Air Treatment Division

DATA & FACTS

GEA Close Control


T-Range Aerial values always on the level

Description

GEA Close Control


T-Range

The T-Range .......................................................................................3


Upflow and Downflow Versions
Direct Expansion and Chilled Water Units .............................................................3
Key to Type Codes .................................................................................................3

Energy Saving Options .....................................................................4


Dimensions and Weights ...................................................................5
Dimensions and Weights D/U 3 42 ...................................................................5
Dimensions and Weights D/U 48 - 83 ..................................................................6

Service Entry / Access ......................................................................5


Guide Specification ...........................................................................8
Typical Airflow Arrangements ........................................................ 11
General Details ................................................................................ 11
Cooling Performance ......................................................................15
Cooling Performance Models 3 19 ..................................................................15
Cooling Performance Models 21 42 ................................................................16
Cooling Performance Models 48 83 ................................................................17

Electrical Details .............................................................................. 18


"X" Version.............................................................................................................18
"A" Version.............................................................................................................19
"W" and "F" Versions.............................................................................................20
"C" Version ............................................................................................................21

Schematic Diagrams ....................................................................... 22


"X" Version.............................................................................................................22
"A" Version.............................................................................................................23
"W" Version............................................................................................................24
"F" Version.............................................................................................................25
"C" Version ............................................................................................................26

Ancillaries and Options ................................................................... 27

PR-2006-0295-GB y Subject to modifications y Status 10/2007

The Range

GEA Close Control


T-Range

Key to Type Codes

Upflow and Downflow Versions


Direct Expansion and Chilled Water Units
The T Range comprises nineteen (19) models, in six (6) cabinet sizes, with nominal
capacities from 3 kW to 80 kW in the following versions: -

X: Split System using Denco Condensing Units.


A: Air Cooled DX System with inbuilt compressor(s) and using Denco DCRA
Condensers.
W: Water Cooled DX System with inbuilt compressor(s) and Water Cooled
Condensers.
F: Ambicool System.
C: Chilled Water System.

Key to Type Codes


Example:

U 28 A V G H
H=
G=
V=
A=

28 =

U=

Humidifier fitted
Front Grille Return [Upflow only not on U48 - U83]
(as opposed to underfloor return)
Variable Refrigerant Flow (VRF)
X - Split System
A - Air Cooled System
W - Water Cooled System
F - Ambicool System
D - Combicool system
C - Chilled Water System
Unit Size:
3, 4, 5,
8, 10, 12,
17, 19, 21, 23, 28,
32, 37, 42
48, 53
63, 73 and 83
(models available dependent on System)
Upflow (D = Downflow)

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Energy Saving Options

GEA Close Control


T-Range

T Range air conditioning units incorporate all of the energy/cost saving benefits for
which Denco products are renowned. These include:
Ambicool (Glycol freecooling system) - "F" Version
(not available on models 48 83)
This substantially reduces annual energy consumption, and
consequently costs, by exploiting low average ambient
temperatures to provide partial or full freecooling. It is very
unusual to experience the design summer ambient for any
length of time, and external temperatures are generally
considerably less for much of the year. This allows the
drycooler to produce glycol at lower temperatures.
When the glycol is colder than the room air, it is passed
through the economy coil before reaching the condenser,
picking up some heat directly from the room rather than via
the refrigeration system. Under conditions such as this, the
compressor run time is reduced, thereby saving energy. As
an example, some degree of freecooling is usually
available for 70% of the year in northern Europe, giving
very substantial running cost savings.
Variable Refrigerant Flow (VRF) - "V" Option
This provides various compressor options for efficient partload performance, with exceptional economy.
Full Cooling Load
Both compressors running to circulate the full design
refrigerant flow in order to achieve specified maximum
cooling capacity. The scroll compressor coefficient of
performance (COP) is typically 3.5.
Part Load Operation
Lead compressor only running to circulate approximately
60% of the refrigerant flow. Evaporator and condenser are
both oversized under this condition, causing increase in
suction pressure and a reduction in discharge pressure.
Resultant part-load COP increases to typically 5.0.
Secondary benefits include reduced temperature swing and
increased compressor reliability caused by reduced cycling
and an optional two-stage high-pressure trip. Lower inrush
current and inbuilt redundancy is also provided by dual
compressors and reduced humidifier run time due to the
very high sensible heat ratio achieved at the higher
evaporating temperatures. Payback period is typically less
than one year.

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Dimensions and Weights D/U 3 - 42

GEA Close Control


T-Range

Unit Weights - kgs


Model

"X"

"A"

"W"

"F"

"C"

D/U3-5

135

165

175

N/A

140

D / U 8 - 12

210

255

270

305

215

D / U 17 - 28

345

445

460

505

355

D / U 32 - 42

420

520

535

590

430

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Dimensions and Weights D/U 48 - 83

GEA Close Control


T-Range

Unit Weights - kgs

Model

"X"

"A"

"W"

"F"

"C"

D / U 48 - 53

660

860

890

N/A

680

D / U 63 - 83

810

1010

1040

N/A

830

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Service Entry / Access

GEA Close Control


T-Range

The T Range of air conditioning units has been designed to be completely front
access for service/maintenance via the front hinged/removable doors. Therefore, no
allowance for access to the ends or back is necessary, although the end panels can
be removed in-situ if required.

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Guide Specification

GEA Close Control


T-Range

Cabinet
The cabinets shall be attractively designed having bevelled corners with flush fitting
curved panels. Units shall have a rigid frame, manufactured from non corroding
Aluzink, with hinged curved front panel(s) to provide access for installation and
servicing. Panels shall be lined with class "O" non eroding insulation material with
both thermal and acoustic properties. External panels shall be manufactured from
pre-coated steel, colour Grey (RAL number 7024).

