Sie sind auf Seite 1von 4

VLT Energy Box Report

Date:

To:

SPML Infra Ltd


11 KW Tertiary treatment Feed Pump

Prepared by:

Project: 20 MGD Nilothi STP

System Data

Duty Cycle
10.00 m.wg
9.0 kW
86.0 %
8.00 m.wg
5.00 m.wg

Flow (%)

AC Motor Data
Motor Power:
Motor Efficiency:

9.8 kW
90.0 %

Drive Data
Drive Power:
Drive Efficiency:
Drive Cost:

11.0 kW
96.0 %
INR 140,000

Electricity
Cost per kWh:
Utility Incentive:

INR 5.500
0 INR/kW

100
50
25
70
60
50
40
30
20
10

Page: 1

Sharad Srivastava

Pump Application
Design Head:
Shaft Power:
Design Efficiency:
Set-Point Static Head:
Removed Pressure Drop:

2010-07-23

Throttling Valve System


Time (%)

Time (hrs)

AC Drive

kW-hr/yr

kW-hr/yr

17
50
33
0
0
0
0
0
0
0

1,489
4,380
2,891
0
0
0
0
0
0
0

14,900
32,114
14,162
0
0
0
0
0
0
0

8,365
19,604
8,274
0
0
0
0
0
0
0

Total:

8,760

61,175

36,242

kW-hr/yr savings:
Annual cost savings:

24,933
INR 137,131

Energy Savings
Individual System Costs

Drive System Cost Comparison

Throttling Valve System

Net Cost Savings

Initial Cost:
Annual Energy Cost:
Other Annual Cost:

INR 0
INR 336,465
INR 0

Drive System Inc. Initial Cost:


Utility Incentive
Annual Energy Cost Savings:
Other Annual Cost Savings:

INR 140,000
INR 0
INR 199,333
INR 0

* Initial cost includes drive cost

Drive System
Drive Cost:
Initial Cost:
Annual Energy Cost:
Other Annual Cost:

INR 140,000
INR 0
INR 137,131
INR 0

Cost Savings
Simple Payback Time:

1.02 Years

Calculations are based on data available. Danfoss assumes no responsibility for the accuracy of the supplied data or of the resulting report.

VLT Energy Box

Page: 2

VLT Energy Box

Page: 3

VLT Energy Box

Page: 4

Das könnte Ihnen auch gefallen