.TELE-DATA.de www.a-eberle.de
a-eberle
Creation Date:
Release Date:
12-05-2004
24-07-2007
a-eberle
- 2/10 -
www.TELE-DATA.de www.a-eberle.de
Author
Department
Changes
Version
Date
www.tele-data.de
Draft
1.0
05-12-2004
Wolfgang Borchers
www.tele-data.de
1.1
01-12-2005
Wolfgang Borchers
www.tele-data.de
19-version amendment
1.2
02-02-2005
Bernd Klein
www.tele-data.de
Chapter 4 FTP
1.3
03-18-2005
Wolfgang Borchers
www.tele-data.de
netmask amendment
1.4
24-07-2006
Distribution:
Name
Department
Location
Telephone
- 3/10 -
www.TELE-DATA.de www.a-eberle.de
a-eberle
1. Content
1.
2.
3.
Content...............................................................................................................3
Introduction .......................................................................................................4
Operating in Boot Loader Mode.......................................................................5
3.1
Load of Firmware ....................................................................................... 5
3.1.1
REG-PE version for 19 racks ............................................................... 5
3.1.2
REG-PE version for REG-DA ................................................................ 6
4.
Pin Out ...............................................................................................................8
4.1
Internal RS232 (COM 2) of REG-D/DA....................................................... 9
4.2
Graphic view of REG-DA.......................................................................... 10
- 4/10 -
www.TELE-DATA.de www.a-eberle.de
a-eberle
2. Introduction
This document is especially designed for the IEC61850 and IEC 60870-5-104
protocol using the REG-PE device. It is describing the primal, initial Configuration of
the REG-PE telecontrol device. The configuration is done by setting up the desired
IP-addresses.
There are 2 REG-PE versions available: for internal use in REG-DA and for external
use in a 19 rack. Please have a look in the fitting section according to the version
you got.
- 5/10 -
www.TELE-DATA.de www.a-eberle.de
a-eberle
Baud:
Bit:
Parity:
Stop:
115200
8
none
1
If any key on PC keyboard is pressed in the first 5 seconds after entering boot mode
of REG-PE, PPCBoot will stay active.
Please enter the following if you want to enter the IP-address 192.168.1.1:
setenv ipaddr 192.168.1.1
saveenv
Then reset ( press red REG-PE reset button) the REG-PE and you can start working
with it.
a-eberle
- 6/10 -
www.TELE-DATA.de www.a-eberle.de
RXD
TXD
GND
GND-SCR Screen Wire
these wires to the Com 1 port on the REG-PE card as shown in section
RXD
TXD
GND
GND-SCR Screen Wire
115200
8
none
1
None or Xon/Xoff
5.Note at this stage you will still be unable to talk with the REG-DA
6. Place REG-DA in boot mode with menu Setup 6 F5 F1 depressed for 5
seconds or just restart the REG-DA ( restart means just power OFF and ON REGDA).
Please note, the loader mode with menu Setup 6 F5 F1 depressed for 5
seconds is only necessary to reset the internal REG-PE, the internal version got no
separate reset button. After REG-DA has been switched on one time in the loader
mode the REG-PE is in the reset mode. REG-PE is then able for IP address setting
via terminal program. Please press reset button F4 in REG-DA loader mode to
continue normal voltage regulator mode on REG-DA again.
- 7/10 -
www.TELE-DATA.de www.a-eberle.de
a-eberle
7. Within 5secs hit any key on the keyboard of your PC. This will stop the timer and
bring up an arrow on the screen.
The screen will look like the following example:
PPCBoot 1.2.0 (Oct 29 2004 - 15:38:39)
CPU: XPC860xxZPnnD4 at 50 MHz: 16 kB I-Cache 8 kB D-Cache FEC present
Watchdog enabled
Board: ### No HW ID - assuming TQM8xxL
DRAM: 64 MB
FLASH: 8 MB
In: serial
Out: serial
Err: serial
PCMCIA: No Card found
Net: FEC ETHERNET [PRIME]
Type "run flash_nfs" to mount root filesystem over NFS
Hit any key to stop autoboot: 0
=>
8. You are now in the PPCBoot mode.
9. To set the IP address Enter "setenv ipaddr ???.???.???.???" and hit enter.
10 If a gateway is required then enter "setenv gatewayip ???.???.???.???" and hit
enter. If a netmask is required then enter "setenv netmask ???.???.???.???" and hit
enter.
11. To save the new IP address and gateway enter "saveenv" and hit enter.
Example:
=> setenv ipaddr 192.168.1.64
=> setenv netmask 255.255.0.0
=> saveenv
12. Reset the REG-DA by pressing F4 or restart the REG-DA. From here you will be
able to access the device via the Web server or over the IEC61850 connection.
- 8/10 -
www.TELE-DATA.de www.a-eberle.de
a-eberle
4. Pin Out
Pin out is done customer specific. Please refer to the according wiring scheme.
Here is an example of the pin out for the external REG-PE for 19 racks:
a-eberle
- 9/10 -
www.TELE-DATA.de www.a-eberle.de
87 88 89 90
91 92 93 94
COM1
COM2
Ethernet
For setting up the IP-address please use COM1 with RXD, TXD and GND connected.
For details please see chapter 3.1 firmware loading.
ECL
57600
Even
Xon/Xoff
- 10/10 -