Cooling Coil
The coils shall be multi row constructed from 3/8" O/D copper tubes with
mechanically bonded aluminium fins. Direct expansion coils shall have internal
grooving for optimum heat transfer. The coil face area shall be maximised to ensure
high sensible heat ratio and low airside pressure drop, thereby minimising fan power
and noise level. A stainless steel drain tray shall be included to ensure efficient
removal of the condensate, via a factory fitted trap.
-

DX: Units shall have one, two or four refrigeration circuits (dependent upon
model), inclusive of liquid distributor, expansion valve, solenoid valve, sight glass
and filter drier, and these components shall be housed in the cabinet.
C: Units shall be fitted with a modulating 3 way valve having manual override
facility with water pressure / temperature test points, and these components shall
be housed in the cabinet.

Fans
T Range models 3 to 5 shall be fitted with one fan, which shall be single inlet
backward curved centrifugal, and shall be direct driven by an integral motor. A
differential pressure switch shall be fitted to monitor airflow, failure of which shall
result in an alarm and automatic disabling of all functions. The fan motor shall be
single speed, the final airflow therefore depending on exact static pressure
requirements.
T Range models 8 to 42 shall be fitted with one, two or three fans, whilst models 48
to 83 shall be fitted with four or six fans, depending on unit size. The fans shall be
double inlet, double width with forward curved impeller, and shall be direct driven by
an integral motor. A differential pressure switch (8-42) and current monitoring relay
(48-83) shall be fitted to monitor airflow, failure of which shall result in an alarm and
automatic disabling of all functions. Fan motors shall be three speed. HIGH or
MEDIUM speed shall be factory selected, depending on airflow and static pressure
requirement, and LOW speed shall be assigned for dehumidification mode.

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Guide Specification

GEA Close Control


T-Range

Electric Heaters
Electric heaters shall have rigid Incoloy sheathed elements with stainless steel
finning balanced over three phases and rated to operate at black heat. Control shall
be in one or two stages, each stage being protected by a high temperature safety
cut-out.

Filtration
The filters shall have an efficiency of 30 % ASHRAE 52/76 Eurovent 4/5 arrestance
value 90 % (G4). They shall be fitted in the return air stream, held by quick release
retaining clips, and be accessible from the front of the unit. A differential pressure
switch shall be fitted which, through the alarm facility in the microprocessor
controller, shall indicate when the filters need changing.

Water Cooled Condensers


The condenser shall be a compact brazed plate heat exchanger having a multiplicity
of parallel stainless steel pressed plates. The construction shall give high turbulent
flows resulting in a compact heat exchanger form with low pressure drops.

Humidifier
The humidifier shall be of the electrode boiler type, located in the bottom of the unit.
Features shall include proportional steam output and microprocessor control with
alarms and diagnostic facilities. The control system shall allow the use of a wide
range of mains water conditions and optimise drain down frequency for maximum
operational economy.

Compressor and Safety Controls


Robust fully hermetic scroll compressor(s) shall be located either in the base of the
unit on "A", "W" and "F" systems or the outdoor condensing unit on "X" systems. The
compressor(s) shall be resiliently mounted on a robust frame, which assists to
minimise noise and vibration transmission to the structure. The compressor(s) shall
be fitted with back seating isolating valves together with crankcase heater ("X"
systems only) and oil level sight glass on larger models. Protection shall be provided
by an internal self-setting overload device and pressure relief valve.
An external adjustable high pressure cut off switch, with manual reset facility shall be
provided for high pressure protection, in addition to the internal devices. To protect
primarily against loss of refrigerant charge, an adjustable low pressure switch shall
also be provided, which includes an automatic reset facility.
A low pressure Alarm delay function is fitted to facilitate low ambient start condition
as standard.

Dehumidification
This shall be achieved by switching on a single stage of cooling and automatic
selection of low fan speed (models 8 to 42).

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Guide Specification

GEA Close Control


T-Range

Electrical Panel
The electrical switchgear shall be contained in a cubicle located in the top of the unit,
and shall include:
- Controller baseboard and modules (if applicable)
- MCB's and contactors for fans, heaters, humidifier and compressors as
appropriate
- MCB's for remote condensing units (if applicable)
- MCB's plus pressure operated on off switches for remote condensers (if
applicable)
Cabling shall be colour coded and numbered, and neatly run in trunking segregating
high and low voltages. All wiring shall comply with BS EN 60204 Part 1.

Microprocessor Controls
All units shall be fitted, as standard, with a C3-05 advanced microprocessor controls
system, designed by Denco. This shall provide maximum economy of operation, a
comprehensive intelligent alarm system and a wide range of information for
operators and service engineers. All information shall be presented in a user friendly
format with tamper proof setting up arrangements.
In addition to precise control of temperature and humidity, the system shall include
the following features:
- A liquid crystal semi - graphical display indicating unit function via icons,
displaying control conditions and historic logging of temperature and humidity
conditions.
- Coded security access for set point parameter adjustment
- Programmable stage delays, to minimise inrush currents
- A comprehensive alarm system. Alarms shall be memorised and displayed in the
order in which they occur in order to aid fault diagnosis
- Programmed set points and parameters shall be held in a non volatile memory,
therefore being safeguarded upon power failure
- Denco Net functions are a standard feature within the controller.
- Various third party communication and interface options are available which
connect direct to the C3-05 controller.

10

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Typical Airflow Arrangements

GEA Close Control


T-Range

General Details

Section "A" Downflow, into raised floor. Return from room or ceiling.
Section "B" Upflow, with horizontal discharge plenum (as shown) or room/ceiling discharge, and front grille return (not
available on models 48 83).
Section "C" Upflow, with ceiling duct extension and underfloor return.

