TECHNICAL SCHEDULES
TABLE OF CONTENTS
TITLE

PAGE

1.

POWER TRANSFORMERS............................................................................111

2.

33kV EARTHING TRANSFORMER...............................................................117

3.

OUTDOOR STATION SERVICE TRANSFORMER ....................................119

4.

66kV OUTDOOR LIVE TANK CIRCUIT BREAKER....................................121

5.

66kV OUTDOOR DISCONNECT SWITCH ..................................................126

6.

66kV OUTDOOR EARTHING SWITCH ........................................................127

7.

66kV POTENTIAL TRANSFORMERS ..........................................................128

8.

66kV OUTDOOR CURRENT TRANSFORMERS........................................130

9.

66kV OUTDOOR POST INSULATORS ........................................................131

10.

66kV OUTDOOR SURGE ARRESTERS ......................................................132

11.

33kV OUTDOOR LIVE TANK CIRCUIT BREAKERS .................................133

12.

33kV OUTDOOR DISCONNECT SWITCH ..................................................134

13.

33kV OUTDOOR EARTH SWITCH ...............................................................135

14.

33kV OUTDOOR DROP-OUT FUSED DISCONNECT SWITCH .............136

15.

33kV OUTDOOR POST INSULATORS ........................................................137

16.

33kV OUTDOOR VOLTAGE TRANSFORMERS ........................................138

17.

33kV OUTDOOR CURRENT TRANSFORMERS........................................139

18.

33kV OUTDOOR SURGE ARRESTER.........................................................140

19.

STEEL SUPPORTING STRUCTURES FOR ELECTRICAL EQUIPMENT141

Supply & Installation of 66/33 & 66/22kV Substations in Greater Monrovia and Bomi- Corridor

1.

POWER TRANSFORMERS

Item

Description

2
3

Location of Manufacturer

6
7

8
9
10
11
12

13

14

15

Shipping Method
Dry Air Supply (yes/no)
Transformer oil filled
(yes/no)
Quality Control ISO9001 (yes/no)

Required

Oil Filled Type


Yes

Quality Assurance Describe the manufacturing


techniques and
production control to ensure building to
standards,
requirements,
quality control
Transformerdesign
Standard
(CAN/CSA C88-M90,
ANSI, IEC
etc)
Deviations
from Standards (itemize below, including
reasons).
Deviations from this Specification (itemize below including
reasons).

Offer of alternatives (Itemize below including reasons


and
advantage to Purchaser
Vacuum Filling Confirmation the assembled transformer
with radiators and fittings normally connected when in
service, are designed for full vacuum and for vacuum
filling with oil at a continuous rate of 175 litres per
minute at the filling connection while maintaining a tank
of absolute gas pressure in the order of

Overload Capability Confirmation the transformer and


components will permit short time overloading
according to IEC
60076 (yes/no)
Overload
Limitations If the transformer or any

Yes

components do not comply with IEC 60076 the Vendor


shall state the limitations and recommendations for short
time overloading.

Short Circuit Design


Mechanical
(Yes/No)
Electrical
Provide a brief description of the Vendors design
philosophy for
withstanding short circuit forces, in particular
highlighting the items noted below.
1. Approach to handling short circuit problem
(particularly the mechanical forces but including
the thermal problem)
2. Basic criteria used by the Vendor in
establishing their short circuit design
3. Analytical methods (computer programs etc.) used
by the
Vendor to establish the requirements and verify
the design will withstand the specified short
circuit capability
4. Work done and results of model testing or full scale

Yes
Yes

Offered

16

17

18
19
20
21

22

23

24

Vendor to supply a volt time curve to demonstrate


the
permissible excitation versus time:
Vertical axis: voltage in pu of tap voltage
Horizontal axis: time (log scale) showing
permissible
timeaof
excitation
Attachedthe
to flux
Vendor
to supply
B-H
curve indicating
density, from 80
130 percent rated voltage, for the proposed design
Attached
to
Rated Capacity
@65C rise ONAN/ONAF
Number of phases
Frequency
Tank
1. Conservator (Yes/ No)
2. Vacuum rating (mHg)
Windings
1. Circular Design (Yes/No)
2. High Voltage Windings
- HV Rated Voltage
- HV Connection
- HV BIL rating
- HV winding Material
3.
-

