TREATED FRESH AIR UNIT WITH HEAT RECOVERY WHEELS

Supply,installation, testing and


commissioning of Centralised Treated Fresh
air unit consists of exhaust air block and
fresh air block. Each block is made up of
double skin construction designed on
modular concept basis and has for fans,
motors, VFDs for fan motors, chilled water
coil, damper and filter. Each block module
shall be fitted with other block, housing heat
recovery devices, washable metallic viscous
filters (50mm thick) and inlet and outlet
dampers (extruded aluminium low leakage
construction) with bird screen for supply and
return air.
Air flow parameters: Heat Recovery wheel to
recover energy complete with desiccant
coated aluminium media rotor seal GI
structural frame work to house rotor, drive
system, rotor drive motor, belt, pre-filter
complete with starter panel. The TFA shall
have Thermal Break Profile.
The price quoted for Treated fresh air unit
shall include the following
a) All internal wiring, power cabling copper
earthing of treated fresh air unit motors, from
the panel and control wiring
b) Bimetallic lugs shall be used at copper to
aluminium joints and as per specification.

Coil size shall be eight row coil selected for a maximum face velocity of 2.75 mps and
external static pressure shall be minimum 500pa.
The vendor shall be select the suitable units with minimum leakage. The fresh air quantity
required after leakage is as follows.