TM 1703 ACP

PE-640x/USIO65
Peripheral Controller (Ax-PE Bus el/opt)

System element for interfacing I/O modules


via the TM bus

up to 8 I/O modules
focus on telecontrol
acquisition, conditioning and output
of process data using I/O modules
acc. to IEC 60870-5-101/104

automation
open- and closed-loop control (cycle
time typically 100ms and slower)

function and error indication via LED


16 Mbps Ax 1703 peripheral bus
(electrical, optical)

Supports I/O modules for process input

binary signals
analog signals (currents, voltages,
temperatures)

Supports I/O modules for process output

binary signals
analog signals (currents, voltages)

Power to be supplied by PS-6620, PS-6630


or PS-6632

Copyright Siemens AG 2008

MC6-023-2.01

Application and Overview

The IEC 60870-5-101/104 compliant PE-640x/USIO65 peripheral element is used in the TM


1703 system for connecting I/O modules to a basic system element with open-/closed-loop
control function (master control element, processing element).
The connection is made via the serial Ax 1703 peripheral bus using bus interfaces. Several
bus interfaces are available:
Type

Designation

CM-0843

Bus Interface Ax-PE 4x USB

CM-0842

Bus Interface Ax-PE 4x optical

Connection

Number of Peripheral
Elements

electrical

up to 16

optical

up to 16

Configurations with CM-0843 and CM-0842 can be found in the respective data sheet.
PE-640x/USIO65 is mainly used in telecontrol and automation. The peripheral element is in
charge for process data input and output. For this it is supported by I/O modules:
I/O Module

Designation

Load

DI-6100

Binary Input 2x8, 24-60VDC

Digital I/O module

170 mW

DI-6101

Binary Input 2x8, 110/220VDC

Digital I/O module

170 mW

DI-6102

Binary Input 2x8, 24-60VDC 1ms

Digital I/O module

170 mW

DI-6103

Binary Input 2x8, 110/220VDC 1ms

Digital I/O module

170 mW

DI-6104

Binary Input 2x8, 220VDC

Digital I/O module

170 mW

DO-6200

Binary Output Transistor 2x8, 24-60VDC

Digital I/O module

600 mW

DO-6212

Binary Output Relays 8x 24-220VDC/230VAC Digital I/O module

800 mW

AI-6300

Analog Input 2x2 20mA/10V

Analog I/O module

480 mW

AI-6307

Analog Input 2x2 5mA/10V

Analog I/O module

480 mW

AI-6310

Analog Input 2x2 Pt100/Ni100

Analog I/O module

480 mW

AO-6380

Analog Output 4x 20mA/10mA/10V

Analog I/O module

1900 mW

Module

Designation

Type

Load

PE-6400

Peripheral Control Module Ax-PE Bus


(electrical)

---

720 mW

PE-6401

Peripheral Control Module Ax-PE Bus (1x


opt.)

---

typ. 1150 mW

Peripheral Control Module Ax-PE Bus (2x


opt.)

---

typ. 1400 mW

PE-6402
1)

1)

on request only
Module

Type

Designation

Type

Available Power

PS-6620

Power Supply Module 24-60 VDC

---

8000 mW

PS-6630

Power Supply Module 24-60 VDC (EMC+)

---

8000 mW

PS-6632

Power Supply Module 110-220 VDC (EMC+)

---

8000 mW

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Up to 8 I/O modules can be installed in addition to the peripheral control module as long as
both

the total load of the I/O modules does not exceed 7000 mW

the total load of the I/O modules and the peripheral control module does not exceed the
power provided by the power supply module

The PE-640x/USIO65 peripheral element communicates via the TM bus with the I/O modules
and through them with the process. Via the Ax 1703 peripheral bus the communication is
done with higher-level basic system element.
Ax 1703
Peripheral Bus

....

....