Low Voltage Windings


LV Rated Voltage
LV Connection
LV BIL rating
LV winding Material

4.
-

Neutral
Rated Voltage
Rated Current
BIL Rating

5.
6.
-

Winding resistance @85C


HV Winding
LV Winding
Percentage resistance @85C on ONAN Base
HV Winding
LV Winding

Short Circuit Withstand


1. Multiple of rated ONAN current
2. Maximum duration of fault
Impedance
1. Positive Sequence Impedance@85C on ONAN Base
- Highest Tap

10 MVA @
ONAN
13 MVA3 @
50
Hz
Yes

Yes
66
KV
Star
325
KVp
Electrolytic
grade
22kV/33
KV
Star/Delta
170
KVp
Electrolytic
grade
33
KV
630
A
170

Must state

8.80%

25

26

27

28

29

30

- Nonimal
Must state
8.25%
Tap
Must state
7.70%
- Lowest
Tap
2. Zero sequence Impedance @85C on ONAN Base, nominal Tap
7.70% High to low
Must state
Load Loss @85C, nominal Tap
ONAN
Must
state
ONAF
Must
state
ONAF/ONAF
Must state
No Load (Core) losses (As per IEC Tol.) at:
100%
rated
Voltage
Must state
110%
rated
Voltage
Must state
Flux Density
100%
rated
Voltage
Must state
Sound Level at
ONAN
Rating
Must state
ONAF
Rating
ONAF/ONAF
Rating
Regulation @85C based on ONAF/ONAF Base
1.0
Power
factor
Must state
0.9
Power
factor
Must state
0.8
Power
factor
Must state
Masses & Dimensions
1.
Overall
Dimensions
Lengt
h
Width
Heigh
t
2.
Shipping
Dimensions
Lengt
h
Width
Heigh

t
3. Masses
Core & Coils
Tank &
fittings
Oil in main Tank (including All
Accessories) Oil in radiator
Radiators (including
framework) Total
4.
Shipping
Weight
Main
Transformer
including Oil
Items
removed
for
shipping
5.
Oil
Volume
Total,
completely
Transformer

assembled

31

Amount Shipped separately


Accessory Data
1. Cooling equipment power requirements:
First stage cooling, ONAF
Second Stage Cooling ONAN/ONAF
2. Bushings
1. High Voltage Bushings
Manufacturer
Standard (IEC)
Type
Catalogue Number
Voltage rating
Current rating
Creep
2. Low Voltage Bushings
Manufacturer
Standard (IEC)
Type

Catalogue Number
Voltage rating
Current rating
Creep (33kV/22kV)
3. Tertiary Bushings (66/22kV )
Manufacturer
Standard (IEC)
Type
Catalogue Number
Voltage rating
Current rating
Creep
4. Safe top transverse force, (static force)
HV
5. Safe top transverse force, (static force)
HV
LV
Xo

IEC-60137

72
KV
800
A
216
0
IEC-60137
Oil
Communicati
ng Type
36
KV
630
A
1080/720

Cantilever
Load

3. Current Transformers
Manufacturer
HVCT Ratio / Quantity

200/1 Amp

HVCT Accuracy
LVCT Ratio / Quantity
LVCT Accuracy
XoCT Accuracy
4. Lighting Arrestors
1. High
Voltage
Manufacture
r Class
Voltage
Type or model no.
2. Low
Voltage
Manufacture
r Class
Voltage
Type or model no.
5. Load Tap Changer (LTC): (HV or LV)
Manufacturer
Type or Model No.
speed

Range in %
@1.25% Number of taps
Rated maximum service voltage
Rated maximum continuous current
Operations before service @100% current
Operations before service @50% current

6. Load Tap Changer (LTC) controller


Manufacturer
Type or Model No.
32
Auxilliary
Equipment
1. Pressure Relief Devices
Main
Tank
Make
Model
Quantity
LTC
Tank
Make