General Details
U / D - All Versions

3-5

8 - 12

17 - 28

32 - 42

48 - 53

63 - 83

Coil Face Area

m2

0.200

0.414

0.864

1.382

1.728

2.764

No. of Fans
Air Volume
Fan Heat Absorbed

m3/s
m3/hr
kW

1
0.415
1490
0.27

1
1.00
3600
1.17

2
2.17
7810
2.86

3
3.3
11880
4.37

4
4
14400
5.37

6
6.1
21960
8.24

Electric Reheat:
No. of Steps
Capacity

kW

1
3.0

1
6.0

2
12.0

2
12.0

2
12.0

2
12.0

Humidifier Capacity
Power

kg/hr
kW

3.0
2.3

3.0
2.3

3.0
2.3

3.0
2.3

3.0
2.3

3.0
2.3

Filters (Standard G4):


No. of Pieces
Length
Width
Depth

mm
mm
mm

1
455
455
50

2
442
505
50

2
885
505
50

3
885
540
50

4
885
505
50

6
885
540
50

PR-2006-0295-GB y Subject to modifications y Status 10/2007

11

General Details

GEA Close Control


T-Range

10

12

17

19

3/4
3/8
15
22

3/4
3/8
15
22

3/4
3/8
15
22

7/8
1/2
15
22

7/8
1/2
15
22

1-1/8
1/2
15
22

1-1/8
5/8
15
22

1-1/8
5/8
15
22

CT18
1

CT18
1

CT22
1

CS40
1

CM48
1

CM61
1

CP72
1

CP81
1

"X" Versions
Suction Line
Liquid Line
Humidifier Feed
Drain

ins
ins
mm
mm

C.U. Type
No. fitted

"A" Versions
Discharge Line
Liquid Line
Humidifier Feed
Drain

ins
ins
mm
mm

N/A

N/A

1/2
3/8
15
22

3/4
1/2
15
22

3/4
1/2
15
22

3/4
1/2
15
22

7/8
5/8
15
22

7/8
5/8
15
22

Compressor
No. fitted
A/C Condenser *
No. fitted

ZR
DCRA
-

N/A

N/A

22
1
08-6
1

34
1
13-6
1

48
1
21-6
1

61
1
21-6
1

61
1
26-6
1

72
1
26-6
1

Cond Water In
Cond Water Out
Humidifier Feed
Drain

mm
mm
mm
mm

N/A

N/A

22
22
15
22

28
28
15
22

28
28
15
22

28
28
15
22

35
35
15
22

35
35
15
22

Compressor
Compr. Type
No. fitted
W/C Condenser
No. fitted

ZR
-

N/A

N/A

22
Scroll
1
B8/20
1

34
Scroll
1
B8/30
1

48
Scroll
1
B8/30
1

61
Scroll
1
B8/30
1

61
Scroll
1
B10/30
1

72
Scroll
1
B10/30
1

"W" Versions

F" Versions
Coolant In
Coolant Out
Humidifier Feed
Drain

mm
mm
mm
mm

N/A

N/A

N/A

28
28
15
22

28
28
15
22

28
28
15
22

35
35
15
22

35
35
15
22

Compressor
No. fitted
W/C Condenser
No. fitted

ZR
-

N/A

N/A

N/A

34
1
B8/30
1

48
1
B8/30
1

61
1
B8/30
1

61
1
B10/30
1

72
1
B10/30
1

"C" Versions
Chilled Water In
Chilled Water Out
Humidifier Feed
Drain

mm
mm
mm
mm

N/A

N/A

22
22
15
22

N/A

N/A

28
28
15
22

N/A

N/A

Valve Size
Valve kv

ins
m3/hr

N/A

N/A

1/2"
2.5

N/A

N/A

3/4"
6.3

N/A

N/A

Note:
Variable Refrigerant Flow option NOT available on models 3 - 19.
*
- Quiet / Residential Condensers are available as an alternative to the Standard versions stated.

12

PR-2006-0295-GB y Subject to modifications y Status 10/2007

General Details

GEA Close Control


T-Range

21

23

28

32

37

42

"X" Versions
Suction Line
Liquid Line
Humidifier Feed
Drain

ins
ins
mm
mm

1-1/8
5/8
15
22

1-1/8
5/8
15
22

1-3/8
5/8
15
22

1-3/8
3/4
15
22

1-3/8
3/4
15
22

1-3/8
3/4
15
22

C.U. Type
No. fitted

CL90
1

CL11
1

CL12
1

CL12
1

CL16
1

CL19
1

"A" Versions
Discharge Line
Liquid Line
Humidifier Feed
Drain

ins
ins
mm
mm

7/8
5/8
15
22

7/8
5/8
15
22

1-1/8
5/8
15
22

1-1/8
3/4
15
22

1-1/8
3/4
15
22

1-1/8
3/4
15
22

Compressor
No. fitted
A/C Condenser *
No. fitted

ZR
DCRA
-

81
1
32-6
1

48
2 **
32-6
1

61
2 **
32-6
1

61
2 **
50-6
1

72
2 **
50-6
1

81
2 **
50-6
1

"W" Versions
Cond Water In
Cond Water Out
Humidifier Feed
Drain

mm
mm
mm
mm

35
35
15
22

35
35
15
22

35
35
15
22

42
42
15
22

42
42
15
22

42
42
15
22

Compressor
No. fitted
W/C Condenser
No. fitted

ZR

81
1
B10/30
1

48
2 **
B10/30
1

61
2 **
B10/30
1

61
2 **
B10/40
1

72
2 **
B10/40
1

81
2 **
B10/40
1

"F" Versions
Coolant In
Coolant Out
Humidifier Feed
Drain

mm
mm
mm
mm

35
35
15
22

35
35
15
22

35
35
15
22

42
42
15
22

42
42
15
22

42
42
15
22

Compressor
No. fitted
W/C Condenser
No. fitted

ZR

81
1
B10/30
1

48
2 **
B10/30
1

61
2 **
B10/30
1

61
2 **
B10/40
1

72
2 **
B10/40
1

81
2 **
B10/40
1

"C" Versions
Chilled Water In
Chilled Water Out
Humidifier Feed
Drain

mm
mm
mm
mm

N/A

N/A

35
35
15
22

N/A

N/A

42
42
15
22

Valve Size
Valve kv

ins
m3/hr

N/A

N/A

1"
10

N/A

N/A

1"
16

Note:
Variable Refrigerant Flow option NOT available on model 21.
* Quiet / Residential Condensers are available as an alternative to the Standard versions stated.
** - Variable Refrigerant Flow as Standard