Peripheral
Control
Module

Power
Supply
Module

8 I/O-Modules, max.

Common Functions
I/O module monitoring, failure management
Signaling via LED's

Functions for Telecontrol and Automation


Acquisition and processing of process data according to IEC 60870-5-101/104

The functions, specific for each I/O module, are listed in the following.
Footnotes are used to specify the effect of the functions in detail (they are
explained at the bottom of this page)

Output of process data according to IEC 60870-5-101/104

The functions, specific for each I/O module, are listed in the following.
Footnotes are used to specify the effect of the functions in detail (they are
explained at the bottom of this page)

Transmission of spontaneous process information to the basic system element for


further distribution
Transmission of periodical process information, from and to the open-/closed-loop
control function in the higher-level basic system element
The functions stated above are described in detail in the document 1703 Common
Functions Peripheral Elements according to IEC 60870-5-101/104
t

Telecontrol
the function affects process information which is spontaneously transmitted

t1

Telecontrol
the function delivers (acquisition) spontaneously transmitted process information or is
controlled by such information (output); partly, periodically transmitted information is also
created/required

Automation
the function affects process information which is periodically transmitted

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Acqusition Functions in Detail


DI-6100
DI-6101
DI-6104

Binary Input 2x8, 24-60VDC


Binary Input 2x8, 110/220VDC
Binary Input 2x8, 220VDC

single-point information
acquisition with a resolution of 10ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
determination of the cause of transmission t
spontaneous transmission of changes t
periodical transmission a

double-point information
acquisition with a resolution of 10ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
monitoring intermediate and faulty positions t
determination of the cause of transmission t
reporting switching operations in progress t
breaker tripping detection t
breaker tripping suppression during auto-reclose t
spontaneous transmission of changes t
periodical transmission a

integrated totals via count pulses (via binary inputs of the module) t1
acquisition by firmware with a maximum count frequency of 20Hz
pulse length/pause >20ms/>20ms
revision
power monitoring
inversion
pulse counting
counter value formation
count pulse evaluation
set counter
formation of integrated totals
counter request
interval control
freezed absolute value
freezed relative value
not power-fail safe
integrated total transmission according to IEC 60870-5-101
spontaneous transmission

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

DI-6102
DI-6103

Binary Input 2x8, 24-60VDC 1ms


Binary Input 2x8, 110/220VDC 1ms

single-point information
acquisition with a resolution of 1ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
determination of the cause of transmission t
spontaneous transmission of changes t
periodical transmission a

double-point information
acquisition with a resolution of 1ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
monitoring intermediate and faulty positions t
determination of the cause of transmission t
reporting switching operations in progress t
breaker tripping detection t
breaker tripping suppression during auto-reclose t
spontaneous transmission of changes t
periodical transmission a

integrated totals via count pulses (via binary inputs of the module) t1
acquisition by firmware with a maximum count frequency of 20Hz
pulse length/pause >2ms/>2ms
revision
power monitoring
inversion
pulse counting
counter value formation
count pulse evaluation
set counter
formation of integrated totals
counter request
interval control
freezed absolute value
freezed relative value
not power-fail safe
integrated total transmission according to IEC 60870-5-101
spontaneous transmission

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

AI-6300
AI-6307

Analog Input 2x2 20mA/10V


Analog Input 2x2 5mA/10V

currents and voltages


settable acquistion grid n*100ms t
measurement range settable with a resloution of t
12 bits + sign at 20mA
12 bits + sign at 10V
shrinking the range results in decreasing resolution
revision t
noise rejection t
automatic calibration t
smoothing t
adaptation t
linear (normalized, technologically scaled or short floating point)
suppression of zero range
plausibility check
change monitoring t
spontaneous transmission of changes t

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

AI-6310

Analog Input 2x2 Pt100/Ni100

temperatures t1

acquisition of resistance thermometers via analog inputs of a SM-0571


connection of the resistance thermometers: two-, three-, or four-wire technique
update every 400ms
settable measuring range
when transferring temperatures
(a) Pt100: -50 .. +350C / -58 .. +662F / (80.31 .. 229.67 )
(b) Pt100: -100 .. +700C / -148 .. +1292F / (60.25 .. 345.13 )

(c) Ni100: -60 .. +250C / -76 .. +482F / (74.18 .. 295.52 )


when transferring resistance values
(a) Pt100: 0 .. 230
(b) Pt100: 0 .. 346
(c) Ni100: 0 .. 346

resolution
when transferring temperatures
(a) Pt100: 0.20C / 0.36F / (90 m

(b) Pt100: 0.35C / 0.63F / (130 m


(c) Ni100: 0.35C / 0.63F / (130 m
when transferring resistance values
(a) Pt100: 90 m
(b) Pt100: 130 m
(c) Ni100: 130 m

revision
noise rejection
automatic calibration
calibration for 2-wire technique
smoothing
adaptation
temperature value (C, F)
conversion using implemented curves
resistance ()

