Firefighting System
EHS Department
Atlas Power Plant
1 | Page
Firefighting
System
Table of Content
Contents
Scope:......................................................................................................................... 3
Fire Fighting Engines:................................................................................................. 3
Jockey Pump:............................................................................................................ 3
Foam Tank:................................................................................................................ 4
Fire Water Tank:......................................................................................................... 4
Fire Fighting Systems:.................................................................................................... 4
Fire Hydrant:.............................................................................................................. 4
Indoor Fire Cabinets:................................................................................................... 5
Indoor & Outdoor Foam Tanks:..................................................................................... 5
Fire Extinguishers:...................................................................................................... 6
Foam Water System:................................................................................................... 6
Foam Monitor Guns:................................................................................................... 6
Water Deluge System:................................................................................................. 6
Foam Water Deluge System:........................................................................................ 7
CO2 System:.............................................................................................................. 7
Fire Detection System.................................................................................................... 8
Sprinkler system......................................................................................................... 8
Working:................................................................................................................ 8
Manual foam water open sprinkler system:..................................................................8
Smoke detectors:....................................................................................................... 9
Multi detectors:........................................................................................................... 9
Panel:.......................................................................................................................... 9
Fire Alarm Panel:........................................................................................................ 9
CO2 Panel:.............................................................................................................. 10
Recommendations:...................................................................................................... 10
2 | Page
Firefighting
System
Scope:
It covers the fragments of firefighting room, operation of firefighting system and working of fire
detection system. Lastly some recommendations are also listed.
Jockey Pump:
It is used to maintain pressure in case of minor leakage in firefighting line. It functions at 5 bar
and stop at 7.5 bar. Current it is operating automatically.
3 | Page
Firefighting
System
Foam Tank:
The capacity of foam tank is 10,000 ltr and the type of fluid is AFFF. 3 % AFFF and 97% water is
mixed, after that it used for firefighting where foam water extinguishing is required.
Fire Hydrant:
Standard followed for this system is NFPA 24. Fire Cabinet and Hydrants are around tank yard,
boiler area, fuel decanting area, engine hall and FT building. Total number of cabinets and
hydrants are 34. Every cabinet includes one call point. If we push the call point then a fire signal
is generated at fire panel and control room.
4 | Page
Firefighting
System
5 | Page
Firefighting
System
Fire Extinguishers:
Standard followed for this system is NFPA 10. Fire extinguishers are around tank yard, control
room, washing room, chemical room, fuel decanting area, engine hall, FT building and offices.
Total numbers of fire extinguishers are 104. Varies types available on plant are water, CO2,
DCP, foam and Halotron and they range from 5 to 150 ltr.
6 | Page
Firefighting
System
7 | Page
Firefighting
System
CO2 System:
Standard followed for this system is NFPA 12 and the system is installed in MV & LV room,
battery room, trench area and in the basement of control room, but still testing is required for
CO2 system. Total 54 cylinders in CO2 room and every cylinder have 45 Kg capacity.
Sprinkler system
Standard followed for this system is NFPA 16 and the system is installed in switch yard, engine
hall and in firefighting house. Sprinklers are available with different temperature bulbs and
colors.
1. Transformer area:
Temperature 68, with red sprinkler
2. Firefighting house:
Temperature 79, with yellow sprinkler
3. Engines:
8 | Page
Firefighting
System
Temperature 93, with green sprinkler
4. Turbo charger:
Temperature 141, with blue sprinkler
Working:
If any sprinkler detects fire then it burst due to high temperature. Foam water will discharge
through an open spray nozzle attached with every sprinkler.
Smoke detectors:
Smoke detectors are installed at following locations,
Multi detectors:
Total 53 multi detectors are only installed in engine hall. Multi detector has two detection
systems
9 | Page
Firefighting
System
Smoke detection
Heat detection
Panel:
Following are the panels that are used to check the status of system
CO2 Panel:
If fire is detected in effected area then fire detection system send a signal to CO2 panel and then
rings the alarm. Healthy and faulty condition of detection system is also shown on CO2 panel.
10 | P a g e
Firefighting
System
Recommendations: