LG AIR CONDITIONERS

Outdoor Units, 60Hz, R22

6CSS2-01A

LG Airconditioners Product Data

TABLE OF CONTENTS
1
Outdoor Units
Introduction ..............................................................................................................................3
MPS Variable Single A(LUUC(H)-B / R22) ...........................................................................1-1
1

Single A Outdoor Units

Introduction

Introduction
Outdoor Units - R22
(LVNC(H)-B)
Models List
Model name

Series

Power supply

LUUC362B
LUUC482B

Cooling
2 Compressor,
MPS Variable

Single A
Heating

LUUC602B
LUUH362B

1, 220V, 60Hz

LUUH482B
LUUH602B

Indoor Unit Matching


LGs
ual system.

system consist of one outdoor unit which can match with three different indoor units as individ-

The indoor units are ceiling suspended only type.

Outdoor unit

Type

Model name

LUUC362B

LVNC362KLAA

LUUC482B

LVNC482LLAA

LUUC602B
LUUH362B

Indoor unit

Ceiling
suspended
only

LVNC602LLAA
LVNH362KLAA

LUUH482B

LVNH482LLAA

LUUH602B

LVNH602LLAA

Single A Outdoor Units

Introduction

Model Number Nomenclature


1. Outdoor units(Global)
L U U C 3 6 2 B

Serial Number
Electric Standard (Phase, Volts, Freq)
2 : 1, 220v, 60Hz
Nominal Cooling Capacity in Btu/h
36 : 36,000 Btu/h
48 : 48,000 Btu/h
60 : 60,000 Btu/h
Model Type
C : Cooling Only
H : Heat Pump
Indicates that this is a
R22

outdoor unit

Single A Outdoor Units

Single A Outdoor Units

(R22Outdoor Units)
LUUC(H)-B

1
Contents
1. Features & Benefits .............................................................................1-2
2. Specifications.......................................................................................1-3
3. Dimensional Drawings .........................................................................1-6
4. Wiring Diagrams ..................................................................................1-8
5. Piping Diagrams ................................................................................1-11
6. Performance Data..............................................................................1-12
7. The Coefficient of Capacity Change ..................................................1-18
8. Electric Characteristics ......................................................................1-19
9. Operation Limit ..................................................................................1-20
10. Sound Levels .....................................................................................1-21
11. Installation..........................................................................................1-22

Single A Outdoor Units

1-1

Single Split R22 MPS Variable

Features & Benefits

1. Features & Benefits


MPS(Multi Power System) Variable Control
Big Energy Saving with MPS Variable Control
Basic Principle of MPS Variable Control
MPS control provides comfortable and convenient environment as there are two compressors with 60&40%
load sharing with on compressor of small capacity always working to maintain the set temperature conditions &
meanwhile other compressor is at rest if the load is low whereas in conventional system the only compressor is
working with ON/OFF cycles.
Conventional (On/Off Operation)

MPS Control

40%

100%

60%

Comfort Control
- Conventional Operation : The compressor must turn on and off to reach desired temperature setting. A large
portion of power is used during restarting. This causes unnecessary power consumption.
- MPS(Multi Power System) Control : This is a power saving system with two rotary compressors of different
capacity (60% & 40%) operating an A/C at high power until it reaches desired temperature. And when it
reaches the temperature, only the 40% capacity rotary compressor operates.
On

Off

On

Off

(C)
Conventional on/off operation (Single Stage)

27
25
23
21

MPS Control (Multi Stage)

19
100% operation

5'

1-2

Single A Outdoor Units

40% operation

10'

15'

20'

(min)

Single Split R22 MPS Variable

Specifications

2. Specifications
Norminal Capacity and Nominal Input
For combination indoor units + outdoor units :
Indoor Units
LVNC362KLAA
Outdoor Units
LUUC362B
Norminal Capacity Cooling
W(kcal/hr)
10,554(9,072)
Btu/hr
36,000
Heating
W(kcal/hr)
Btu/hr
Nominal Input
Cooling
W
4,050
Heating
W
E.E.R
Cooling W/W(kcal/hrW)
2.6(2.24)
Btu/hrW
8.9
C.O.P
Heating W/W(kcal/hrW)
Btu/hrW
-