change monitoring
spontaneous transmission of changes

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Output Functions in Detail


DO-6200

Binary Output Transistor 2x8, 24-60VDC


commands t1

pulse
checked output of pulse commands
1-pole
single, double and regulating step commands
command output (OC)
basic application functions and procedures according to IEC 60870-5-101/104
formal check
direct command
select and execute command ("select/execute")
retry suppression
1-out-of-n check
control location check
command locking
synchronization
revision
command output time
settable
dependent on the process
return information monitoring
command prolongation
switching sequences
command output for the auto-reclose function
if outputs of the module are used for pulse commands, no outputs of the same
module can be used for binary information output

binary information output


selectable behavior on communication failure ta
(deactivation or retention)
deactivation on module failure ta
spontaneous transmission t or
periodical transmission a
if outputs of the module are used for binary information output, no outputs of the
same module can be used for pulse commands

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

DO-6212

Binary Output Relays 8x 24-220VDC/230VAC

pulse commands t1
checked output of pulse commands
1-pole, 1-pole, 2-pole
cannot be mixed
single, double and regulating step commands
command output (OC)
basic application functions and procedures according to IEC 60870-5-101/104
formal check
direct command
select and execute command ("select/execute")
retry suppression
1-out-of-n check
control location check
command locking
synchronization
revision
command output time
settable
dependent on the process
return information monitoring
command prolongation
switching sequences
command output for the auto-reclose function
if outputs of the module are used for pulse commands, no outputs of the same
module can be used for binary information output

binary information output


selectable behavior on communication failure ta
(deactivation or retention)
deactivation on module failure ta
spontaneous transmission t or
periodical transmission a
if outputs of the module are used for binary information output, no outputs of the
same module can be used for pulse commands

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

AO-6380

setpoint values by means of currents and voltages


output via analog outputs of a SM-0572 ta
output range settable with a resloution of ta
15 bits + sign at 20mA
15 bits + sign at 10V
shrinking the range results in decreasing resolution
basic application functions and procedures according to IEC 60870-5-101/104 ta
formal check
direct command
select and execute command ("select/execute")
adaptation t
linear (normalized, technologically scaled or short floating point) t
selectable behavior on communication failure and module failure ta
(keep value, output substitute value)
spontaneous transmission t or
periodical transmission a

10

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Further Functions

return information to pulse command assignment


settable assignment
when using the peripheral element on a ACP 1703 platform

for messages and pulse commands, which are acquired or output on the
peripheral element itself
for messages and pulse commands, which are acquired or output on different
peripheral elements of the same basic system element
predefined assignment
for messages and pulse commands, which are acquired or output on the
peripheral element itself

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

11

PE-6400

Peripheral Control Module Ax-PE Bus (electrical)

Peripheral control module

connects I/O modules via the TM bus


up to 8 I/O modules

connects to the basic system element via


electrical Ax 1703 peripheral bus
indication of function and errors via LEDs
power to be supplied by PS-6620, PS-6630 or
PS-6632

12

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Processor and Memory
Processor

80C251SQ-16, 16 MHz

Program memory

PE-ROM 256 kByte

Main memory

RAM 64 kByte

Parameter memory

EEPROM 512 Bytes

Power Supply
Operating voltage

4.7 .. 5.1 VDC, max. 720 mW


Power to be supplied by PS-6620, PS-6630 or PS-6632

Mechanics and Connectors


Ax 1703 peripheral bus

Transmission rate 16Mbps

Connector(s) for den Ax 1703


peripheral bus

USB / Serie A, 4-pin

Dimensions

127 x 63 x 72 mm (L x W x H, dimensions w/o DIN rail)

Weight

Approx. 135 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

USB cables, 3 m maximum length

13

PE-6401

Peripheral Control Module Ax-PE Bus (1x opt.)

