Sie sind auf Seite 1von 4

Report No

SKF Haridwar

FIRE HAZARD & PROTECTION


ASSESSMENT

Page

1/4

Date

2015.09.07

Name of Assessors

Mohit Tiwari ,AK Dixit & Nitin


A
1
2
3
4
5
6
7

B
1
2
3
4
5
6
7
8
9
1
0

C
1
2
3
4
5
6
7

D
1
2
3
4
5

Area
Name / Description
Admin Block NE wing first floor
Size of the Area
595 m2
(14m X 42.5 m)
Construction details of the Area RCC under false ceiling
Activities carried out in the
Training and sports activities
Area
Maximum No of Persons at one
Nil
time
Additional Persons that visit the
40
Area
Attach sketch of the Area with exits, escape route, stairs, fire protection /warning
devices, emergency lights, safe areas, high risk areas.

Fuel Source (for Fire)


Wood /paper /cardboard
Furniture and furnishings
Textiles, Clothes
Display materials
Plastics /rubber /foam
Flammable liquids /solvents
/oils
Flammable gases, Vapours
Chemicals
Waste materials
Others

Ignition sources
Smoking materials /matches,
lighters
Friction /sparks
Naked flames /hot work
processes
Lighting equipment
Electrical equipment
Machinery
Others
People at Risk from Fire
(Number)
Employees
Visitors
Contractors
Customers
Suppliers

Paper 150 kgs


Nil
Nil
31 ACP display boards on channel
Nil
Nil
Nil
Nil
Nil
Nil

Nil
Nil
Nil
Nil
Nil
Nil
Nil

Nil
Nil
Nil
Nil
Nil

Report No

SKF Haridwar

FIRE HAZARD & PROTECTION


ASSESSMENT

Others

E
1

Means of Escape
Time for likely spread of fire

Number of Exits

3
4

Widths of Exits
Signs on Exits (visible in dark)
Travel distances to the nearest
exit
Time to escape for all in the
area
Door to open without use of a
key
Obstructions in escape routes
Number of stairways

5
6
7
8
9

F
1
2
3
4
5

Emergency lighting System


Functioing of emergency light
Illumination for escape route
Illumination to show fire exit
doors
Illumination for fire alarm call
points
Illumination for firefighting
eqpt

Illumination for First Aid Box

G
1

Fire Warning Systems


Automatic fire detection
Fire warning system to alert
occupants
Manual call points knowledge
of using
People response to warnings

Fire Fighting Equipment

2
3

Page

2/4

Date

2015.09.07

Nil

90 minutes
Two exits
Reception side
Shivam auto tech side
1.7 metres
Yes, Glows in dark
10 meters
8 secs
Yes,all doors are push mechanism doors
No
Two, One for downstair

Yes
Yes, Illumination of escape routes is marked
Yes, On every door exit sign is marked
Yes, blinks in every second
Yes , Around the floor at the hieght of 3 metres fire
extingusher signs are marked
Yes , Around the floor at the hieght of 3 metres first
Aid Box signs are marked

Yes,Provision of 9 Smoke detectors done


Yes, Fire alarm rings on smoke dectection
Yes, Every associate can operate MCP
Yes, peoples response to alarm

Firefighting equipment provided

Firefighting equipment Appropriate

Pendlum sprinklers -35 covering


Three Fire Extingushers
1 CO2
2 WCO2
Yes,

Report No

SKF Haridwar

FIRE HAZARD & PROTECTION


ASSESSMENT

Firefighting equipment Competence of use

Firefighting equipment Location (on escape


route)

5
6

Fire fighting equipment Accessible &


unobstructed
Fire fighting equipment Checked &
maintained

Fire Safety Signs and Notices

Fire Exit-Keep Clear Notice

Door opening mechanism - Push Bar


to Open
General fire action notices

Fire-fighting equipment indication

Fire hazard area Notice

Observations:
Coments / Concluding Remarks:

Actions to be Taken:

Signature of Assessors:

Page

3/4

Date

2015.09.07

For AHU fire extigushing C02


Extingushers.
For Electrical panels Dry chemical
powder extingusher
Yes, Three trained fire marshals in
every shift
Yes
1. In front of Training room 1
2. In front of UPS room
3. In Tennis court
Yes,all fire fighting euipments are
accessible & unobstructed
Yes, as per maintenance procedures
for fire protection

No, Fire Exit-Keep Clear Notice is not


found
Yes, every door opens in push mechanism
Yes, notice placed in production hall
Yes, Indicators are put on every fire
extingusher
No, Notice is not provided

Report No

SKF Haridwar

FIRE HAZARD & PROTECTION


ASSESSMENT

Mohit Tiwari

Nitin

Page

4/4

Date

2015.09.07

AK Dixit

Verified by:

[Name, Date & Signature]


Date & Signature]

[Name,