PR-2006-0295-GB y Subject to modifications y Status 10/2007

13

General Details

GEA Close Control


T-Range

48

53

63

73

83

"X" Versions
Suction Line
Liquid Line
Humidifier Feed
Drain

ins
ins
mm
mm

1-1/8
5/8
15
22

1-1/8
5/8
15
22

1-3/8
3/4
15
22

1-3/8
3/4
15
22

1-3/8
3/4
15
22

C.U. Type
No. fitted

CL11
2

CL12
2

CL12
2

CL16
2

CL19
2

Discharge Line
Liquid Line
Humidifier Feed
Drain

ins
ins
mm
mm

1-1/8
5/8
15
22

1-1/8
5/8
15
22

1-1/8
3/4
15
22

1-1/8
3/4
15
22

1-1/8
3/4
15
22

Compressor
No. fitted
A/C Condenser *
No. fitted

ZR
DCRA
-

48
4 **
32-6
2

61
4 **
32-6
2

61
4 **
32-6
2

72
4 **
50-6
2

81
4 **
50-6
2

"A" Versions

"W" Versions
Cond Water In
Cond Water Out
Humidifier Feed
Drain

mm
mm
mm
mm

2 x 35
2 x 35
15
22

2 x 35
2 x 35
15
22

2 x 42
2 x 42
15
22

2 x 42
2 x 42
15
22

2 x 42
2 x 42
15
22

Compressor
No. fitted
W/C Condenser
No. fitted

ZR

48
4 **
B10/30
2

61
4 **
B10/30
2

61
4 **
B10/40
2

72
4 **
B10/40
2

81
4 **
B10/40
2

"C" Versions
Chilled Water In
Chilled Water Out
Humidifier Feed
Drain

mm
mm
mm
mm

N/A

54
54
15
22

N/A

N/A

54
54
15
22

Valve Size
Valve kv

ins
m3/hr

N/A

1"
25

N/A

N/A

2"
40

Note:
* Quiet / Residential Condensers are available as an alternative to the Standard versions stated.
** Variable Refrigerant Flow as Standard

14

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Cooling Performance Models 3 to 19

GEA Close Control


T-Range

All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static
and Air On at 24 C, 45 %RH.

Airflow

10

12

17

19

m /s
m3/hr

0.30
1080

0.35
1260

0.415
1490

0.70
2520

0.80
2880

1.00
3600

1.40
5040

1.60
5760

kW
kW
-

4.6
4.1
0.89

4.8
4.4
0.93

5.6
5.1
0.92

9.5
8.7
0.92

11.6
10.0
0.88

13.4
11.6
0.87

17.6
16.7
0.95

19.4
18.4
0.95

kW
kW
-

N/A

N/A

5.6
5.1
0.91

8.7
8.3
0.95

12.1
10.2
0.86

14.1
11.9
0.85

16.1
15.6
0.86

18.3
17.6
0.96

kW
kW
-

N/A

N/A

5.7
5.2
0.90

8.7
8.3
0.95

11.7
10.1
0.86

13.9
11.7
0.85

15.7
15.2
0.97

18.0
17.3
0.96

kW
kW
-

N/A

N/A

N/A

7.9
7.6
0.97

10.7
9.7
0.90

12.6
11.1
0.88

14.1
14.0
0.99

16.3
16.0
0.98

kW
kW
l/s
kPa

N/A

N/A

5.8
5.4
0.92
0.279
49.7

N/A

N/A

13.9
12.5
0.90
0.664
57.8

N/A

N/A

"X" Version 1
Total
Sensible
S.H.R.
"A" Version 2
Total
Sensible
S.H.R.
"W" Version 3
Total
Sensible
S.H.R.
"F" Version 4
Total
Sensible
S.H.R.
"C" Version 5
Total
Sensible
S.H.R.
CW Flow Rate
Unit P.D

Refrigerant R407C used as standard on DX units.


Notes:
1. "X" performances are NETT and based on:
(a) Standard matching Condensing Units (alternatives available, enquire for details).
(b) 1.0 C suction line loss.
(c) 32 C ambient temperature.
2. "A" performances are NETT and based on:
(a) Standard matching A/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 32 C ambient temperature.
3. "W" performances are NETT and based on:
(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) Condenser water in 30 C, temperature rise 8 C.
4. "F" performances are NETT and based on:
(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 25 % ethylene glycol solution coolant in 40 C, temperature rise 6 C.
5. "C" performances are GROSS and based on:
(a) Standard coil with chilled water in 7C, temperature rise 5 C

PR-2006-0295-GB y Subject to modifications y Status 10/2007

15

Cooling Performance Models 21 to 42

GEA Close Control


T-Range

All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static
and Air On at 24 C, 45 %RH.

Airflow

21

23

28

32

37

42

m /s
3
m /hr

1.80
6480

2.00
7200

2.17
7810

2.50
9000

2.90
10440

3.30
11880

kW
kW
-

23.0
21.0
0.92

26.4
23.2
0.89

29.2
25.0
0.87

31.2
29.5
0.95

36.1
33.4
0.93

41.3
37.0
0.91

kW
kW
-

20.7
19.7
0.95

23.8
22.1
0.93

27.2
24.1
0.89

31.5
29.7
0.94

35.7
33.2
0.93

39.2
36.2
0.92

kW
kW
-

20.1
19.3
0.96

23.6
22.0
0.93

27.6
24.3
0.88

30.0
28.6
0.95

34.4
32.5
0.95

38.2
35.7
0.94

kW
kW
-

18.1
17.7
0.98

21.2
20.4
0.96

24.9
23.0
0.92

27.0
26.3
0.97

31.2
30.1
0.96

34.4
32.9
0.96

kW
kW
l/s
kPa

N/A

N/A

28.7
26.4
0.92
1.372
65.6

N/A

N/A

45.4
41.3
0.91
2.171
79.8

"X" Version 1
Total
Sensible
S.H.R.
"A" Version 2
Total
Sensible
S.H.R.
"W" Version 3
Total
Sensible
S.H.R.
"F" Version 4
Total
Sensible
S.H.R.
"C" Version 5
Total
Sensible
S.H.R.
CW Flow Rate
Unit P.D

Refrigerant R407C used as standard on DX units.