CTR/OLG
High
Transit resister
type
10%
8 Taps
72 KV
200 A

Model
Quantit
y

2. Sudden Pressure (Main


Tank) Make
Model
3. Liquid Level Indicators
Conservator - Main Tank (Low oil
Alarm) Make
Model
Conservator -LTC (Low oil
Alarm) Make
Model
Main Tank (Very Low oil
Trip) Make
Model
LTC Tank (Very Low oil
Trip) Make
Model
4. Top Oil Temperature
Make
Model
5. Winding Temperature
Make
Model
6. Gas Detector (Main
Tank) Make
Model
7. Other Auxiliary or protective devices in addition
to specified equipment, list devices, reason, make
& model

2.
Item
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.1
1.11
1.12

1.13

1.14

2
3
3.1
3.2
4
4.1
5
5.1
5.2

33kV EARTHING TRANSFORMER

Description
Manufacturer
General
Cross-sectional area of copper
conductors
Maximum current density in
windings Zero sequence
impedance per phase Total
volume of oil
Volume of oil above level of winding
excluding conservator oil
Weight of core and winding
Total weight of complete transformer
ready for service
Weight of transformer arranged for
transport
Filling medium for transport
Type of material used for gasket joints
Vacuum withstand
capability: Main tank
Conservator
Radiators and Cooler Banks
Dimensions of main transport
package: Length
Width
Height
Dimensions as
installed: Length
overall
STANDARDS
CURRENT RATING:
Continuous Neutral
Current Maximum Neutral
Current(10
s)
VECTOR

L
kg
kg
kg

kPa
kPa
kPa
m
m
m
m
m
m
m

IEC 60076-6

A
A

3180

Zn

Impulse Withstand voltage


(1.2/50) Power Frequency
Test
COOLING
AND TEMPERATURE

kV pk
kV
rms

TANK AND ACCESSORIES

Required

mm

A/mm 19.4
ohm
L

GROUP
Vector GroupLEVELS:
INSULATION

6
6.1 CONTROL: Radiators on Main
6.2 Number of radiators
6.3 Rating of each radiator
7

Unit

Yes/N
o kW

170
70

Offered

Item
7.1

7.2
8
8.1
9
9.1
9.2
9.3
9.4
9.5
9.6
9.7
9.8
9.9

Description
Surface Treatment
Method of surface
treatment: Tank
Radiators,
etc.
Conservator
Total
volume of OIL:
conservator
TRANSFORMER
Manufacture and type of transformer oil
BUSHINGS:
Manufactur
er Type
Total Creepage distances to earth
Protected creepage distance to earth
Electrical distance to earth
Rated Current
Rated voltage
1 Min. 50 Hz. Wet/dry withstand voltage
Impulse withstand Voltage

9.1 Rated short-time current


10 NOISE LEVEL:
10.1 Guaranteed noise level in dB(A) to IEC
60076-10

Unit

Required

mm
%
m
m
A
kV
kV
kV
A
dB(A)

1080
< 50
320
18/30(36)
70
170
3180A, 10
Sec
60

Offered

3.

OUTDOOR STATION SERVICE TRANSFORMER

ITEM

DESCRIPTION

UNIT

Required

A.

RATINGS

Nominal transformer rating

kVA

50, 100

Primary voltage

33000/22000

Secondary voltage

400/230

Impedance

0.0425

Vector group

Dyn0

Frequency

Hz

50

B.

TEMPERATURE RISE

Average winding temperature rise

55

Top oil temperature rise

50

Maximum winding hotspot temperature rise

68

C.

TRANSFORMER LOSSES

Core loss

kW

specify

Winding loss

kW

specify

Magnetizing current

specify

D.

WINDINGS

Conductor material (Al or Cu)


(a) HV winding

Cu.

(b) LV winding

Cu.

E.

BUSHINGS

Manufacturer

Manufacturer's catalogue number:


(a) High voltage
(b) Low voltage

HV/LV bushing BIL

KV

HV/LV bushing power frequency withstand

KV

33kV:170
22kV: 125
33kV: 75/3
22kV: 50/3

Offered

Section IV. Bidding Forms

1-13

ITEM

DESCRIPTION

UNIT

Required

F.

