Sie sind auf Seite 1von 60

Operation and Maintenance Manual

Bently Nevada Asset Condition Monitoring

1900/25 Vibration Monitor

Part Number 190125-01


Rev. R (01/08)

1900/25 Vibration Monitor Operation and Maintenance Manual

Copyright 1993. Bently Nevada LLC.


All rights reserved.
The information contained in this document is subject to change without notice.
The following are trademarks of General Electric Company in the United States and other
countries:
Trendmaster and Snapshot
The following are trademarks of the legal entities cited:
Sealtite is a registered trademark of Anamet Inc.
Teflon is a registered trademark of DuPont.

ii

Contact Information
The following ways of contacting Bently Nevada are provided for those times when you
cannot contact your local representative:
Mailing Address

Telephone
Fax
Internet

1631 Bently Parkway South


Minden, Nevada USA 89423
USA
1.775.782.3611
1.800.227.5514
1.775.215.2873
www.ge-energy.com/bently

iii

1900/25 Vibration Monitor Operation and Maintenance Manual

Additional Information
Notice:
This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.

Trendmaster 2000 User Guide (Part Number 85000-01)


200150, 200155, and 200157 Accelerometers Information and Installation
Guide (Part Number 164985-01)
89129 and 190520 Accelerometer User Guide (Part Number 89134-01)
Product Disposal Statement
Customers and third parties, who are not member states of the European Union, who are
in control of the product at the end of its life or at the end of its use, are solely
responsible for the proper disposal of the product. No person, firm, corporation,
association or agency that is in control of product shall dispose of it in a manner that is
in violation of any applicable federal, state, local or international law. Bently Nevada LLC
is not responsible for the disposal of the product at the end of its life or at the end of its
use.

iv

Contents
1. 1900/25 Vibration Monitor Description..................................................... 1
1.1
1.2

Features................................................................................................................................................. 1
Monitor Connections, Indicators, & Controls ........................................................................ 4

2. Installation ...................................................................................................... 6
2.1
2.1 Receiving Inspection.................................................................................................................... 6
2.2
Jumper Settings................................................................................................................................... 6
2.2.1 Setting Relays for Latching or Non-Latching Behavior............................................... 6
2.2.2 Setting Relays for Normally Energized or Normally De-energized Behavior .... 7
2.2.3 Setting Trendmaster 2000 Behavior During 1900/25 Monitor Bypass ............ 8
2.2.4 Internal Jumper Location ......................................................................................................... 9
2.3
Monitor Enclosure ............................................................................................................................... 9
2.4
Configuration Switch SettingS...................................................................................................10
2.4.1 Relay Time Delay ........................................................................................................................10
2.4.2 Alert Relay Alarm Conditions.................................................................................................10
2.4.3 Configuring the Display for English or Metric Units ....................................................11
2.4.4 Initiating Self Test .......................................................................................................................11
2.5
Connecting Remote Reset...........................................................................................................12
2.6
Trendmaster2000 Connections ..................................................................................12
2.6.1 Connecting the Trendmaster 2000 System Cable to the 1900/25 Monitor.13
2.6.2 Trendmaster 2000 Address ...............................................................................................15
2.7
Relay Connections .............................................................................................................................16
2.7.1 Alert Relay Configuration........................................................................................................16
2.7.2 Relay Internal Jumper Settings............................................................................................18
2.7.3 Relay Electrical Connections .................................................................................................18
2.8
Power Connections ........................................................................................................................20
2.8.1 Types of Power Connections.................................................................................................20
2.8.2 Power Electrical Connections ...............................................................................................20
2.9
Field Wiring Diagram........................................................................................................................22

3. Monitor Operation ....................................................................................... 23


3.1
Monitor Display ................................................................................................................................23
3.1.1 English or Metric Display Units.............................................................................................23
3.1.2 The Display Mode Switch........................................................................................................24
3.1.3 Display Error Codes ...................................................................................................................25
3.2
LED Indicators...................................................................................................................................27
v

1900/25 Vibration Monitor Operation and Maintenance Manual


3.3
Relay ModeSwitch.............................................................................................................................28
3.4
Setpoint Adjustment .......................................................................................................................28
3.5
Resetting the Monitor.....................................................................................................................30
3.6
Buffered Transducer Output ......................................................................................................30
3.7
Initiating a Self Test ........................................................................................................................30