Notes:
1. "X" performances are NETT and based on:
(a) Standard matching Condensing Units (alternatives available, enquire for details).
(b) 1.0 C suction line loss.
(c) 32 C ambient temperature.
2. "A" performances are NETT and based on:
(a) Standard matching A/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 32 C ambient temperature.
3. "W" performances are NETT and based on:
(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) Condenser water in 30 C, temperature rise 8 C.
4. "F" performances are NETT and based on:
(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 25 % ethylene glycol solution coolant in 40 C, temperature rise 6 C.
5. "C" performances are GROSS and based on:
(a) Standard coil with chilled water in 7 C, temperature rise 5 C.
.

16

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Cooling Performance Models 48 to 83

GEA Close Control


T-Range

All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static
and Air On at 24 C, 45 %RH.

Airflow

48

53

63

73

83

4.0
14400

4.34
15620

5.00
18000

5.80
20880

6.60
23760

kW
kW
-

52.8
46.4
0.89

58.5
49.9
0.87

62.5
59.0
0.95

72.3
66.7
0.93

78.7
74.1
0.91

kW
kW
-

47.7
44.3
0.94

54.6
48.3
0.90

63.3
59.4
0.95

71.5
66.4
0.94

78.7
72.4
0.93

kW
kW
-

47.1
44.0
0.94

55.3
48.6
0.89

60.2
57.3
0.96

68.9
65.1
0.95

76.7
71.6
0.94

kW
kW
l/s
kPa

N/A

57.3
52.8
0.92
2.743
56.8

N/A

N/A

90.7
82.5
0.91
4.343
71.2

m /s
3
m /hr

"X" Version 1
Total
Sensible
S.H.R.
"A" Version 2
Total
Sensible
S.H.R.
"W" Version 3
Total
Sensible
S.H.R.
"C" Version 4
Total
Sensible
S.H.R.
CW Flow Rate
Unit P.D

Refrigerant R407C used as standard on DX units.


Notes:
1. "X" performances are NETT and based on:
(a) Standard matching Condensing Units (alternatives available, enquire for details).
(b) 1.0 C suction line loss.
(c) 32 C ambient temperature.
2. "A" performances are NETT and based on:
(a) Standard matching A/C Condensers (alternatives available, enquire for details).
(b) 0.5C suction line loss.
(c) 32C ambient temperature.
3. "W" performances are NETT and based on:
(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) Condenser water in 30 C, temperature rise 8 C.
4. "C" performances are GROSS and based on:
(a) Standard coil with chilled water in 7 C, temperature rise 5 C.

PR-2006-0295-GB y Subject to modifications y Status 10/2007

17

Electrical Details at 400 Volt / 3 Ph + N / 50 Hz

GEA Close Control


T-Range

"X" Version
Models

10

12

17

19

21

23

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

0.7
0.9

0.7
0.9

0.7
0.9

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

Heaters

FLA

13.0

13.0

13.0

8.7

8.7

8.7

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Condensing Unit

OA
CLA

6.7
8.2

6.7
8.2

3.8
4.2

6.4
7.3

7.4
8.4

9.2
10.5

10.1
12.0

11.9
14.1

14.9
16.8

17.0
19.4

Operating Amps

FLA

16.3

16.3

16.3

19.1

20.1

21.9

31.5

33.3

36.3

38.4

Connected Load

CLA

18.6

18.6

18.6

21.0

22.1

24.2

34.4

36.5

39.2

41.8

Maximum Inrush

LRA

42.2

42.2

37.0

59.7

63.7

79.7

96.4

123

121

145

Operating kW

kW

5.5

5.5

5.5

9.3

9.9

10.7

18.3

19.0

19.9

21.4

Connected Load kW

kW

7.0

7.0

7.0

10.2

10.9

11.9

19.9

20.8

21.8

23.6

Models

28

32

37

42

48

53

63

73

83

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

8.0
10.0

8.0
10.0

8.0
10.0

8.0
10.0

8.0
10.0

Heaters

FLA

17.4

17.4

17.4

17.4

17.4

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Condensing Unit

OA
CLA

19.1
21.8

19.1
21.8

21.9
25.8

25.5
29.9

34.0
38.8

38.2
43.6

38.2
43.6

43.8
51.6

51.0
59.8

Operating Amps

FLA

40.5

41.5

44.3

47.9

46.4

50.6

51.6

57.2

64.4

Connected Load

CLA

44.2

45.2

49.2

53.3

55.0

59.8

60.8

68.8

77.0

Maximum Inrush

LRA

149

149

189

220

159

165

166

210

245

Operating kW

kW

22.5

23.1

25.2

27.8

22.6

23.7

24.9

28.5

33.7

Connected Load kW

kW

25.0

25.8

28.4

31.5

26.2

29.0

30.5

35.7

41.9

Notes:
Controls are 24 volt.
Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).
Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

18

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Electrical Details at 400 Volt / 3 Ph + N / 50 Hz