LVNH362KLAA
LUUH362B
10,554(9,072)
36,000
10,554(9,072)
36,000
4,050
3,708
2.6(2.24)
8.9
2.8(2.5)
9.7

LVNC482LLAA
LUUC482B
14,067(12,096)
48,000
6,056
2.3(2.0)
7.9
-

Norminal Capacity and Nominal Input


For combination indoor units + outdoor units :
Indoor Units
LVNH482LLAA
Outdoor Units
LUUH482B
Norminal Capacity Cooling
W(kcal/hr)
14,067(12,096)
Btu/hr
48,000
Heating
W(kcal/hr)
14,067(12,096)
Btu/hr
48,000
Nominal Input
Cooling
W
6,056
Heating
W
5,755
E.E.R
Cooling W/W(kcal/hrW)
2.3(2.0)
Btu/hrW
7.9
C.O.P
Heating W/W(kcal/hrW)
2.5(2.1)
Btu/hrW
8.3

LVNC602LLAA
LUUC602B
17,585(15,120)
60,000
6,500
2.7(2.3)
9.2
-

LVNH602LLAA
LUUH602B
17,585(15,120)
60,000
17,585(15,120)
60,000
6,500
5,950
2.7(2.3)
9.2
2.9(2.5)
10.0

Single A Outdoor Units

1-3

Single Split R22 MPS Variable

Specifications

Technical Specification
Outdoor Units
Running Current
Starting Current
Power Supply
Power Factor
Compressor

LUUC362B
Cooling/Heating
A
19/86
Cooling/Heating
1, 220, 60
,V,Hz
%
52
Locked Rotor Amp.
A
Rotary
Type
2
Quantity
No.
QJ278KCB
Model
LG
Maker
4,940(19,600)
Capacity
kcal/hr(Btu/hr)
single phase induction
Motor Type
1,867
Motor Input
W
SUNISO 4GSI
Oil Type
Oil Charge
cc
500
Internal
O.L.P Type(Model Name)
L.E.V
Refrigerant Control
2,250(79.3), R22
Refrigerant Charge
g(oz), type
0.275(7.0)
Outdoor Coil
Tube Size (OD)
inch(mm)
21
Fins per inch
2R 36C
No. of Rows & Column
116
Outdoor fan motor Output
W
OBM-4040B1
Model
6
No. of Poles
190
Input
W
0.61
Running Current
A
6 / 370
Capacitor
F/Vac
Propeller
Outdoor Fan
Type
1/18.1(460)
No. Used / Diameter /inch(mm)
Side Discharge
Discharge
Side / Top
1040
Speed
rpm
58(2,047)
Air Circulation
Outdoor
CMM(CFM)
58
Noise Level (Sound Press,1m) Outdoor
dB(A)3
1/4 (6.35)
SVC Valve
Liquid
inch(mm)
5/8 (15.88)
Gas
Dimensions (W*H*D) Outdoor
inch(mm) 41.1*44.9*17.3 (1045*1140*440)
Net Weight
Outdoor
kg(lbs)
80(176)
3 * 5.5
Power Supply Cable(With Earth Cable)
No.* mm2
4 * 0.75
Conncecting Cable(With Earth Cable)
1/4 (6.35)
Connecting Tube
Liquid Side
inch(mm)
5/8 (15.88)
(. Socket Flare)
Gas Side
inch(mm)
5
Length, std
m
30/15
Max length/elevation
m
17
Drain hose (ID ) Indoor Unit
mm
1452*315*750
Packing Dimension Indoor(W*H*D)
1060*1140*440
Outdoor(W*H*D)
Stuffing Quanity
With(Without)S/Parts
20/40ft
25
Additional Refrigerant Charge(Over 5m)
g
Notes:
1. Capacities are based on the following conditions:
Cooling:
- Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
Heating:
- Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
Piping Length
- Interconnecting Piping Length 7.5m(25ft)
- Level Difference of Zero.