Peripheral control module

connects I/O modules via the TM bus


up to 8 I/O modules

connects to the basic system element via


optical Ax 1703 peripheral bus
indication of function and errors via LEDs
power to be supplied by PS-6620, PS-6630 or
PS-6632

14

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Processor and Memory
Processor

80C251SQ-16, 16 MHz

Program memory

PE-ROM 256 kByte

Main memory

RAM 64 kByte

Parameter memory

EEPROM 512 Bytes

Interfaces
1 interface to the BSE
(Ax 1703 peripheral bus, optical,
full duplex)
(X6)
Optical interface
(duplex plastic optical fibre)

Optical interface
Transmission rate 16Mbps
Securing of data, hamming distance D=4
Specification see below

Type

TODX295

Optical fibre:
(+) Glass fibre (PCF fibre)

(Toshiba TOSLINK)

(10dB/km)

16Mbps

Transmitter (660nm):
Power launched into the fibre
(+)

max

min

-14dBm

-20dBm

Receiver (660nm):
Received power:

max
-9dBm

min
-28dBm

Line lenghts (3dB system reserve):


(+)

0 .. 200m

Power Supply
Operating voltage

4.75 .. 5.25 VDC, typ. 1150 mW


Power to be supplied by PS-6620, PS-6630 or PS-6632

Mechanics and Connectors


Ax 1703 peripheral bus

Transmission rate 16Mbps

Connector(s) for den Ax 1703


peripheral bus

Glass fibre (+)

Dimensions

127 x 63 x 72 mm (L x W x H, dimensions w/o DIN rail)

Weight

Approx. 160 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

TOCP201

(Toshiba TOSLINK)

15

PE-6402

Peripheral Control Module Ax-PE Bus (2x opt.)

Peripheral control module

connects I/O modules via the TM bus


up to 8 I/O modules

connects to a redundant basic system element


via two optical Ax 1703 peripheral buses
indication of function and errors via LEDs
power to be supplied by PS-6620, PS-6630 or
PS-6632

16

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Processor and Memory
Processor

80C251SQ-16, 16 MHz

Program memory

PE-ROM 256 kByte

Main memory

RAM 64 kByte

Parameter memory

EEPROM 512 Bytes

Interfaces
2 interfaces to the BSE
(Ax 1703 peripheral bus, optical,
full duplex)
(X6, X7)
Optical interface
(duplex plastic optical fibre)

Optical interface
Transmission rate 16Mbps
Securing of data, hamming distance D=4
Specification see below

Type

TODX295

Optical fibre:
(+) Glass fibre (PCF fibre)

(Toshiba TOSLINK)

(10dB/km)

16Mbps

Transmitter (660nm):
Power launched into the fibre
(+)

max
-14dBm

min
-20dBm

Receiver (660nm):
Received power:

max
-9dBm

min
-28dBm

Line lenghts (3dB system reserve):


(+)

0 .. 200m

Power Supply
Operating voltage

4.75 .. 5.25 VDC, typ. 1400 mW


Power to be supplied by PS-6620, PS-6630 or PS-6632

Mechanics and Connectors


Ax 1703 peripheral bus

Transmission rate 16Mbps

Connector(s) for den Ax 1703


peripheral bus

Glass fibre (+)

Dimensions

127 x 63 x 72 mm (L x W x H, dimensions w/o DIN rail)

Weight

Approx. 170 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

TOCP201

(Toshiba TOSLINK)

17

DI-6100

Binary Input 2x8, 24-60VDC

Binary input module

18

16 inputs (2 groups of 8 each)


galvanically insulated by optocouplers
each group has a common return
signal voltage 24-60 VDC
removable screw terminals
indication of function and states of the inputs
via LEDs
one (dedicated) input of each group can be
used for power monitoring
acquisition functions
single-point information
double-point information
integrated totals via count pulses
further functions
return information to pulse command
assignment

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary Inputs
16 binary inputs

2 groups, 8 inputs each


Galvanical insulation
Each group has a common return of selectable polarity

Filter time

One dedicated input


All other inputs

Nominal voltages

24/48/60 VDC

Operating points

12 V
16 V

Rated current

1.01.5 mA (at 18 .. 78 V)

Input circuits

1878 VDC
The circuits are operated by means of an external voltage.

2 ms
3 ms

"logic 0"
"logic 1"

Power Supply
Operating voltage

4.75.1 VDC, 170 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

19

DI-6101

Binary Input 2x8, 110/220VDC

Binary input module

16 inputs (2 groups of 8 each)


galvanically insulated by optocouplers
each group has a common return
signal voltage 110/220 VDC
removable screw terminals
indication of function and states of the inputs
via LEDs

one (dedicated) input of each group can be


used for power monitoring
acquisition functions
single-point information
double-point information
integrated totals via count pulses

20

further functions
return information to pulse command
assignment

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary Inputs
16 binary inputs

2 groups, 8 inputs each


Galvanical insulation
Each group has a common return of selectable polarity

Filter time

One dedicated input


All other inputs

Nominal voltages

110/220 VDC

Operating points

55 V
82.5 V

Rated current

1.01.7 mA (at 82250 V)