GEA Close Control


T-Range

"A" Version

Models

10

12

17

19

21

23

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

0.7
0.9

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

Heaters

FLA

13.0

8.7

8.7

8.7

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Compressors

OA
CLA

3.0
3.5

4.5
5.4

6.2
7.2

8.0
9.3

8.0
9.3

8.7
10.6

10.5
12.7

12.4
14.4

Condenser Fans

FLA

0.9

1.7

3.3

3.3

3.3

3.3

3.3

3.3

Operating Amps

FLA

17.3

17.2

18.9

20.7

30.4

31.1

32.9

34.8

Connected Load

CLA

19.6

19.3

20.9

23.0

32.7

34.0

36.1

37.8

Maximum Inrush

LRA

38.0

53.7

63.7

79.7

89.4

97.4

125

80.6

Operating kW

kW

5.5

9.2

10.6

11.4

18.2

18.9

19.6

20.8

Connected Load kW

kW

7.0

10.1

11.7

12.7

19.6

20.5

21.4

22.9

Models

28

32

37

42

48

53

63

73

83

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

8.0
10.0

8.0
10.0

8.0
10.0

8.0
10.0

8.0
10.0

Heaters

FLA

17.4

17.4

17.4

17.4

17.4

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Compressors

OA
CLA

16.0
18.6

16.0
18.6

17.4
21.2

21.0
25.4

24.8
28.8

32.0
37.2

32.0
37.2

34.8
42.4

42.0
50.8

Condenser Fans

FLA

3.3

6.6

6.6

6.6

3.3

3.3

6.6

6.6

6.6

Operating Amps

FLA

38.4

44.0

45.4

49.0

41.1

47.7

51.0

52.7

59.9

Connected Load

CLA

42.0

47.6

50.2

54.4

47.7

56.1

59.4

64.6

73.0

Maximum Inrush

LRA

98.7

105

114

143

90.5

112.4

116.4

129.4

162.4

Operating kW

kW

22.4

23.8

25.2

26.6

22.0

31.1

24.3

28.7

31.5

Connected Load kW

kW

24.9

26.5

28.3

30.1

25.6

29.6

32.7

36.3

39.9

Notes:
Controls are 24 volt.
Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).
Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

PR-2006-0295-GB y Subject to modifications y Status 10/2007

19

Electrical Details at 400 Volt / 3 Ph + N / 50 Hz

GEA Close Control


T-Range

"W" and "F" Versions


Models

5***

10

12

17

19

21

23

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

0.7
0.9

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

Heaters

FLA

13.0

8.7

8.7

8.7

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Compressors

OA
CLA

3.0
3.5

4.5
5.4

6.2
7.2

8.0
9.3

8.0
9.3

8.7
10.6

10.5
12.7

12.4
14.4

Operating Amps

OA

16.3

17.2

18.9

20.7

29.4

30.1

31.9

33.8

Connected Load

CLA

18.6

19.3

20.9

23.0

31.7

33.0

35.1

36.8

Maximum Inrush

LRA

37.0

53.7

63.7

79.7

88.4

96.4

124

79.6

Operating kW

kW

5.5

8.8

9.8

10.6

17.4

18.1

18.8

19.6

Connected Load kW

kW

7.0

9.7

10.9

11.9

18.8

19.7

20.6

22.1

Models

28

32

37

42

48***

53***

63***

73***

83***

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

4.0
5.0

4.0
5.0

4.0
5.0

4.0
5.0

8.0
10.0

8.0
10.0

8.0
10.0

8.0
10.0

8.0
10.0

Heaters

FLA

17.4

17.4

17.4

17.4

17.4

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Compressors

OA
CLA

16.0
18.6

16.0
18.6

17.4
21.2

21.0
25.4

24.8
28.8

32.0
37.2

32.0
37.2

34.8
42.4

42.0
50.8

Operating Amps

OA

37.4

38.4

39.8

43.4

37.8

43.3

44.3

47.1

53.3

Connected Load

CLA

41.0

42.0

44.6

48.8

44.4

52.8

53.8

58.0

66.4

Maximum Inrush

LRA

97.7

98.7

108

137

87.8

110

111

123

156

Operating kW

kW

21.6

22.2

23.6

25.0

21.2

22.8

24.0

25.4

28.3

Connected Load kW

kW

24.1

24.9

26.7

28.5

23.6

28.0

29.5

33.1

36.7

Notes:
*** F System not available for model 5 and models 48 to 83.
Controls are 24 volt.
Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).
Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).
.

20

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Electrical Details at 400 Volt / 3 Ph + N / 50 Hz

GEA Close Control


T-Range

"C" Version

Models

12

28

42

53

83

Controls

FLA

1.0

1.0

1.0

1.0

1.0

1.0

Main Fan(s)

OA
CLA

0.7
0.9

4.0
5.0

4.0
5.0

4.0
5.0

8.0
10.0

8.0
10.0

Heaters

FLA

13.0

8.7

17.4

17.4

17.4

17.4

Humidifier

OA
CLA

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

3.3
5.6

Operating Amps

OA

16.3

16.0

24.7

25.7

28.7

29.7

Connected Load

CLA

18.6

19.3

28.0

29.0

33.0

34.0

Maximum Inrush

LRA

18.6

19.3

28.0

29.0

34.8

35.8

Operating kW

kW

5.5

8.7

15.5

16.1

16.7

17.9

Connected Load kW

kW

7.0

10.4

17.3

18.1

18.8

20.3

Notes:
Controls are 24 volt.
Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).
Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

PR-2006-0295-GB y Subject to modifications y Status 10/2007

21

Schematic Diagram: "X" Version

22

GEA Close Control


T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007

GEA Close Control


T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007

RI-Schema: "A"-Version

23

Schematic Diagram: "W" Version

24

GEA Close Control


T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007

GEA Close Control


T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Schematic Diagram: "F" Version

25

Schematic Diagram: "C" Version

26

GEA Close Control


T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Ancillaries and Options

GEA Close Control


T-Range

Plinth
For upflow units, a standard plinth is available that raises the Air Handling Unit
200mm (or 400mm) from the floor level to facilitate services entry. It is a plain
sheetmetal box supplied complete with gasket and fixing bolts, and finished to match
the Air Handling Unit.

Base Stand
When the Air Handling Unit is to be installed before the installation of a raised floor, a
matching Base Stand should be used to support it. This consists of a rigid frame of
6mm thick MS angle complete with adjustable feet. The upper face of the frame is
lined with 3mm semi hard gasket. When ordering, specify the nominal height
required, which normally will be the same as the overall height of the raised floor.
The feet have an adjustment of 25mm.