TANKS

Tank Construction

Top oil temperature for internal pressure of 100


kN.m-2

See Section
2.1.2

Steady load at 40C ambient at oil temperature as


given in (2)

kVA

See Section
2.1.2

Steady load at 40C ambient by considering


2
effect of solar radiation of 1200 W.m

kVA

See Section
2.1.2

Tank Steel thickness

mm

Radiator steel thickness

mm

1.2

Weight of tank

kg

Weight of oil at 20C

kg

Total weight of transformer ready for service

kg

Shipping weight of transformer

kg

H.

TRANSFORMER DIMENSIONS

Width

mm

Height

mm

Depth

mm

I.

MISCELLANEOUS

Design continuous ambient temperature

Type of cooling

Total number of tap changer positions

Flux density

Rigid

ONAN
5

30

Offered

4.
Item
1

66kV OUTDOOR LIVE TANK CIRCUIT BREAKER

Description

Required

1.1 Manufacturer
1.2 Designation & Type
1.3 Place of Manufacture
2.1 Number of Poles
2.2 Interrupting units per pole

Class / Type

Rated Voltage

Rated Insulation Level:

3
1
Outdoor
-Live Tank
kV

72.5

(a) Lightning impulse withstand voltage

V Peak

140

(b) Power frequency withstand voltage

kVrms

140

Hz

50
630

Rated Frequency

Rated Normal Current

Rated Cable-Charging Breaking Current

A Bidder to specify

Associated Maximum Switching Overvoltage

10

kV

IEC 60056

Is the Circuit Breaker Restrike-Free?

Yes

11

Rated Small Inductive Breaking Current

10

12

First-Pole-to-Clear Factor

13

Rated Line-Charging Breaking Current

14

Rated Short Circuit Breaking Current:


(a) RMS Value of AC Component
(b) percentage of DC Component

1.5
A

80

kA
%

31.5
80

Are the rated transient recovery


voltages/times and characteristics for faults as
listed in IEC 60056

Yes

16

Are each of the test values for item 15 listed

Yes

17

Out-of-Phase Breaking Current.

kA

IEC 60056

18

Rated Short Circuit Making Current

kA

80

15

Offered

Item

Description

Required

19

Rated Duration of Short Circuit

20

Rated Operating Sequence

21

Circuit Breaker designed for triple and single pole


rapid auto reclosing?

22

Circuit Breaker Opening Time:

ms

Bidder to specify

23

Circuit Breaker Total Break Time

ms

Bidder to specify

24

Maximum Time Discrepancy between First and


Last Contact

1
O-0.3 sec-CO-3
min-CO
Yes

- at opening
- at closing

ms
ms

25

Circuit Breaker Closing Time

ms

26

Maximum Make Time

ms

27

Minimum Dead Time

ms

28

Insulator Creepage to Earth

29

HV Terminals:

mm

2175 min.

(a) Type
(b) Materials
(c) Dimensions
IEC 60518

(d) Standard Specification


30

Parallel inter pole spacing

31

Minimum Clearances in Air:


(a) Live Parts to Earth
(b) Bottom of Live Insulator to Earth

32

33

Maximum Permissible Horizontal


Terminal:
(a) Parallel to Pole
(b) Perpendicular to Pole

Pull on

Close Coil
(a) Rated Voltage
(b) Power Consumption
(c) Maximum/Minimum Operating Voltage

mm

Bidder to specify

mm
mm

3000
2300

HV
kN
KN
VDC
W
%

110
Bidder to specify
110/85

Offered

Item
34

Description
Number of Trip Coils

Required
2
VDC
W
%

(a) Rated Voltage of each Element


(b) Power Consumption
(c) Maximum/Minimum Operating Voltage
35

Tripping mechanism function correctly when one or


both trip coils are energized

36

Mechanism Cabinet Heaters:

110/70

Yes

VAC

(a) Rated Voltage of each Element

110

230

(b) Rated Power of each Element


(c) Minimum number of Normally-Open Contacts
(d) Minimum Number of Normally-Closed Contacts
37