Input circuits

82250 VDC
The circuits are operated by means of an external voltage.

2 ms
3 ms

"logic 0"
"logic 1"

Power Supply
Operating voltage

4.75.1 VDC, 170 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

21

DI-6102

Binary Input 2x8, 24-60VDC 1ms

Binary input module

22

16 inputs (2 groups of 8 each)


galvanically insulated by optocouplers
each group has a common return
signal voltage 24-60 VDC
removable screw terminals
indication of function and states of the inputs
via LEDs
one (dedicated) input of each group can be
used for power monitoring
acquisition functions
single-point information
double-point information
integrated totals via count pulses
further functions
return information to pulse command
assignment

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary Inputs
16 binary inputs

2 groups, 8 inputs each


Galvanical insulation
Each group has a common return of selectable polarity

Filter time

one dedicated input


all other inputs

Nominal voltages

24/48/60 VDC

Operating points

12 V
16 V

Rated current

1.01.5 mA (at 1878 V)

Input circuits

1878 VDC
The circuits are operated by means of an external voltage.

2 ms
3 ms

"logic 0"
"logic 1"

Power Supply
Operating voltage

4.75.1 VDC, 170 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

23

DI-6103

Binary Input 2x8, 110/220VDC 1ms

Binary input module

24

16 inputs (2 groups of 8 each)


galvanically insulated by optocouplers
each group has a common return
signal voltage 110/220 VDC
removable screw terminals
indication of function and states of the inputs
via LEDs
one (dedicated) input of each group can be
used for power monitoring
acquisition functions
single-point information
double-point information
integrated totals via count pulses
further functions
return information to pulse command
assignment

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary Inputs
16 binary inputs

2 groups, 8 inputs each


galvanical insulation
each group has a common return of selectable polarity

Filter time

one dedicated input


all other inputs

Nominal voltages

110/220 VDC

Operating points

55 V
82.5 V

Rated current

1.01.7 mA (at 82250 V)

Input circuits

82250 VDC
the circuits are operated by means of an external voltage.

2 ms
3 ms

"logic 0"
"logic 1"

Power Supply
Operating voltage

4.75.1 VDC, 170mW


the voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

25

DI-6104

Binary Input 2x8, 220VDC

Binary input module


16 inputs (2 groups of 8 each)
galvanically insulated by optocouplers
each group has a common return
signal voltage 220 VDC
removable screw terminals
indication of function and states of the inputs
via LEDs
one (dedicated) input of each group can be
used for power monitoring
acquisition functions
single-point information
double-point information
integrated totals via count pulses

26

further functions
return information to pulse command
assignment

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary Inputs
16 binary inputs

2 groups, 8 inputs each


Galvanical insulation
Each group has a common return of selectable polarity

Filter time

One dedicated input


All other inputs

Nominal voltages

220 VDC

Operating points

110 V
165 V

Rated current

1.11.5 mA (at 165 :: 250V)

Input circuits

165250 VDC
The circuits are operated by means of an external voltage.

2 ms
3 ms

"logic 0"
"logic 1"

Power Supply
Operating voltage

4.75.1 VDC, 170 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

27

DO-6200

Binary Output Transistor 2x8, 24-60VDC

Binary output module

16 transistor outputs (2 groups of 8 each)


Galvanically insulated by optocouplers
Each group has a common return
Switching voltage 24-60 VDC
All outputs proof against continued short
circuit
To increase switching capacity 2 outputs can
be connected in parallel
No impact on other outputs if one is shortcircuit
Removable screw terminals
Indication of function and states of the outputs
via LEDs
output functions
pulse commands
binary information output
pulse commands and binary information
output cannot be mixed on the same module

28

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary Outputs
16 binary outputs
(transistor)

2 groups, 8 outputs each


Galvanical insulation
Each group has a common return

Nominal switching voltage

24/48/60 VDC

Voltage range

1878 VDC

Nominal current
(resistive load)

Due to thermal loading capacity of the module:

Maximum continuous current

Due to electrical ratings of the transistor switch:

0.25 A at 24, 48, and 60 VDC


(for each output, if 16 outputs are active at the same time)
0.35 A when connecting 2 outputs in parallel
(for each pair ot outputs, if 8 pairs of outputs are active at the
same time)
0.9 A

at 1878 VDC
(only 1 output active)

