W a t e r S u p p ly
W a t e r S u p p la y c o m e s f ro m w a t e r t re a t m e n t a n d a c c o m m o d a t e d in a
b a s in t h a t d im e n s io n s 5 0 m ( L ) x 1 5 m ( W ) x 5 ,7 9 m ( H )
B a s in is s e m i- u n d e r g ro u n d
T h e w a t e r d e b it t o t a l a re 7 ,5 5 7 L /m in in t o t a l ( 5 ,6 6 7 L / m in a t T P - C -T V 1 1 2 a n d h o s e s t re a m d e m a n d 1 ,8 9 0 L / m in )
It c a n b e 2 h o u r s s u p p la y f o r fi re p ro t e c t io n re q u ir e m e n t in 8 h o u r s
p e r io d
Reduction of
Pressure
Jockey Pump A
reach 12,5 Bar
Jockey Pump A
stoped
Pressure Switch
System
electrical driven
main starts at
10,5 Bar
Pump Control
Panel
Jockey Pump A
electrical driven
fault, start diesel
driven at 10 Bar
Valves
Types of valve use in KPJB are OS&Y Gate Type and Butterfly Type (Fire
water pump house)
All valve located on approriate location for inspection, testing,
maintenance and removal equipment
Yard Mains and Hydrants
Yard mains is arrangement like ring which arounding power palnt to
serve water for The System (more detail read "Piping Classification and
Piping Specification)
Piping in above ground have been protected from corrosion
Distance between Hydrants are 75 m
The cabinet is provide with single door (fitted with neoprene), painted
red, and prevented from build-up condensation
Spray Water System for Oil Filled Transformer and Oil Tank (Deluge Valve
System)
consists of Spray nozzles, Heat Detectors, Deluge Valve, Isolation
Valve and Piping etc
Provides on :Unit 3. Unit Transformers A, Unit 3. Unit Transformer B,
Unit 3. Excitation Transformer, Unit 3, Generator Transformer, Unit 4,
Unit Transformers A, Unit 4. Unit Transformers B, Unit 4. Excitation
Transformer B, Unit 4. Generator Transformer, 500 MVA Inter-bus
Transformer, Main Oil Tank 3, Turbine Lube Oil Conditioner 3, Main Oil
Tank 4. Turbine Lube Oil Conditioner 4, Diesel Generator Oil Tank, Fuel
Oil Tank for Engine Pump, BFPT Oil Tank.
Carbon Dioxide (CO2) System
provides for Switchgear Bay No 1, No 3 and Electrical & CVCF Room
in Central Control Building
activated by automatic by fire alarm and manual
discharge CO2 by 2 detectors (Crossed Zone) in 1 Specified Hazard
Area or manual release from Manual Release Station at Specified
Hazard Area or Mechanical manual release by lever operated control
head on Specified Hazard Nitrogen Pilot cylinder
Detectors used for the system are Addressable Photoelectric Smoke
Detector and Addressable Ionization Smoke Detector
Important to know about evacuation procedure when CO2 discharge