Single phase AC socket outlet

38

SF6Gas

Yes

(a) Quantity of SF6 per Pole at 0.1 MPa


(b) Rated Supply Pressure of SF6
(c) Minimum SF6 Gas Pressure for Making and
Breaking the Rated SC Currents
(d) Minimum SF6 Gas Pressure to Maintain
Insulation Withstand Levels.
(e) SF6 Gas Leakage rate per annum
39

Litre
MPa
MPa
MPa
%

:S0.1

VDC

110

Driving Mechanism
Type (MW Spring)
(a) Rated Voltage of Motor
(b) Power Consumption of Motor
(c) Does the Mechanism Offered Satisfy the
Conditions in technical specifications?
(d) Does the MW spring have remote indication of
spring charged and spring charge fail conditions

40

VAC

Compressor motor
Minimum Period, Dating from Delivery of
Equipment during which a full range of Spare Parts
will be available

41

Are the essential tools for


maintenance listed and described?

kW

erection

and

Years

Yes

Offered

Item
42
43

Description
Availability of Spare Parts
Total Weight of the complete circuit Breaker
erected

Required
Yes

44

Local control cabinet, weather-proof version to IP44


and supporting structure

Yes

45

Support structure for CB

Yes

46

Mechanical Operation counter

Yes

47

Anti-pumping relay

Yes

48

Poles discrepancy-signaling relays with time delay


of 0 1 sec.

Yes

49

Phase discrepancy relay

Yes

50

Mechanical position indicator for each pole


ON & OFF

Yes

51

SF6 gas filling-in device

Yes

52

Under voltage trip circuit

Yes

53

Local-Remote selector switch

Yes

54

Trip and close inhibit relay

Yes

55

CB position indicator lamps

Yes

56

C B WATCHER : Electronic controller device

N/A

57

Electronic gas density monitoring device

58

Emergency manual trip lever/button


control cabinet.

59

Control panel internal lights

kg

on local

Yes
Yes

SERVICE ENVIRONMENTAL CONDITIONS


1

Service temperature

Seismic withstand

Max. wind speed

Isokeraunic level

Exposure to heavy rains, high humidity (up to 98%)


and salt pollutants.

C
g

Km/h

45
0.2
122
100
Yes

Offered

Item

Description

Required

LIMITS OF SUPPLY
1

Earthing Connection points on Circuit Breaker


Structures

Yes

SF6 gas for first filling

Yes

Anchor Bolts

Yes

Offered

5.
Item
1

66kV OUTDOOR DISCONNECT SWITCH

Description
1.1 Manufacturer and Place of Manufacture
1.2 Designation and Type
1.3 Service Conditions

Class/Type

Disconnects : Pole Spacing

Rated Voltage

kVrms

72.5

Rated Insulation Level (to earth)


- Impulse (1.2/50 !-s)
- Power Frequency for 1 min

kVpeak
kVrms

325
140

Rated Insulation Level (Across Open Disconnect)


- Impulse
- Power Frequency for 1 min

kVpeak
kVrms

375
160

mm

2175

1250

kA

31.5

Rated Normal Current

Rated Short Time Current (3 sec)

10

Rated Peak. Withstand Current

11

Type of Drive for Disconnect Switch


- At Voltage

14

Outdoor
1800

Creepage Path to Earth (min)

13

Refer to
Tech. Specs.

mm

12

Required

kA
VDC

80
D.C. Motor
110

Have Type Tests been carried out to


IEC 60129 and IEC 60694

Yes

Do the Disconnects Switch as mounted conform to


Specification in the following respects:
- Clearances
- Controls
- Interlocking
- Position Indications

Yes
Yes
Yes
Yes

Steel Supporting Structures

No
(Gantry
Mounting)

Offered

6.