1-4

Single A Outdoor Units

LUUH362B
LUUC482B
19/18
25/86
97
1, 220, 60
1, 220, 60
52
69
Rotary
Rotary
2
2
QJ278KCB
QP362KBA
LG
LG
4,940(19,600)
6,803(27,000)
single phase induction single phase induction
1,867
2,571
SUNISO 4GSI
ATMOS M60 or SUNISO 4GSI
500
700
Internal
Internal
L.E.V
L.E.V
2,250(79.3), R22
3,600(126.9), R22
0.275(7.0)
0.374(9.52)
21
18
2R 36C
2R 44C
116
116
OBM-4040B1
OBM-4040B1
6
6
190
190
0.61
0.61
6 / 370
6 / 370
Propeller
Propeller
1/18.1(460)
2/18.1(460)
Side Discharge
Side Discharge
1040
1040
58(2,047)
105(3,706)
58
62
1/4 (6.35)
3/8 (9.52)
5/8 (15.88)
3 / 4 (19.05)
41.1*44.9*17.3 (1045*1140*440) 35.4*48.0*14.6 (900*1220*370)
80(176)
95(209.4)
3 * 5.5
3 * 8.5
4 * 0.75
4 * 1.25
1/4 (6.35)
3/8 (9.52)
5/8 (15.88)
3/4 (19.05)
5
5
30/15
30/15
17
17
1452*315*750
1850*315*750
1060*1140*440
1060*1220*465
25
50

2. : Full factory charge is shipped in the outdoor unit.


The charge of 36k model is determined based on 7.5m(25ft) of line.
48/60k models : Chargeless for 30m of piping length.
3. Due to our policy of innovation some specifications may be changed without notification.

Single Split R22 MPS Variable

Specifications

Technical Specification
Outdoor Units
Running Current
Starting Current
Power Supply
Power Factor
Compressor

Cooling/Heating
Cooling/Heating

A
,V,Hz
%
A

Locked Rotor Amp.


Type
Quantity
No.
Model
Maker
Capacity
kcal/hr(Btu/hr)
Motor Type
Motor Input
W
Oil Type
Oil Charge
cc
O.L.P Type(Model Name)

Refrigerant Control
Refrigerant Charge
g(oz), type
Outdoor Coil
Tube Size (OD)
inch(mm)
Fins per inch
No. of Rows & Column
Outdoor fan motor Output
W
Model
No. of Poles
Input
W
Running Current
A
Capacitor
F/Vac
Outdoor Fan
Type
No. Used / Diameter /inch(mm)
Discharge
Side / Top
Speed
rpm
Air Circulation
Outdoor
CMM(CFM)
Noise Level (Sound Press,1m) Outdoor
dB(A)3
SVC Valve
Liquid
inch(mm)
Gas
Dimensions (W*H*D) Outdoor
inch(mm)
Net Weight
Outdoor
kg(lbs)
Power Supply Cable(With Earth Cable)
No.* mm2
Conncecting Cable(With Earth Cable)
Connecting Tube
Liquid Side
inch(mm)
(. Socket Flare)
Gas Side
inch(mm)
Length, std
m
Max length/elevation
m
Drain hose (ID ) Indoor Unit
mm
Packing Dimension Indoor(W*H*D)
Outdoor(W*H*D)
Stuffing Quanity
With(Without)S/Parts
20/40ft
Additional Refrigerant Charge(Over 5m)
g

LUUH482B
25/23
97
1, 220, 60
69
Rotary
2
QP362KBA
LG
6,803(27,000)
single phase induction
2,571
ATMOS M60 or SUNISO 4GSI
700
Internal
L.E.V
3,600(126.9), R22
0.374(9.52)
18
2R 44C
116
OBM-4040B1
6
190
0.61
6 / 370
Propeller
2/18.1(460)
Side Discharge
1040
105(3,706)
62
3/8 (9.52)
3 / 4 (19.05)
35.4*48.0*14.6 (900*1220*370)
95(209.4)
3 * 8.5
4 * 1.25
3/8 (9.52)
3/4 (19.05)
5
30/15
17
1850*315*750
1060*1220*465
50

Notes:
1. Capacities are based on the following conditions:
Cooling:
- Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
Heating:
- Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
Piping Length
- Interconnecting Piping Length 7.5m(25ft)
- Level Difference of Zero.

LUUC602B
LUUH602B
27/27/26
104
104
1, 220, 60
1, 220, 60
74
74
Rotary
Rotary
2
2
QP425KBB
QP425KBB
LG
LG
7,937(31,500)
7,937(31,500)
single phase induction single phase induction
2,930
2,930
ATMOS M60 or SUNISO 4GSI ATMOS M60 or SUNISO 4GSI
700
700
Internal
Internal
L.E.V
L.E.V
4,300(151.6), R22
4,300(151.6), R22
0.374(9.52)
0.374(9.52)
18
18
2R 44C
2R 44C
116
116
OBM-4040B1
OBM-4040B1
6
6
190
190
0.61
0.61
6 / 370
6 / 370
Propeller
Propeller
2/18.1(460)
2/18.1(460)
Side Discharge
Side Discharge
1040
1040
105(3,706)
105(3,706)
62
62
1 / 2 (12.7)
1 / 2 (12.7)
3 / 4 (19.05)
3 / 4 (19.05)
35.4*48.0*14.6 (900*1220*370) 35.4*48.0*14.6 (900*1220*370)
95(209.4)
95(209.4)
3 * 8.5
3 * 8.5
4 * 1.25
4 * 1.25
1/2 (12.7)
1/2 (12.7)
3/4 (19.05)
3/4 (19.05)
5
5
50/30
50/30
17
17
1850*315*750
1850*315*750
1060*1220*465
1060*1220*465
50
50

