PE-640x/USIO65
Peripheral Controller (Ax-PE Bus el/opt)
up to 8 I/O modules
focus on telecontrol
acquisition, conditioning and output
of process data using I/O modules
acc. to IEC 60870-5-101/104
automation
open- and closed-loop control (cycle
time typically 100ms and slower)
binary signals
analog signals (currents, voltages,
temperatures)
binary signals
analog signals (currents, voltages)
MC6-023-2.01
Designation
CM-0843
CM-0842
Connection
Number of Peripheral
Elements
electrical
up to 16
optical
up to 16
Configurations with CM-0843 and CM-0842 can be found in the respective data sheet.
PE-640x/USIO65 is mainly used in telecontrol and automation. The peripheral element is in
charge for process data input and output. For this it is supported by I/O modules:
I/O Module
Designation
Load
DI-6100
170 mW
DI-6101
170 mW
DI-6102
170 mW
DI-6103
170 mW
DI-6104
170 mW
DO-6200
600 mW
DO-6212
800 mW
AI-6300
480 mW
AI-6307
480 mW
AI-6310
480 mW
AO-6380
1900 mW
Module
Designation
Type
Load
PE-6400
---
720 mW
PE-6401
---
typ. 1150 mW
---
typ. 1400 mW
PE-6402
1)
1)
on request only
Module
Type
Designation
Type
Available Power
PS-6620
---
8000 mW
PS-6630
---
8000 mW
PS-6632
---
8000 mW
Up to 8 I/O modules can be installed in addition to the peripheral control module as long as
both
the total load of the I/O modules does not exceed 7000 mW
the total load of the I/O modules and the peripheral control module does not exceed the
power provided by the power supply module
The PE-640x/USIO65 peripheral element communicates via the TM bus with the I/O modules
and through them with the process. Via the Ax 1703 peripheral bus the communication is
done with higher-level basic system element.
Ax 1703
Peripheral Bus
....
....
Peripheral
Control
Module
Power
Supply
Module
8 I/O-Modules, max.
Common Functions
I/O module monitoring, failure management
Signaling via LED's
The functions, specific for each I/O module, are listed in the following.
Footnotes are used to specify the effect of the functions in detail (they are
explained at the bottom of this page)
The functions, specific for each I/O module, are listed in the following.
Footnotes are used to specify the effect of the functions in detail (they are
explained at the bottom of this page)
Telecontrol
the function affects process information which is spontaneously transmitted
t1
Telecontrol
the function delivers (acquisition) spontaneously transmitted process information or is
controlled by such information (output); partly, periodically transmitted information is also
created/required
Automation
the function affects process information which is periodically transmitted
single-point information
acquisition with a resolution of 10ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
determination of the cause of transmission t
spontaneous transmission of changes t
periodical transmission a
double-point information
acquisition with a resolution of 10ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
monitoring intermediate and faulty positions t
determination of the cause of transmission t
reporting switching operations in progress t
breaker tripping detection t
breaker tripping suppression during auto-reclose t
spontaneous transmission of changes t
periodical transmission a
integrated totals via count pulses (via binary inputs of the module) t1
acquisition by firmware with a maximum count frequency of 20Hz
pulse length/pause >20ms/>20ms
revision
power monitoring
inversion
pulse counting
counter value formation
count pulse evaluation
set counter
formation of integrated totals
counter request
interval control
freezed absolute value
freezed relative value
not power-fail safe
integrated total transmission according to IEC 60870-5-101
spontaneous transmission
DI-6102
DI-6103
single-point information
acquisition with a resolution of 1ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
determination of the cause of transmission t
spontaneous transmission of changes t
periodical transmission a
double-point information
acquisition with a resolution of 1ms t
update every 10ms a
(or with the same cycle as the open-/closed-loop control function in the basic system
element, depending on which cycle is larger)
revision ta
power monitoring ta
inversion ta
firmware filter t
bounce suppression t
monitoring intermediate and faulty positions t
determination of the cause of transmission t
reporting switching operations in progress t
breaker tripping detection t
breaker tripping suppression during auto-reclose t
spontaneous transmission of changes t
periodical transmission a
integrated totals via count pulses (via binary inputs of the module) t1
acquisition by firmware with a maximum count frequency of 20Hz
pulse length/pause >2ms/>2ms
revision
power monitoring
inversion
pulse counting
counter value formation
count pulse evaluation
set counter
formation of integrated totals
counter request
interval control
freezed absolute value
freezed relative value
not power-fail safe
integrated total transmission according to IEC 60870-5-101
spontaneous transmission