Item
1

66kV OUTDOOR EARTHING SWITCH

Description
1.1 Manufacturer & Place of Manufacture

Required

1.2 Designation and Type


1.3 Service Conditions

Refer to Tech.
Specs

Class/Type

Outdoor

Earthing Switch: Pole Spacing

Rated Voltage

kVrms

72.5

Rated Insulation Level (to earth)


- Impulse (1.2/50 !-s)
- Power Frequency for 1 min

kVpeak
kVrms

325
140

mm

2175

1250

mm

Creepage Path to Earth (min)

Rated Normal Current

Rated Short Time Current (1 sec)

kA

31.5

Rated Peak. Withstand Current

kA

80

10

Mode of Earthing Switch operation

Manual interlocked with


disconnect switches

11

Have Type Tests been carried out

Yes

12

Do the Earthing Switch as mounted conform to


Specification in the following respects:
- Clearances
- Interlocking
- Position Indications

Yes
Yes
Yes

13

Supporting Structures if required

No

Offered

7.

66kV POTENTIAL TRANSFORMERS

Item

Description

Required

Manufacturers name

Manufacturers type designation

Standards in force (with reservations as


mentioned in Tech. Specifications)

Service Conditions
- elevation above sea level
- ambient temperature
maximum value
minimum value
average yearly value

IEC

m
C

100
+40
+15
+30

Nominal system voltage

kV

66

Highest continuous operating voltage

kV

72.5

Rated frequency

Hz

50

Rated Voltage
- primary
- secondary

kV
V

66/3
110/3

Secondary windings

10

Protection winding
- Rated burden
- Accuracy class

VA

100
3P

Metering winding
- Rated burden
- Accuracy class

VA

100
0.2

pf

Not applicable

11

12

Rated Capacitance

13

Insulation levels
- Power frequency withstand voltage
- Lightning impulse withstand voltage

14

kV rms
kVp

Rated voltage factor


- continuos service
- 30 seconds duration

15
16

Temperature rise
Mechanical strength

17

Insulators
- manufacturer
- type
- rated voltage

140
325
1.2
1.5
see Tech. Specs
see Tech. Specs

kV

72.5

Offered

- minimum creepage distance


18

Gaskets

mm

2175
non-ageing
neoprene or
nitrile rubber or
other approved
material

Section IV. Bidding Forms

1-23

8.

Item

66kV OUTDOOR CURRENT TRANSFORMERS

Description
Manufacturer

Type

Insulation Medium

Sealing

Ratios:

Secondary Current

Outputs and Accuracy Class


-

600-300/1/1A
200-100/1/1/1A
A

Rated Extended Primary Current

Rated Insulation Levels


Impulse
Power Frequency for 1 min

10

Creepage Path to Earth

11

Supporting Structures

15VA, 0.2S
15VA, 10P
15VA, 5P

Core 1 (metering)
Core 2 (protection)
Core 3 (protection)

Required

120

kVpeak
kVrms

325
140

mm

2175
Yes

Offered

9.
Item
1

66kV OUTDOOR POST INSULATORS

Description
1.1
1.2
1.3

Required

Manufacturer and Place of Manufacture


Designation and Type
Service Condition

Type/Class

Rated Voltage

Rated Insulation Level (to earth)


- Impulse
- Power Frequency for 1 min

Refer to Tech.
Specs

kV

72.5

kVpeak
kVrms.

325
140

Creepage Path to Earth

mm

2175

Strength Class Chosen

Specify

Calculated Maximum Load on Which the Strength Class


was chosen.

Specify

Do the Post Insulators, when erected, give the required


clearances between conductors and earth?

Have the Type Tests been carried out in accordance


with IEC 60168

Yes

10

Steel Supporting Structure

No

11

Minimum height of steel supporting structure

Yes

mm

N/A

Offered

10.
Item
1

66kV OUTDOOR SURGE ARRESTERS

Description

Required

1.1 Manufacturer and Place of Manufacture


1.2 Designation and Type
1.3 Service Condition

Refer to
Tech. Specs

Type/Class

Nominal Voltage

kV

66

Rated Voltage

kV

60

Nominal Discharge Current

kA

10

IEC Discharge Class

Lightning Impulse Protection Level

Energy Discharge Capacity

Porcelain Housing:
- Lightning Impulse Test Value
- Power Frequency Voltage Test
value

10

Minimum creepage distance

11

Steel Supporting Structure

12

Minimum
Structure

height

of

kVpeak

300

kJ/kV

7.5

kVpeak
kVrms.