2. : Full factory charge is shipped in the outdoor unit.


The charge of 36k model is determined based on 7.5m(25ft) of line.
48/60k models : Chargeless for 30m of piping length.
3. Due to our policy of innovation some specifications may be changed without notification.

Single A Outdoor Units

1-5

Single Split R22 MPS Variable

Dimensional Drawings

3. Dimensional Drawings
Model No.: LUUC(H)362B
LUUC(H)362B

L1

H
L4

L2

L3

L5

L10 L11

Gas side
3-way valve

L7

L6

L8

Liquid side
2-way valve

L9

Model No.
LUUC(H)362B

Dim
W

mm

870

mm

800

mm

320

L1

mm

370

L2

mm

25

L3

mm

340

L4

mm

775

L5

mm

25

L6

mm

546

L7

mm

162

L8

mm

162

L9

mm

54

L10

mm

74.5

L11

mm

79

1-6

Single A Outdoor Units

Single Split R22 MPS Variable

Dimensional Drawings

Model No.: LUUC(H)48(60)2B


LUUC(H)48(60)2B

L1

L4

L2

L3

L5

L10 L11

Liquid side
3-way valve

L7

L6

L8

Gas side
3-way valve

L9

Model No.
LUUC(H)48(60)2B

Dim
W

mm

900

mm

1,225

mm

370

L1

mm

460

L2

mm

45

L3

mm

410

L4

mm

1,135

L5

mm

90

L6

mm

550

L7

mm

175

L8

mm

175

L9

mm

112

L10

mm

120

L11

mm

83

Single A Outdoor Units

1-7

Single Split R22 MPS Variable

4. Wiring Diagrams
LUUC362B

LUUH362B

1-8

Single A Outdoor Units

Wiring Diagrams

Single Split R22 MPS Variable

Wiring Diagrams

LUUC482B

LUUH482B

Single A Outdoor Units

1-9

Single Split R22 MPS Variable

LUUC602B

LUUH602B

1-10

Single A Outdoor Units

Wiring Diagrams

Single Split R22 MPS Variable

Piping Diagrams

5. Piping Diagrams
LUUC(H)-B
OUTDOOR UNIT

Refrigerant Flow
Cooling
Heating

LED

Liquid

HEAT
EXCHANGER
(CONDENSER)

COMPRESSOR
Gas

Single A Outdoor Units

1-11

Single Split R22 MPS Variable

Performance Data

6. Performance Data
LUUC362B + LVNC362KLAA
Cooling Capacity
Model
AFR
Indoor Air
Temperature
CWB CDB TC
14
20
8.5
16
22
9.9
18
25 11.0
19
27 11.6
22
30 12.7
24
32 13.2

LVNC362KLAA
29
20
SHC
6.6
7.5
8.2
8.5
9.0
9.1

PI
2.8
2.9
2.9
3.0
3.0
3.0

TC
8.3
9.7
10.8
11.3
12.4
12.9

25
SHC
6.6
7.4
8.1
8.4
8.9
9.0

PI
3.3
3.4
3.4
3.5
3.5
3.6

Outdoor Air Temperature : CDB


32
35
TC SHC PI
TC SHC PI
7.9
6.4
3.9
7.7
6.3
4.1
9.2
7.2
4.0
9.0
7.1
4.2
10.3 7.8
4.0 10.0 7.7
4.2
10.8 8.1
4.1 10.5 7.9
4.3
11.8 8.6
4.1 11.5 8.4
4.4
12.3 8.7
4.2 11.9 8.5
4.4

Symbol
AFR : Air flow rate

TC
7.4
8.6
9.6
10.1
11.1
11.5

40
SHC
6.1
6.9
7.5
7.7
8.1
8.2

PI
4.4
4.4
4.5
4.6
4.6
4.7

TC
7.2
8.4
9.4
9.8
10.8
11.2

43
SHC
6.0
6.8
7.4
7.6
8.0
8.1

Notes
[m3/min]

DB : Dry bulb temperature

[C]

1. All capacites are net, evaporator fan motor heat is


deducted.

