Beruflich Dokumente
Kultur Dokumente
Calculation techniques
A naturally ventilated building consists of a series of openings through which air will
pass. These openings include:
Purpose provided openings (e.g vents and windows as described in chapter A3);
Adventitious infiltration openings.
Taking all the flow paths, the conservation of mass requires a flow balance between
the ingoing and outgoing airflow. This is expressed by:
j
Q
i 1
(kg/s)
(A8.1)
where:
i = Density of air flowing through flow path i (kg/m3);
Qi = Volume airflow rate through flow path i (m3/s).
The air density, i, of incoming air is given by that of the value for the outside air
while, for outflowing air, it is given by that of the internal air density. If the density
differences between the internal and external air masses are negligible in comparison
to the magnitude of the overall density of air then density term may be ignored and,
instead, calculation can be considered in terms of conservation of volume flow rather
than mass flow. Working in terms of volume flow rate rather than mass flow rate
helps simplify iterative calculation and presents results in the familiar format of
volume flow.
Thus Equation (A8.1) above is simplified to:
(A8.2)
j
i 1
Qi 0
To determine the flow rate through each flow path, it is necessary to express Qi by
the chosen flow equation (in this module the popular power law equation is used
although alternative equations such as the quadratic approach are equally
applicable). The power law equation gives:
(A8.3)
j
C p
i 1
ni
Where:
Ci and ni = the flow coefficient and flow exponent of the ith flow path
respectively;
(pi)
= the pressure difference acting across the path.
The pressure difference (pi) is made up of the wind and stack pressure acting on
the outside of the opening and the internal pressure of the space, pint. This internal
pressure adjusts itself to preserve flow balance and is the unknown that must be
determined in order to calculate the flow through each opening.
For the airflows to add up to zero therefore some flows must be positive (air coming
into the building) and others must be negative (air leaving the building). This means,
also, that some ps will be positive and some ps will be negative. Unfortunately it
is not possible to raise a negative p to the power n and therefore some
rearrangement of the Equation 8.3 above is needed. Incorporating this
rearrangement and replacing pi by pi - pint gives:
C
i 1
pi pint
(Term 1) (Term 2)
ni
pi pint
pi pint
(Term 3)
In this rearrangement, Term 2 is always positive (and hence can be raised to the
power n) while term three becomes either +1 or -1 and hence defines the flow
direction.
any number of flow paths, terminating within each internal zone, can be
selected to represent leakage openings in the building envelope.
Additionally paths are selected to represent leakage openings across
internal zones. For the m'th such zone with a total of j flow paths, the mass
flow balance is given by:
jm
im 1
im im
pim pm
nim
pim pm
pim pm
jm
(
m 1 im 1
im im
pim pm
nim
pim pm
pim pm
) 0
Unlike the 'single zone' approach, where there was only one internal
pressure to determine, there are now many values. This adds considerably
to the complexity of the numerical solution method.
Q k.A.Uref
Where,
A is the area of opening and
Uref is the speed of the undisturbed wind at the height of the
building containing the space under consideration.
In practice the value of k will depend upon a number of factors,
including wind direction relative to the faade containing the
opening, surrounding structures and any local obstruction at the
surface of the building in proximity of the opening. However, a
conservative value for design purposes may be taken as 0.025.
The basic equations for stack effect set out in Section A6.1 can be
applied to flow through a single opening. The neutral plane (see
Figure A6.1) occurs within the opening and, if internal air
temperature is higher than outside air, air flow out above the
opening and in at the lower part of the opening. The position of the
neutral plane is determined by the equality of the mass flow in and
mass flow out. For a plane rectangular opening of height, h, and
area A, the ventilation rate is given by the following equation;
A .h.g
Q Cd . .
3 273
0.5
where,
is the difference between internal and external air temperature
q is the mean of internal and external air temperatures
g is the gravitational constant
Cd is the discharge coefficient of the opening (see Chapter A4)
Area of opening,
A2 = 0.1 m2
A2
ext = 10C
int = 20C
Building Height
= 4.5 m
4m
Area of opening, A1
= 0.1 m2
A1
1m