AI-6300
AI-6307
AI-6310
temperatures t1
resolution
when transferring temperatures
(a) Pt100: 0.20C / 0.36F / (90 m
revision
noise rejection
automatic calibration
calibration for 2-wire technique
smoothing
adaptation
temperature value (C, F)
conversion using implemented curves
resistance ()
change monitoring
spontaneous transmission of changes
pulse
checked output of pulse commands
1-pole
single, double and regulating step commands
command output (OC)
basic application functions and procedures according to IEC 60870-5-101/104
formal check
direct command
select and execute command ("select/execute")
retry suppression
1-out-of-n check
control location check
command locking
synchronization
revision
command output time
settable
dependent on the process
return information monitoring
command prolongation
switching sequences
command output for the auto-reclose function
if outputs of the module are used for pulse commands, no outputs of the same
module can be used for binary information output
DO-6212
pulse commands t1
checked output of pulse commands
1-pole, 1-pole, 2-pole
cannot be mixed
single, double and regulating step commands
command output (OC)
basic application functions and procedures according to IEC 60870-5-101/104
formal check
direct command
select and execute command ("select/execute")
retry suppression
1-out-of-n check
control location check
command locking
synchronization
revision
command output time
settable
dependent on the process
return information monitoring
command prolongation
switching sequences
command output for the auto-reclose function
if outputs of the module are used for pulse commands, no outputs of the same
module can be used for binary information output
AO-6380
10
Further Functions
for messages and pulse commands, which are acquired or output on the
peripheral element itself
for messages and pulse commands, which are acquired or output on different
peripheral elements of the same basic system element
predefined assignment
for messages and pulse commands, which are acquired or output on the
peripheral element itself
11
PE-6400
12
Technical Specifications
Processor and Memory
Processor
80C251SQ-16, 16 MHz
Program memory
Main memory
RAM 64 kByte
Parameter memory
Power Supply
Operating voltage
Dimensions
Weight
Approx. 135 g
13
PE-6401
14
Technical Specifications
Processor and Memory
Processor
80C251SQ-16, 16 MHz
Program memory
Main memory
RAM 64 kByte
Parameter memory
Interfaces
1 interface to the BSE
(Ax 1703 peripheral bus, optical,
full duplex)
(X6)
Optical interface
(duplex plastic optical fibre)
Optical interface
Transmission rate 16Mbps
Securing of data, hamming distance D=4
Specification see below
Type
TODX295
Optical fibre:
(+) Glass fibre (PCF fibre)
(Toshiba TOSLINK)
(10dB/km)
16Mbps
Transmitter (660nm):
Power launched into the fibre
(+)
max
min
-14dBm
-20dBm
Receiver (660nm):
Received power:
max
-9dBm
min
-28dBm
0 .. 200m
Power Supply
Operating voltage
Dimensions
Weight
Approx. 160 g
TOCP201
(Toshiba TOSLINK)
15
PE-6402
16
Technical Specifications
Processor and Memory
Processor
80C251SQ-16, 16 MHz
Program memory
Main memory
RAM 64 kByte
Parameter memory
Interfaces
2 interfaces to the BSE
(Ax 1703 peripheral bus, optical,
full duplex)
(X6, X7)
Optical interface
(duplex plastic optical fibre)
Optical interface
Transmission rate 16Mbps
Securing of data, hamming distance D=4
Specification see below
Type
TODX295
Optical fibre:
(+) Glass fibre (PCF fibre)
(Toshiba TOSLINK)
(10dB/km)
16Mbps
Transmitter (660nm):
Power launched into the fibre
(+)
max
-14dBm
min
-20dBm
Receiver (660nm):
Received power:
max
-9dBm
min
-28dBm
0 .. 200m
Power Supply
Operating voltage
Dimensions
Weight
Approx. 170 g
TOCP201
(Toshiba TOSLINK)
17
DI-6100
18
Technical Specifications
Binary Inputs
16 binary inputs
Filter time
Nominal voltages
24/48/60 VDC
Operating points
12 V
16 V
Rated current
1.01.5 mA (at 18 .. 78 V)
Input circuits
1878 VDC
The circuits are operated by means of an external voltage.
2 ms
3 ms
"logic 0"
"logic 1"
Power Supply
Operating voltage
Dimensions
Weight
Approx. 225 g
19
DI-6101
20
further functions
return information to pulse command
assignment
Technical Specifications
Binary Inputs
16 binary inputs
Filter time
Nominal voltages
110/220 VDC
Operating points
55 V
82.5 V
Rated current
Input circuits
82250 VDC
The circuits are operated by means of an external voltage.
2 ms
3 ms
"logic 0"
"logic 1"
Power Supply
Operating voltage
Dimensions
Weight
Approx. 225 g
21
DI-6102
22
Technical Specifications
Binary Inputs
16 binary inputs
Filter time
Nominal voltages
24/48/60 VDC
Operating points
12 V
16 V
Rated current
Input circuits
1878 VDC
The circuits are operated by means of an external voltage.
2 ms
3 ms
"logic 0"
"logic 1"
Power Supply
Operating voltage
Dimensions
Weight
Approx. 225 g
23
DI-6103
24
Technical Specifications
Binary Inputs
16 binary inputs
Filter time
Nominal voltages
110/220 VDC
Operating points
55 V
82.5 V
Rated current
Input circuits
82250 VDC
the circuits are operated by means of an external voltage.