WB : Wet bulb temperature

[C]

2.

TC : Total capacity

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

[kW]

4. Capacities are based on the following conditions:


- Interconnecting Piping Length 7.5m
- Level Difference of Zero.

PI : Power Input
[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

1-12

Single A Outdoor Units

Indicates nominal capacity.

PI
4.5
4.6
4.6
4.7
4.8
4.9

Single Split R22 MPS Variable

Performance Data

LUUH362B + LVNH362KLAA
Heating Capacity
Model
AFR
Indoor DB
(C)

LVNH362KLAA
29
Outdoor WB(C)
-10

-5

10

15

TC

PI

TC

PI

TC

PI

TC

PI

TC

PI

TC

PI

16

6.9

3.0

8.2

3.3

9.4

3.6

11.0

3.8

11.9

4.0

13.1

4.3

18

6.7

3.1

7.9

3.4

9.1

3.7

10.6

4.0

11.5

4.2

12.7

4.5

20

6.5

3.2

7.7

3.5

8.9

3.8

10.3

4.1

11.2

4.3

12.3

4.6

22

6.3

3.3

7.4

3.6

8.5

3.9

9.9

4.2

10.8

4.5

11.9

4.8

24

6.1

3.4

7.1

3.7

8.3

4.0

9.6

4.4

10.4

4.6

11.5

4.9

Symbol
AFR : Air flow rate

[m3/min]

DB : Dry bulb temperature

[C]

WB : Wet bulb temperature

[C]

TC : Total capacity

[kW]

PI : Power Input
[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the
effect of frost on the heat exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature
(CWB, RH=85%)

-10

-6

-4

-2

Correction Factor

0.95

0.95

0.89

0.87

0.87

0.89

0.91

Notes : 1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7C DB/6C WB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)

Single A Outdoor Units

1-13

Single Split R22 MPS Variable

Performance Data

LUUC482B + LVNC482LLAA
Cooling Capacity
Model
AFR
Indoor Air
Temperature
CWB CDB TC
14
20 11.3
16
22 13.2
18
25 14.7
19
27 15.4
22
30 16.9
24
32 17.5

LVNC482LLAA
36
20
SHC
8.8
10.0
10.9
11.3
12.0
12.1

PI
4.1
4.1
4.2
4.3
4.3
4.4

TC
11.1
12.9
14.4
15.1
16.5
17.2

25
SHC
8.7
9.9
10.8
11.1
11.8
12.0

PI
4.8
4.9
5.0
5.0
5.1
5.2

Outdoor Air Temperature : CDB


32
35
TC SHC PI
TC SHC PI
10.5 8.5
5.6 10.2 8.3
5.9
12.3 9.6
5.7 11.9 9.4
6.0
13.7 10.4 5.8 13.3 10.2 6.1
14.3 10.8 5.9 13.9 10.5 6.2
15.7 11.4 6.0 15.3 11.1 6.3
16.3 11.6 6.0 15.9 11.3 6.4

Symbol

TC
9.8
11.5
12.8
13.4
14.7
15.3

40
SHC
8.1
9.2
10.0
10.3
10.8
11.0

PI
6.3
6.4
6.5
6.6
6.7
6.8

TC
9.6
11.2
12.5
13.1
14.4
14.9

43
SHC
8.0
9.1
9.8
10.1
10.6
10.8

Notes

AFR : Air flow rate

[m /min]

DB : Dry bulb temperature

[C]

1. All capacites are net, evaporator fan motor heat is


deducted.

WB : Wet bulb temperature

[C]

2.

TC : Total capacity

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

[kW]

4. Capacities are based on the following conditions:


- Interconnecting Piping Length 7.5m
- Level Difference of Zero.

PI : Power Input
[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

1-14

Single A Outdoor Units

Indicates nominal capacity.