Ceiling Return Duct


The Ceiling Return Duct is a rigid riveted sheetmetal assembly comprising of unit
matched panels lined with 25mm thick insulation. The duct, which is suitable for
downflow units only, is bolted to the top of the Air Handling Unit on site. When
ordering, specify the height between the top of the Air Handling Unit and the under
side of the suspended ceiling. The overall height of the duct will be this dimension
plus 50mm.

Horizontal Discharge Section


The Horizontal Discharge Section consists of a double deflection grille fitted into a
rigid sheetmetal box. The complete assembly is bolted to the top of the Air Handling
Unit on site. The grille has two sets of blades, which allow for both vertical and
horizontal directional adjustment of airflow. The standard height for this section is
500 mm.

Ceiling Discharge Section


For upflow units, where the Air Handling Unit is required to discharge into the ceiling
void, a Ceiling Discharge Extension is available. This consists of a rigid riveted
sheetmetal assembly comprising of unit matched front; rear and end panels lined
with 25 mm thick insulation. The extension is bolted to the top of the Air Handling
Unit on site. When ordering specify the height between the top of the Air Handling
Unit and the underside of the suspended ceiling. The overall height of the duct will be
this dimension plus 50 mm.

High Efficiency Filters


Higher specification filtration can be provided in place of the standard filters having
an efficiency of 80% ASHRAE 52/76 (Eurovent F7). Pre filters are fitted, before the
main high efficiency filters, and are rated as G2. These filters are fitted in the return
airside of the Air Handling Unit within the main cabinet.

Filter Gauge
A dial type manometer can be installed to read the pressure drop across the filter to
give an accurate indication of filter condition.

PR-2006-0295-GB y Subject to modifications y Status 10/2007

27

Ancillaries and Options

GEA Close Control


T-Range

Fresh Air Kit and Filter


Units can be supplied with a fresh air inlet connection and disposable fresh air filter
element. This will admit approximately 35 % of the recirculated air volume. One or
two may be fitted depending on requirements.

Special Colours
Special Colours must be specified when ordering the Air Handling Unit (quote British
Standard number, RAL number, or other, if known). If more than one colour is
specified then state the colour of each panel.

Double Skin Panels


To reduce the sound "break out", Double Skin Panels comprise: - 20 swg steel sheet
glued to the inner face of all outer panels then covered with standard 25mm class O
insulation.

Without Electric Heating


All equipment associated with electric heating is removed from the Air Handling Unit.

LPHW Heating (not available on models 48 83)


Units may be fitted with a Low Pressure Hot Water heating coil in place of the
standard electrical heating. Water flow through the coil is controlled by a modulating
3 way valve. Duties of these coils are nominally the same as standard electric
heating, based on flow and return hot water temperatures of 82 C and 71 C
respectively.

Water Detection
Water Sensors, connected directly to the water detection module of the Air Handling
Unit microprocessor control system, are located in: - Condensate drain pan detecting undue water level.
- Underfloor water tape, supplied loose with 5 metres of cable.
When water is detected, the Air Handling Unit's alarm system is activated and
disables humidifier function.

Sump Pump
Where, due to location, it is not possible to gravity drain units, a sump pump can be
fitted to collect any condensate and pump it to the nearest convenient drain point
(maximum available pump head 5.7 metres). For units fitted with humidifiers, a larger
capacity sump pump is available to accommodate the additional discharge of hot
water during humidifier drain down cycles (maximum available pump head 7 metres).
Please note that when using a sump pump a minimum of a 200 mm high plinth is
required.

28

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Ancillaries and Options

GEA Close Control


T-Range

VRF System
To provide energy saving and thereby limit emission of greenhouse gases that
contribute to global warming, models 23 and above are supplied with the variable
refrigerant flow (VRF) compressor configuration. By applying these models to smaller
loads, even greater energy savings will be realised, due to the very high part load
efficiency.

Electronically Controlled Fans


For applications where high airflow is not required and noise is a major
consideration, then fans with variable speed motors can be fitted. The motors are 3
phase variable frequency but only a single phase feed is provided. The airflow
provided by the fan(s) is determined by a 0 10 Vdc signal that is generated from
the cooling demand via the controls. The lower the cooling demand the lower the
airflow and vice versa. For this option, a reduced heating capacity will be necessary.

Condenser Fan Pressure Switch


A Condenser Fan Pressure Switch can be fitted to the Unit to replace the standard
fan speed controller on "A" versions.

Screwed Water Connections


BSP screwed fittings supplied instead of the standard copper solder connections on
W and C versions.

Hot Gas By Pass


"A" versions can be fitted with hot gas by pass compressor capacity control. This
consists of a hot gas control valve in the by pass line between the discharge line of
the compressor and the evaporator coil suction header, with the sensing line fitted in
the suction line.

Refrigerants
Alternative refrigerants R134a and R410A are available as standard options on
request.

Hand/Auto Switches
A hard wired switch assembly, fitted in the electrical control panel can be used as
manual override or as automatic control function, and is intended as an aid to
commissioning engineers.

Run Status
Run Status is achieved by volt free terminals, located in the electrical box, for remote
monitoring of the unit run (fans) operation.

PR-2006-0295-GB y Subject to modifications y Status 10/2007

29

Ancillaries and Options

GEA Close Control


T-Range

Controller Remote Display


The C3-05 Controller Display can be supplied remote from the Air Handling Unit,
complete with interconnecting cable up to 1 kilometre.

Monitoring Display
The Monitoring Display can be connected to a network of C3-05 Controllers to
enable complete Air Handling Unit monitoring.

Electronic Expansion Valve (EEV)


On DX units the EEV option can be fitted to replace the standard TEV. This consists
of a valve, electronic driven module, pressure transducer and temperature sensor
per refrigerant circuit.

Discharge Pressure Transducer


On DX units a pressure transducer can be fitted to monitor the discharge pressure. It
is recommended that the EEV option it fitted with the Discharge Pressure
Transducer.