2 ms
3 ms
"logic 0"
"logic 1"
Power Supply
Operating voltage
Dimensions
Weight
approx. 225 g
25
DI-6104
26
further functions
return information to pulse command
assignment
Technical Specifications
Binary Inputs
16 binary inputs
Filter time
Nominal voltages
220 VDC
Operating points
110 V
165 V
Rated current
Input circuits
165250 VDC
The circuits are operated by means of an external voltage.
2 ms
3 ms
"logic 0"
"logic 1"
Power Supply
Operating voltage
Dimensions
Weight
Approx. 225 g
27
DO-6200
28
Technical Specifications
Binary Outputs
16 binary outputs
(transistor)
24/48/60 VDC
Voltage range
1878 VDC
Nominal current
(resistive load)
at 1878 VDC
(only 1 output active)
6W
at 24 VDC
12 W at 48 VDC
15 W at 60 VDC
70.2 W
Overload proof
No
10 A
Switching cycles
Unlimited
Switching frequency
Max. 100 Hz
< 0.5 V
at 78 VDC
current limitation
If the current limitation operates,
current is cut off after 10 s
Cyclic reclosing
break time
300 s
make time
10 s
at 0.25 A
Power Supply
Operating voltage
Output circuits
Dimensions
Weight
Approx. 260 g
29
DO-6212
8 relay outputs
Galvanically insulated
Switching voltage 24-220 VDC/230 VAC
The outputs can switch dc and ac voltages
Removable screw terminals
Indication of function and states of the outputs
via LEDs
output functions
pulse commands
binary information output
pulse commands and binary information
output cannot be mixed on the same module
30
Technical Specifications
Binary outputs
8 binary outputs
(relay)
8 outputs, potential-free
Galvanical insulation
Nominal voltage
24/48/60/110/220 VDC
110/230 VAC
2A
5A
250 VDC
253 VAC
Switching capacity
DC voltage
for 1 minute
Min. 50 mW at 5 VDC
Max. acc. to diagram
AC voltage
Max. 1250 VA
Max. 500 VA
Switching cycles
3x104
Output circuits
Power Supply
Operating voltage
Dimensions
Weight
Approx. 265 g
31
AI-6300
32
Technical Specifications
Analog Inputs
4 analog inputs
Measuring ranges
Current measurement
Voltage measurement
Overrange
Resolution
0.013%
0.025%
at 20 mA
at 10 V
Accuracy
0.15%
0.4%
0.5%
at 25C
at 050C
at 2070C
Input impedance
122.5
11.3 k
at 20 mA
at 10 V
Current inputs
min. 70 dB
min. 90 dB
Voltage inputs
min. 73 dB
min. 90 dB
-200+20 mA
-100+10 V
typ. 2%
0 dB
(10 Hz7.5 kHz)
+20 dB/decade
(7.5 kHz1 MHz)
Voltage inputs
0 dB
(10 Hz7.5 kHz)
+20 dB/decade
(7.5 kHz1 MHz)
Input circuits
Power Supply
Operating voltage
Dimensions
Weight
Approx. 225 g
33
AI-6307
34
Technical Specifications
Analoge Inputs
4 analog inputs
Measuring ranges
Current measurement
Voltage measurement
Overrange
Resolution
0.013%
0.025%
at 5 mA
bei 10 V
Accuracy
0.15%
0.4%
0.5%
at 25C
at 050C
at 2070C
Input impedance
490
11.3 k
at 5 mA
at 10 V
Current inputs
min. 70 dB
min. 90 dB
Voltage inputs
min. 73 dB
min. 90 dB
Current inputs
0 dB
+20 dB/decade
Voltage inputs
0 dB
+20 dB/decade
-50+5 mA
-100+10 V
typ. 2%
Input circuits
Power Supply
Operating voltage
Dimensions
Weight
Approx. 225 g
35
AI-6310
36
Technical Specifications
Analog Inputs
4 analog inputs
Measuring range
Resistance measurement
Overrange
typ. 20%
Input impedance
Approx. 2 M
Resolution
11 m
Noise rejection
Conversion time
120 ms
100 ms
180 ms
Accuracy
0.19%
0.21%
at 25C
at 050C
2 mA
max. 40
> 100 dB
> 70 dB
> 100 dB
Input circuits
Power Supply
Operating voltage
Dimensions
Weight
Approx. 235 g
37
AO-6380
38
4 outputs
output functions
setpoint values by means of currents and
voltages
Technical Specifications
Analog Outputs
4 analog outputs
Current output
Voltage output
Resolution
0.025%
Settling time
1 ms
Accuracy
0.3%
0.4%
0.7%
Output circuits
at 20 mA, 10 mA, 10 V
at 25 C
at 050 C
at -2070 C
Power Supply
Operating voltage
Dimensions
Weight
Approx. 300 g
39
Literature
40
MC6-007-2
1703 Common
Functions Peripheral Elements according to IEC 60870-5-101/104
DC0-011-2
MC0-021-2