PI
6.5
6.6
6.7
6.8
6.9
7.0

Single Split R22 MPS Variable

Performance Data

LUUH482B + LVNH482LLAA
Heating Capacity
Model
AFR
Indoor DB
(C)

LVNH482LLAA
36
Outdoor WB(C)
-10

-5

10

15

TC

PI

TC

PI

TC

PI

TC

PI

TC

PI

TC

PI

16

9.3

4.4

11.0

4.8

12.7

5.2

14.7

5.6

16.0

5.9

17.6

6.3

18

9.0

4.5

10.6

4.9

12.3

5.4

14.3

5.8

15.5

6.1

17.1

6.6

20

8.7

4.7

10.3

5.1

11.9

5.6

13.8

6.0

15.0

6.3

16.5

6.8

22

8.4

4.8

9.9

5.3

11.5

5.7

13.3

6.2

14.4

6.5

15.9

7.0

24

8.1

5.0

9.6

5.4

11.1

5.9

12.9

6.4

14.0

6.7

15.4

7.2

Symbol
AFR : Air flow rate

[m3/min]

DB : Dry bulb temperature

[C]

WB : Wet bulb temperature

[C]

TC : Total capacity

[kW]

PI : Power Input
[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the
effect of frost on the heat exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature
(CWB, RH=85%)

-10

-6

-4

-2

Correction Factor

0.95

0.95

0.89

0.87

0.87

0.89

0.91

Notes : 1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7C DB/6C WB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)

Single A Outdoor Units

1-15

Single Split R22 MPS Variable

Performance Data

LUUC602B + LVNC602LLAA
Cooling Capacity
Model
AFR
Indoor Air
Temperature
CWB CDB TC
14
20 13.5
16
22 15.8
18
25 17.6
19
27 18.5
22
30 20.3
24
32 21.0

LVNC602LLAA
40
20
SHC
10.6
12.1
13.1
13.6
14.4
14.6

PI
4.3
4.3
4.4
4.5
4.5
4.6

TC
13.3
15.5
17.3
18.1
19.8
20.6

25
SHC
10.5
11.9
13.0
13.4
14.2
14.4

PI
5.0
5.1
5.2
5.3
5.4
5.4

Outdoor Air Temperature : CDB


32
35
TC SHC PI
TC SHC PI
12.6 10.2 5.9 12.3 10.0 6.2
14.7 11.6 6.0 14.3 11.3 6.3
16.5 12.6 6.1 16.0 12.3 6.4
17.2 13.0 6.2 16.7 12.7 6.5
18.9 13.7 6.2 18.3 13.4 6.6
19.6 13.9 6.3 19.0 13.6 6.7

Symbol

TC
11.8
13.8
15.4
16.1
17.7
18.3

40
SHC
9.8
11.1
12.0
12.4
13.0
13.2

PI
6.6
6.7
6.8
6.9
7.0
7.1

TC
11.5
13.5
15.0
15.7
17.2
17.9

43
SHC
9.7
10.9
11.8
12.2
12.8
12.9

Notes

AFR : Air flow rate

[m /min]

DB : Dry bulb temperature

[C]

1. All capacites are net, evaporator fan motor heat is


deducted.

WB : Wet bulb temperature

[C]

2.

TC : Total capacity

[kW]

3. Direct interpolation is permissible. Do not extrapolate

SHC : Sensible capacity

[kW]

4. Capacities are based on the following conditions:


- Interconnecting Piping Length 7.5m
- Level Difference of Zero.

PI : Power Input
[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

1-16

Single A Outdoor Units

Indicates nominal capacity.

PI
6.8
6.9
7.0
7.1
7.2
7.3

Single Split R22 MPS Variable

Performance Data

LUUH602B + LVNH602LLAA
Heating Capacity
Model
AFR
Indoor DB
(C)

LVNH602LLAA
40
Outdoor WB(C)
-10

-5

10

15

TC

PI

TC

PI

TC

PI

TC

PI

TC

PI

TC

PI

16

11.3

4.7

13.3

5.2

15.4

5.6

17.9

6.1

19.4

6.4

21.4

6.9

18

10.9

4.9

12.9

5.4

14.9

5.8

17.3

6.3

18.7

6.6

20.7

7.1

20

10.6

5.1

12.5

5.5

14.4

6.0

16.7

6.5

18.2

6.8

20.1

7.3

22

10.2

5.2

12.0

5.7

13.9

6.2

16.2

6.7

17.5

7.1

19.3

7.6

24

9.9

5.4

11.6

5.9

13.4

6.4

15.6

6.9

16.9

7.3

18.7

7.8

Symbol
AFR : Air flow rate

[m3/min]