Nominal switching capacity


(resistive load, UN )

6W
at 24 VDC
12 W at 48 VDC
15 W at 60 VDC

Maximum switching capacity

70.2 W

Overload proof

No

Proof against continued


short-circuit

10 A

Switching cycles

Unlimited

Switching frequency

Max. 100 Hz

Output circuit voltage drop

< 0.5 V

Dynamic withstand capability

Capacitive load max. 100 nF at 60V


Inductive
500 ms (any with external free-wheeling
diode)
Lines
Z 100 , line length up to 3 km
Lamps
IN 150 mA (ION 1.8 A)

when connecting in parallel: 8.4 W


when connecting in parallel 16.8 W
when connecting in parallel: 21 W

at 78 VDC

current limitation
If the current limitation operates,
current is cut off after 10 s
Cyclic reclosing
break time
300 s
make time
10 s

at 0.25 A

Power Supply
Operating voltage

4.75.1 VDC, 600 mW


The voltage is picked off at the TM bus

Output circuits

The circuits are operated by means of an external voltage

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 260 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

29

DO-6212

Binary Output Relays 8x 24-220VDC/230VAC

Binary output module

8 relay outputs
Galvanically insulated
Switching voltage 24-220 VDC/230 VAC
The outputs can switch dc and ac voltages
Removable screw terminals
Indication of function and states of the outputs
via LEDs
output functions
pulse commands
binary information output
pulse commands and binary information
output cannot be mixed on the same module

30

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Binary outputs
8 binary outputs
(relay)

8 outputs, potential-free
Galvanical insulation

Nominal voltage

24/48/60/110/220 VDC
110/230 VAC

Maximum continuous current

2A
5A

Maximum switching voltage

250 VDC
253 VAC

Switching capacity

DC voltage

for 1 minute

Min. 50 mW at 5 VDC
Max. acc. to diagram

AC voltage
Max. 1250 VA
Max. 500 VA

5 A/250 VAC, resistive load


2 A/250 VAC, cos = 0.4

Switching cycles

3x104

Output circuits

The circuits are operated by means of an external voltage

Power Supply
Operating voltage

4.75.1 VDC, 800 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 265 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

31

AI-6300

Analog Input 2x2 20mA/10V

Analog input module

4 inputs (2 groups of 2 each)


galvanically insulated by optocouplers
acquisition of currents 20 mA
acquisition of voltages 10 V
removable screw terminals
function indication via LED
acquisition of currents and voltages cannot be
mixed on the same I/O module
recognition of open-circuit with acquisition of
currents
acquisition functions
currents and voltages
currents and voltages cannot be mixed on the
same module

32

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Analog Inputs
4 analog inputs

2 groups, 2 inputs each


Groups are galvanically insulated from one another
Voltage between 2 inputs of a group max. 4 VDC

Measuring ranges

Current measurement
Voltage measurement
Overrange

Resolution

0.013%
0.025%

at 20 mA
at 10 V

Accuracy

0.15%
0.4%
0.5%

at 25C
at 050C
at 2070C

Input impedance

122.5
11.3 k

at 20 mA
at 10 V

Current inputs

min. 70 dB
min. 90 dB

(10 Hz1 MHz)


(10 Hz500 Hz)

Voltage inputs

min. 73 dB
min. 90 dB

(10 Hz1 MHz)


(10 Hz500 Hz)

-200+20 mA
-100+10 V
typ. 2%

Common mode rejection ratio

Normal mode rejection ratio


Current inputs

0 dB
(10 Hz7.5 kHz)
+20 dB/decade
(7.5 kHz1 MHz)

Voltage inputs

0 dB
(10 Hz7.5 kHz)
+20 dB/decade
(7.5 kHz1 MHz)

Input circuits

External sensors, auxiliary voltage 18 VDC78 VDC.


The circuits are operated by means of an external voltage.

