Technical Specifications
Division 16: Electrical
Lighting Installations
SECTION 16500
LIGHTING INSTALLATIONS
PART 1 GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract including "Conditions of Contract" and
"General Requirements" specification sections, shall apply to this section.
SCOPE
A.
B.
C.
D.
E.
Page 1 of 4
Date: 08/12/2011
SAADIYAT ISLAND
ABU DHABI, UAE
1.3
Technical Specifications
Division 16: Electrical
Lighting Installations
SUBMITTALS
A.
The following data (but not limited to) shall be submitted for approval:
1. Details on each fixture, lamp and control gear including manufacturer's catalogue
cuts, catalogue number, rating, material specification, overall dimensions, operating
characteristics, photometric data, etc.
2. Installation details.
3. Detailed computerized lighting calculations in order to achieve the required
LIGHTING FIXTURES
A.
B.
C.
Light reflecting surfaces are to be finished with white baked enamel paint having a
reflection factor not less than 80%.
1. Finish is to withstand 72 hours exposure to an ultra-violet RS lamp placed 100 mm
from surface.
D.
Wiring to be not less than 1mm, insulated for 240 V supply. Wiring is to be terminated on
screw type insulated, terminal blocks.
2.2
Dimmer pack shall be wall mounted, completely pre-wired by the manufacturer, with
individual branch circuit breaker protection for each channel.
Rating of each channel shall be as shown on the drawings.
The dimmers shall be able to control the following load types: Tungsten, L.V. Tungsten,
dimmable fluorescent and 0-10V controllable ballast.
RFI noise suppression shall be provided.
B.
C.
Page 2 of 4
Date: 08/12/2011
SAADIYAT ISLAND
ABU DHABI, UAE
2.3
Technical Specifications
Division 16: Electrical
Lighting Installations
A.
2.4
Normal start, bi-pin, rated as described on the drawings. Guaranteed rated life is to be
above 16000 hours. The luminous output shall be above:
1. 2700 lumens for 36 W lamps (for universal white) and 3250 (for other colors).
PL FLUORESCENT LAMPS
A.
2.5
Compact, with special bi-pin socket, rated as described on the drawings. Guaranteed rated
life is to be above 13000 hours and luminous output above the following:
1. 1200 lumens for 18W lamps.
2. 1800 lumens for 26 W lamps.
3. 2400 lumens for 32 W lamps.
4. 2800 lumens for 36 W lamps.
5. 3500 lumens for 42 W lamps.
METAL HALIDE LAMPS
A.
2.6
Lamps shall be rated as described on the drawings. Color of light is to be warm white with
excellent color rendering properties. Luminous output to be above 12000 lumens for 150
W lamps.
Lux Levels & Lighting Power Densities
A.
No.
SPACE TYPE
1.
OfficeEnclosed
12.64
2.
Conference/Meeting/Multipurpose
51.92
3.
5.75
5.
6.
Restrooms
10.29
7.
Dressing/Locker/Fitting Room
9.75
8.
Corridor/Transition
16.30
9.
Active Storage
14.40
10.
Electrical/Mechanical
7.95
11.
22.73
12.
18.27
13.
10.29
4.
Page 3 of 4
13.09
11.17
Date: 08/12/2011
SAADIYAT ISLAND
ABU DHABI, UAE
14.
2.7
Technical Specifications
Division 16: Electrical
Lighting Installations
3.11
A.
No incandescent lamps may be installed in the internal environment, and all internal and
permanently installed fluorescent lighting installations must incorporate high frequency
electronic ballasts. For projects with no control over fit-out of lighting installations,
provide contractual extracts from the tenant lease highlighting how this credit will be met.
B.
Install occupancy sensors in all rooms intended for individual occupancy, conferencing or
meeting rooms, open plan offices spaces and hallways or corridors.
PART 3 EXECUTION
3.1
INSTALLATION
A.
per
manufacturers
B.
Fixtures are to be installed aligned, leveled and at uniform heights within one room or
area. Fixtures are to be supported with hangers to support weight of fixture.
C.
Exact position of fixtures must be coordinated with the reflected ceiling plan.
D.
Page 4 of 4