DB : Dry bulb temperature

[C]

WB : Wet bulb temperature

[C]

TC : Total capacity

[kW]

PI : Power Input
[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the
effect of frost on the heat exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature
(CWB, RH=85%)

-10

-6

-4

-2

Correction Factor

0.95

0.95

0.89

0.87

0.87

0.89

0.91

Notes : 1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7C DB/6C WB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)

Single A Outdoor Units

1-17

Single Split R22 MPS Variable

The Coefficient of Capacity Change

7. The Coefficient of Capacity Change


Cooling

Capacity(%)

100

90

36k/48k Cooling

60k Cooling

80

70
5

15

20

25

30

35

40

45

50

Total Pipe Length(m)

Heating

Capacity(%)

100

60k Heating

36k/48k Heating
36k/48k Heating

90

80

70
5

15

20

25

30

35

40

Total Pipe Length(m)


Notes:
* Equivalent pipe length = Actual pipe length + number of bend x 0.3
* Refer to the specification for the maximum pipe length of each model.

1-18

Single A Outdoor Units

45

50

Single Split R22 MPS Variable

Electric Characteristics

8. Electric Characteristics
Models
Indoor Unit

Outdoor Unit

LVNC362KLAA

LUUC362B

LVNH362KLAA

LUUH362B

LVNC482LLAA

LUUC482B

LVNH482LLAA

LUUH482B

LVNC602LLAA

LUUC602B

LVNH602LLAA

LUUH602B

Power Supply

Compressor

Hz, Volts Voltage


range MCA MFA

60, 220

Min.
198V
Max.
242V

MSC

RLA

11.7

20

52

8.6

11.7

20

52

8.6

17.2

30

69

13.0

17.2

30

69

13.0

18.2

30

74

13.8

18.2

30

74

13.8

OFM
kW

0.116

FLA

IFM
kW

FLA

0.61 0.063 0.31

Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(A)

The relationship between the starting time


and starting current

MSC : Maximum Starting Current Amperes(A)


OFM : Outdoor Fan Motor
IFM : Indoor Fan motor
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)

Starting current

RLA : Rated Load Amperes(A)

MSC
RLA

Starting time

Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below
or above listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. Select wire size based on the MCA
4. MFA is used to select the circuit breaker and ground fault circuit interrupter(each leakage circuit breaker).
5. RLA is based on the following conditions.
Indoor temperature : 27 DB / 19.0 WB
Outdoor temperature : 35 DB

Single A Outdoor Units

1-19

Single Split R22 MPS Variable

Operation Limits

9. Operation Limit

Inlet air temperature


(Cooling)

Standard operation
Operation with the
optional low ambient kit

Limit
Outdoor air temperature C D.B.(F)

Item
54(129.2)

43(109.4)

21(69.8)
-10(14)

Middle East model

15(59)

* Note:If the ambient temperature goes below


5C(41F), the capacity drops down even
if the low ambient kit is installed.

24(75.2)

Indoor air temperature C W.B.(F)

Outdoor air temperature C W.B.(F)

Inlet air temperature


(Heating)

18(64.4)

Standard operation

-10(14)
10(50)

24(75.2)

Indoor air temperature C D.B.(F)

Power source voltage

Rating 10%

Voltage at starting

Min. 85% of rating

1-20

Single A Outdoor Units

Single Split R22 MPS Variable

Sound Levels

10. Sound Levels


Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
- Reference accoustic pressure 0dB=20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard(KS conditions).

1m
Microphone

1m

60Hz, 220V

Model

Sound Pressure Levels(dBA)


58
62

LUUC(H)362B
LUUC(H)48(60)2B

Sound Pressure Level


LUUC(H)48(60)2B

90

90

80

80

70
NC-70
NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

Sound Pressure Level (dB re 20Pa)

Sound Pressure Level (dB re 20Pa)

LUUC(H)362B

70
NC-70
NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-30
NC-25

20

NC-20

NC-20

NC-15

10

NC-15

10
63

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Single A Outdoor Units

1-21

Single Split R22 MPS Variable

Installation

11. Installation
11.1 Selection of the best location
If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the
condenser is not restricted.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the
roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop
mounting.

Model : LUUC(H)36(48/60)2B
Ensure that the space around the back is more than 30cm and sides is more
than 30cm. The front of the unit should have more than 70cm of space.