Power Supply
Operating voltage

4.75.1 VDC, max. 480 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

33

AI-6307

Analog Input 2x2 5mA

Analog input module

34

4 inputs (2 groups of 2 each)


galvanically insulated by optocouplers
acquisition of currents 5mA
acquisition of voltages 10V
removable screw terminals
function indication via LED
acquisition of currents and voltages cannot be
mixed on the same I/O module
recognition of open-circuit with acquisition of
currents
acquisition functions
currents and voltages

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Analoge Inputs
4 analog inputs

2 groups, 2 inputs each


Groups are galvanically insulated from one another
Voltage between 2 inputs of a group max. 4 VDC

Measuring ranges

Current measurement
Voltage measurement
Overrange

Resolution

0.013%
0.025%

at 5 mA
bei 10 V

Accuracy

0.15%
0.4%
0.5%

at 25C
at 050C
at 2070C

Input impedance

490
11.3 k

at 5 mA
at 10 V

Current inputs

min. 70 dB
min. 90 dB

(10 Hz1 MHz)


(10 Hz500 Hz)

Voltage inputs

min. 73 dB
min. 90 dB

(10 Hz1 MHz)


(10 Hz500 Hz)

Current inputs

0 dB
+20 dB/decade

(10 Hz7.5 kHz)


(7.5 kHz1 MHz)

Voltage inputs

0 dB
+20 dB/decade

(10 Hz7.5 kHz)


(7.5 kHz1 MHz)

-50+5 mA
-100+10 V
typ. 2%

Common mode rejection ratio

Normal mode rejection ratio

Input circuits

External sensors, auxiliary voltage 1878 VDC.


The circuits are operated by means of an external voltage.

Power Supply
Operating voltage

4.75.1 VDC, max. 480 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 225 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

35

AI-6310

Analog Input 2x2 Pt100/Ni100

Analog input module

36

4 inputs (2 groups of 2 each)


galvanically insulated by optocouplers
acquisition of temperatures
via Pt100/Ni100 resistance measurement in 2wire, 3-wire or 4-wire technology
for resistance measurement one current
source is assigned to each input
noise rejection
removable screw terminals
function indication via LED
acquisition functions
temperatures

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Analog Inputs
4 analog inputs

2 groups, 2 inputs each


Groups are galvanically insulated from one another
Voltage between 2 inputs of a group max. 20 VDC

Measuring range

Resistance measurement

50400 (Pt100, Ni100)

Overrange

typ. 20%

Input impedance

Approx. 2 M

Resolution

11 m

Noise rejection

16.7 Hz, 50 Hz, 60 Hz

settable for each group

Conversion time

Noise rejection for 50 Hz


Noise rejection for 60 Hz
Noise rejection for 16.7 Hz

120 ms
100 ms
180 ms

Accuracy

0.19%
0.21%

at 25C
at 050C

(because of the measuring method there is no dependence on


the accuracy of the constant-current source)
Reference current

2 mA

Connecting line impedance

Sum of go-and-return line

max. 40

Common mode rejection ratio

16.7 Hz, 50 Hz, 60 Hz20 kHz


10 Hz1 MHz

> 100 dB
> 70 dB

Normal mode rejection ratio

16.7 Hz, 50 Hz, 60 Hz

> 100 dB

Input circuits

The circuits are operated by means of an internal voltage


(constant-current source).

Power Supply
Operating voltage

4.75.1 VDC, max. 450 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 235 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

37

AO-6380

Analog Output 4x 20mA/10mA/10V

Analog output module

38

4 outputs

galvanically insulated by optocouplers

output of currents 20mA, 10mA

output of voltages 10V

removable screw terminals

function indication via LED

output functions
setpoint values by means of currents and
voltages

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Technical Specifications
Analog Outputs
4 analog outputs

All outputs galvanically insulated

Current output

max. 20 mA on max. 500 load


max. 10 mA on max. 1 k load

Voltage output

max. 10 V on min. 1 k load

Resolution

0.025%

Settling time

1 ms

Accuracy

0.3%
0.4%
0.7%

Output circuits

The circuits are operated by means of an internal voltage.

at 20 mA, 10 mA, 10 V

at 25 C
at 050 C
at -2070 C

Power Supply
Operating voltage

4.75.1 VDC, max. 1900 mW


The voltage is picked off at the TM bus

Mechanics and Connectors


Terminals

Removable screw terminals (grid size 5.08)

Dimensions

131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight

Approx. 300 g

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

39

Literature

40

System Data Sheet TM 1703 ACP

MC6-007-2

1703 Common
Functions Peripheral Elements according to IEC 60870-5-101/104

DC0-011-2

Data Sheet CM-0842

MC0-021-2

Data Sheet CM-0843

MC0-023-2

TM 1703 ACP, PE-640x/USIO65


MC6-023-2.01, Edition 01.2008

Das könnte Ihnen auch gefallen