Remote Temperature and Humidity Sensor


The temperature and humidity sensors Unit, fitted with the required length of cable
(up to a maximum of 25 metres), can be supplied remote from the Air Handling.

Winter Start Kit (ELATE)


Generally recommended for temperatures between 25 C and 40 C, and
comprises horizontal type liquid receiver with trace heater and pressure relief valve
situated in a special section below the air cooled Condensing Unit / Condenser.
However a base section will be required and will increase the overall height of the
horizontal blow Condensing Units / Condensers by 400 mm.

Trend Interface Card


The Trend interface is a small pcb which can be plugged into the C3-05 controller to
provide it with Trend network capability.
The interface needs to be configured in order that the required controller variables
are linked to appropriate Trend parameters; these then become accessible via the
Trend network using standard Trend (text) communications. The interface provides
CNC functionality.
-

30

Flexible number of configuration modules


Peer to peer communications (IC Comms)
Suitable for field installation
Display and directory modules

PR-2006-0295-GB y Subject to modifications y Status 10/2007

Ancillaries and Options

GEA Close Control


T-Range

RS232 Serial Card


The RS232 Serial Card is used to interface the C3-05 controller directly to a standard
HAYES modem. The following hardware signals can be managed:
- Output, request to send (RTS) in parallel to data terminal ready (DTR).
- Input, carrier detected (CD).
The maximum baud rate is 19200.

RS485 Serial Card


The RS485 Serial Card is used to interface the C3-05 controller to an RS485
network.
The card guarantees the optical isolation of the controller from the RS485 serial
network. The maximum baud rate is 19200 (adjustable in software).

Lonworks Serial Card


The LonWorks Serial Card is used to interface the C3-05 controller to a Lonworks
network.
The type of interface on the LonWorks network side is:
- PCO20000F0 interface to FTT-10A 78 Kbs (TP/FT-10).
The baud rate of the C3-05 controller must be set to 4800.

PCOWEB Interface
The pCOWeb Interface allows connection to TCP/IP and SNMP protocols on the
Ethernet standard and BACnet both on the Ethernet and EIA485 standards.

Due to our policy of continuous development and improvement, the specifications and data herein are subject to change
without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated
herein.
All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however,
should independently evaluate the suitability of each product for their own application. GEA makes no warranties as to the
accuracy or completeness of the information, and disclaims any liability regarding its use.
PR-2006-0295-GB y Subject to modifications y Status 10/2007

31

GEA
Klimatechnik GmbH
A-4673 Gaspoltshofen
Tel. +43 / 7735 / 8000-0

GEA Happel Belgium N.V.


B-1130 Brussels
Tel. +32 / 2 / 2406161

GEA Klimateknik ApS


DK-2610 Rdovre
Tel. +45 / 38 / 887070

IS

Rafn Jensson
IS-110 Reykjavik
Tel. +354 / 56 / 780-30

RO

GEA Klimatechnik s.r.l.


RO-300222 Timisoara
Tel. +40 / 356 / 423703

GEA Air Treatment


Marketing Services
Int. GmbH - oficina Espaa
E-28036 Madrid
Tel. +34 / 91 / 3837701

GEA Happel Luxembourg


L-4940 Bascharage
Tel. +352 / 26 / 502970

RUS

GEA Kondicioner
Moskva
RU-105094 Moskva
Tel. +7 / 495 / 9566674

LT

EST

GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060

GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060

LV

GEA Happel France sarl


F-59436 Roncq Cedex
Tel. +33 / 3 / 20689020

GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060

GEA EXOS
Ventilation AB
S -74528 Enkping
Tel. +46 / 171 / 85530

SK

GEA Klimatizcia s.r.o.


SK-83104 Bratislava
Tel. +421 / 7 / 44457917

SLO

GEA Klimatizacijska
Tehnika d.o.o.
SI-1000 Ljubljana
Tel. +386 / 1 / 2573850

SRB

GEA Klimatehnika
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955

TR

ISISAN
TR-80700 Balmumcu
Istanbul
Tel. +90 / 212 / 2757171

UA

GEA Ukraina t.o.v.


UA-01135 Kyiv
Tel. +38 / 044 / 4619356

DK

BG

BIH

BY

CH

CZ

EVISS Ltd.
BG-7000 Rousse
Tel. +359 / 82 / 81000
GEA Klimatehnika
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
GEA Klimatec
Schweiz AG
CH-3065 Bolligen-Station
Tel. +41 / 31 / 9171919
GEA LVZ, a.s.
CZ-46312 Liberec
Tel. +420 / 48 / 5225-111
GEA Klimatizace spol. s r.o.
CZ-46312 Liberec
Tel. +420 / 48 / 5225-303
GEA Happel
Klimatechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-00

MWE

FIN

OY TEKNOCALOR AB
FIN-01300 Vantaa
Tel. + 358 / 9 / 82546020

GB

Denco Ltd.
UK-HR4 8DS Hereford
Tel. +44 / 1432 / 277 277

NL

HR

GEA Klimatechnika Kft


H-1037 Budapest
Tel. +36 / 1 / 4393200
GEA Klima-rashladna
tehnika d.o.o.
HR-10000 Zagreb
Tel. +385 / 1 / 6064900

PL

GEA Klimatehnika
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
GEA Klimaprodukter AS
N-0484 Oslo
Tel. +47 / 220 / 27990
GEA Happel
Nederland B.V.
NL-2909 LL
Capelle a/d Ijssel
Tel. +31 / 10 / 2350606
Nnio, Lda.
P-1269-090 Lisboa
Tel. +351 / 21 / 3826160
GEA
Klimatyzacja Sp. z o.o.
PL-54610 Wroclaw
Tel. +48 / 71 / 3737952

Air Treatment Division

For detailed information on all corporate areas,


go to www.gea-airtreatment.com or contact

A company of GEA Group

us by email info@gea-airtreatment.com

PR-2006-0295-GB Subject to modifications Status 10/2007 Copyright GEA Air Treatment