More than
30cm

Su

nro

More than 50cm


(Service space)

of

Fe
ob nce
sta or
cle
s

More than
30cm
More than 50cm
More than 70cm

11.2 Settlement of outdoor unit


Anchor the outdoor unit with a bolt and nut(10mm)
tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber.

1-22

Single A Outdoor Units

Bolt

Tubing connection

Single Split R22 MPS Variable

Installation

11.3 Piping length and the elevation


Pipe Size
(Diameter:)

Capacity

Gas

Liquid

Length

(m)

Elevation

(m)

Standard

Max.

Standard

Max.

*Additional
refrigerant(g/m)

36k Btu/h

5/8"
1/4"
(15.88mm) (6.35mm)

30

30

25

48k Btu/h

3/4"
3/8"
(19.05mm) (9.52mm)

30

30

50

60k Btu/h

3/4"
1/2"
(19.05mm) (12.7mm)

50

30

50

Extra refrigerant = (Extended length - Rated length) x Additional refrigerant.

Outdoor unit

Indoor unit

A
B

A
Outdoor unit

Outdoor unit

Oil trap

B
Indoor unit

B
Indoor unit

CAUTION
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.

Single A Outdoor Units

1-23

Single Split R22 MPS Variable

Installation

11.4 Wiring Connection


1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current as required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.

1) Connecting cables to the Indoor Unit


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively
36K/42K/48K/60K Btu (1, 220V)
(1, 220V)
Terminals on the indoor unit

Terminals on the outdoor unit

1(L) 2(N)

Main power source

: If a power plug is not used, provide a circuit


breaker between power source and the unit as
shown by.

GN

/YL

Capacity
36K BTU/h

1 Phase
5.5mm2

48K/60K
BTU/h

8.5mm2

Circuit Breaker
Use a circuit breake
or time delay fuse.

The connecting cable connected to the indoor and


outdoor unit should be complied with the following
specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).

20

mm

7.5mm

8.5mm

The power cord connected to the outdoor unit


should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR
or SAA).

Air
Conditioner

NORMAL
CROSS-SECTIONAL
AREA 0.75mm2 (36K)
1.25mm2 (48K/60K)

GN

/YL
20

mm

If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer
or its service agent.

Make sure that the screws of the terminal are not loose.

1-24

Single A Outdoor Units

Single Split R22 MPS Variable

2) Connecting the cable to the Outdoor


Unit

Installation

Outdoor unit

1. Remove the Cover control from the unit by


loosening a screw.
Connect the wires to the terminals on the control board individually as following.
2. Secure the cable onto the control board with
the holder (clamper).

Terminal block
Cord Clamper
Power supply
cord
Over 5mm

3. Refix the cover control to the original position


with the screw.
Cover control

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations
to which the unit is subjected during the course of transportation. Check them and make sure that they are
all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal
function of a overload protection device.
Proper starting power is not given to the compressor.

Single A Outdoor Units

1-25

Single Split R22 MPS Variable

ELECTRICAL WIRING
All wiring must comply with local
requirements.
Select a power source that is capable of
supplying the current required by the air
conditioner.
Use a recognized circuit breaker
between the power source and the unit.
A disconnection device to adequately
disconnect all supply lines must be fitted.
Capacity of circuit breaker
Capacity
36K BTU/h
48K BTU/h
60K BTU/h

1 Phase
35A
50A
50A

3 Phase
-

Installation

Perform the electrical wiring work according to


the electrical wiring connection.

Circuit Breaker
Main
power source

Switch box

Outdoor
Indoor

Control terminal board


Cord damper

WIRING CONNECTION

INDOOR UNIT
Remove side panel cover for electrical
connection between the indoor and
outdoor unit.
(Remove crews 1 .)
Use the cord clamper to fix the cord.

OUTDOOR UNIT
Remove the control cover for wiring
connection.
Use the cord clamper to fix the cord.
Earthing work
Connect the cable of diameter 1.6mm2
or more to the earthing terminal
provided in the control box and do
earthing.

Main terminal board


Control terminal board

Cord
clamper
Cover control

Please check !!

1-26

Single A Outdoor Units

20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355


Seoul 150-721, Korea
Phone: 3777-7969 Fax: 3777-5137/8
http://www.lge.com

Approvals:
EN ISO 9001
BS EN ISO 9001
ANSI/ASQC Q9001

P/No.: 3828A20429Y
For continual product development, LG reserves the right to change specifications without notice