325
140

mm

2175
Yes

steel

supporting

mm

N/A

Offered

11.
Item

33kV OUTDOOR LIVE TANK CIRCUIT BREAKERS

Description

Required

Manufacturer

Type Designation

ARC Quenching Medium

SF6

Is the current breaker single pressure, puffer type?

Yes

Rated Voltage

Minimum Rated Normal Current

1250

Rated Short Circuit Breaking Current

kA

31.5

Rated Short Circuit Making Current

kA

50

Interrupting Time

3 cycles

10

First-Pole-To-Clear-Factor

1.5

11

Voltage Range Factor K

1.0

12

Impulse Withstand

13

Rated Transient Overvoltage Factor

14

Rated Line Charging Current

100

15

Rated Cable Charging Breaking Current

50

16

Rated Isolated Shunt Capacitor Bank Current

250

17

Rated Back to Back Shunt Capacitor Bank Current

250

18

Rated Small Inductive Breaking Current

- (Table

19

Rated Transient Recovery Voltage

20

Rated Short Line Fault Line Characteristic

21

Rated Duration of Short Circuit

22

Rated Out-Of-Phase Breaking Current


(with rate of rise 0.43kV/tts)

23

Rated Operating Sequence

kVrms

kV

36

200
2.5

11a
IEC60056)
(Table V IEC
60056)
1sec. (IEC
kA

60056)
0-0.3S-CO-3 minCO

Offered

12.
Item
1

33kV OUTDOOR DISCONNECT SWITCH

Description
1.1 Manufacturer and Place of Manufacture
1.2 Designation and Type
1.3 Service Conditions

Class/Type

Disconnects : Pole Spacing

Rated Voltage

Rated Insulation Level (to earth)


- Impulse (1.2/50 !-s)
- Power Frequency for 1 min

Rated Insulation Level (Across Open Disconnect)


- Impulse
- Power Frequency for 1 min

Creepage Path to Earth (min)

Required

Refer to
Tech. Specs.
Outdoor
mm
kVrms
kVpeak
kVrms
kVpeak
kVrms

1200
36
170
70
195
80

mm

1080

Rated Normal Current

1250

Rated Short Time Current (1sec)

kA

25

10

Rated Peak. Withstand Current

kA

62.5

11

Type of Drive for Disconnect Switch


- At Voltage

12
13

14

VDC

D.C. Motor
110

Have Type Tests been carried out to


IEC 60129 and IEC 60694

Yes

Do the Disconnects Switch as mounted conform to


Specification in the following respects:
- Clearances
- Controls
- Interlocking
- Position Indications

Yes
Yes
Yes
Yes

Steel Supporting Structures

No

Offered

13.
Item
1

33kV OUTDOOR EARTH SWITCH

Description
1.4 Manufacturer & Place of Manufacture

Required

1.5 Designation and Type


1.6 Service Conditions

Refer to Tech.
Specs

Class/Type

Outdoor

Earthing Switch: Pole Spacing

Rated Voltage

kVrms

36

Rated Insulation Level (to earth)


- Impulse (1.2/50 !-s)
- Power Frequency for 1 min

kVpeak
kVrms

170
70

mm

1080

1250

mm

Creepage Path to Earth (min)

Rated Normal Current

Rated Short Time Current (1 sec)

kA

31.5

Rated Peak. Withstand Current

kA

80

10

Mode of Earthing Switch operation

Manual interlocked with


disconnect switches

11

Have Type Tests been carried out

Yes

12

Do the Earthing Switch as mounted conform to


Specification in the following respects:
- Clearances
- Interlocking
- Position Indications

Yes
Yes
Yes

13

Supporting Structures if required

No

Offered

14.

Item
1

33kV OUTDOOR DROP-OUT FUSED DISCONNECT SWITCH

Description
1.1Manufacturer
1.2Designation and Type
1.3Place of Manufacture

Type/Class

Disconnects : Pole Spacing

Rated

Required

mm

500

kVrms.

36

Rated Insulation Level (to Earth)


- Impulse
- Power Frequency for 1 min

kVpeak
kVrms.

170
70

Rated Insulation Level Across Open Disconnect


- Impulse
- Power Frequency for 1 min

kVpeak
kVrms.

195
80

mm

1080

Voltage

Creepage Path to Earth (min)

Rated Normal Current

Rated Short Time Current ( 3 sec)

kA

25

10

Rated Dynamic Withstand Current

kA

80

11

Mode of operation

12

Have Type Tests been carried out to IEC 60129 and


IEC 60694

13

Do the disconnect switch as mounted conform to


specification in the following respects:
-

Clearances
Position

Manual
Yes

Yes
Yes

Offered

15.

Item
1

33kV OUTDOOR POST INSULATORS

Description
1.1 Manufacturer
1.2 Designation and Type
1.3 Place of Manufacture

Type/Class

Rated Voltage

Rated Insulation Level (To Earth)


- Impulse
- Power Frequency for 1 min

Required

kVrms.

36

kVpeak
kVrms.

170
70

Creepage Path to Earth

mm

Strength Class Chosen

Calculated maximum load on which the strength


class was chosen

1080

Do the post insulators, when erected, give the


required clearances of conductors to earth

Yes

Have the type tests been carried out in accordance


with IEC 60168

Yes

Offered

16.

Item
1

33kV OUTDOOR VOLTAGE TRANSFORMERS

Description
1.1Manufacturer
1.2Designation and Type
1.3Place of Manufacture

Type/Class

Insulation Medium

Sealing

Ratios

Secondary Voltages

Outputs and Accuracy Class


- Core 1 for Metering
- Core 2 for Protection

Rated Voltage Factor (Continues)

Rated Voltage Factor (30 sec):

10

Rated Insulation Levels (To Earth)


- Impulse
-

11

Power Frequency for 1 min

Creepage Path to Earth (min)

Required

As Specified
V

115/>3 and
115/3
100VA, 0.2S
100VA, 5P.20

%
1.9

kVpeak
kVrms.
mm

170
70
1080

Offered

17.

Item

33kV OUTDOOR CURRENT TRANSFORMERS

Description
Manufacturer

Type

Insulation Medium

Sealing

Ratios:

Secondary Current

Outputs and Accuracy Class


-

600-300/1/1A
400-200/1/1/1A
A

Rated Extended Primary Current

Rated Insulation Levels


Impulse
Power Frequency for 1 min

10

Creepage Path to Earth

11

Supporting Structures

15VA, 0.2S
15VA, 10P
15VA, 5P

Core 1 (metering)
Core 2 (protection)
Core 3 (protection)

Required

120

kVpeak
kVrms

170
70

mm

1080
Yes

Offered

Section IV. Bidding Forms

1-33

18.
Item
1

33kV OUTDOOR SURGE ARRESTER

Description
1.1Manufacturer
1.2Designation and Type
1.3Place of Manufacture

Required

Type/Class

Normal Voltage

kVrms.

34.5

Rated Voltage

kVrms.

36

Normal Discharge Current

IEC Discharge Class

Lightning Impulse Protection

Energy Discharge Capacity

Porcelain Housing
- Lightning Impulse test value
- Power frequency voltage test value

9
10

Do the surge arresters, when erected, give the


required clearances of conductors to earth
Have the type tests been carried out in accordance
with IEC 60168

kA

10
2

kVpeak

94

KJ/kV

3.0

kVpeak
kVrms.

170
70
Yes
Yes

Offered

19.

Item

STEEL SUPPORTING
EQUIPMENT

STRUCTURES

Description

FOR ELECTRICAL

Required

1.1 Manufacturer
1.2 Designation and Type
1.3 Place of manufacture

Have the supports been fabricated in accordance with


the listed specifications
BS 449
BS 7668

Yes

Have the supports been hot-dip galvanised, after


fabrications, in accordance with BS 729

Yes

Do the supports, when erected, give the required ground


clearances for the supported electrical equipment

Yes
Yes

Is provision made for supporting the electrical equipment


earth lead to earth

Has an earthing screw been provided for earthing


steel structures

Size of earthing screw

Yes

Offered