4. Maintenance & Troubleshooting ...............................................................31


4.1
General Maintenance....................................................................................................................31
4.2
Monitor Adjustments .....................................................................................................................32
4.2.1 LCD Zero Adjustment................................................................................................................32
4.2.2 Adjustment of the Monitor's Trendmaster 2000 Interface ..................................34
4.3
Troubleshooting...............................................................................................................................37

5. Appendix A - Performance Specifications................................................40


5.1
1900/25 Monitor Specifications................................................................................................40
5.1.1 Mechanical Specifications......................................................................................................40
5.1.2 Environmental Specifications Temperature Range: ...................................................40
5.1.3 Monitor Power Specifications ...............................................................................................42
5.1.4 Relay Specifications ..................................................................................................................42
5.1.5 Signal Conditioning....................................................................................................................42
5.1.6 Accuracy.........................................................................................................................................43
5.1.7 LED Indicators..............................................................................................................................43
5.1.8 Monitor Controls .........................................................................................................................43
5.1.9 Trendmaster 2000 Interface Specifications ...............................................................44

6. Appendix B - Peak Detection Methods .....................................................45


6.1

Peak Detector Theory....................................................................................................................45

7. Appendix C - Trendmaster 2000 Address Settings .............................46


8. Appendix D - 1900/25 Monitor Configuration Form ..............................49
9. Appendix E - Accessories and Spare Parts ..............................................51
9.1
9.2

10.

vi

Installation Hardware....................................................................................................................51
Spare Parts.........................................................................................................................................53

Appendix F - Hazardous Area Approvals..............................................54

Section 1 - 1900/25 Vibration Monitor Description

1. 1900/25 Vibration Monitor Description


The 1900/25 Vibration Monitor provides continuous vibration monitoring for
machinery where most of the shaft vibration is transmitted through the bearing to
the case. Vibration amplitude is a primary indicator of the overall mechanical
condition of rotating machinery. Many machine malfunctions, including rotor
imbalance, misalignment, and bearing wear can be detected with vibration
measurements. Typical applications include general purpose and essential
machines with roller element bearings like pumps, fans, and compressors.
This section helps familiarize you with the monitor by listing the features that
make the monitor flexible and describing the monitor controls that make the
monitor easy to use.

1.1 Features
The features of the 1900/25 Vibration Monitor make the monitor more reliable
and easier to use. Many of these features have been used on previous Bently
Nevada monitors and have proven to be useful for protecting machinery. You can
program some of the features of the monitor by using jumpers or the 6-position
Configuration switch.
Some of the non-programmable features are described below.
Transducer separate from monitor - Mounting only the transducer on the machine
requires less space and makes the transducer easier to install on small
machinery. Mounting the monitor away from the machine protects the monitor
from the harsh machine enviroment that is less suitable for electronic
instrumentation. This location makes it easier and safer for plant personnel to
access the monitor.
Digital LCD display - A digital liquid crystal display on the front of the monitor
indicates overall vibration or the Alert or Danger setpoints. Because the monitor is
designed to be mounted close to the machine rather than on the machine, the
monitor can be located where service personel can read it easily.
Status LED indicators - Four LEDs on the front of the monitor indicate the status of
the monitor. These LEDs show whether the monitor is OK, in alarm, or bypassed.
Remote Reset - A front panel reset button and remote reset terminals let you reset
latched relays or flashing LEDs without turning the monitor off. The remote reset
terminals allows the monitor to be reset from a remote location without having to
open the weatherproof enclosure.

1900/25 Vibration Monitor Operation and Maintenance Manual


Relay BYPASS - A relay BYPASS switch lets you disable both relays while you
adjust the relay setpoints or maintain the machinery. This feature prevents false
alarms or undesired machinery shutdowns. When the monitor is bypassed, the
red BYPASS LED is on.
Coaxial connector - A coaxial connector on the front of the monitor provides a
buffered velocity signal (500 mV/in/s or 20 mV/mm/s) for locally sampling dynamic
data. The connector provides direct access to the integrated transducer signal
which can be used to diagnose and analyze machinery.
Two alarm relays - The monitor has two single-pole, double-throw relays (Type 2
FORM C). Use these relays as inputs to the machinery control circuits, or to drive
alarm annunciators such as a bell or light on an alarm panel. You can also wire
these relays together with other relays into an AND or OR voting logic scheme.
Although typically used as an Alert relays, you can reconfigure the Alert relay to
become a NOT OK relay, an Alert logically OR'ed with NOT OK relay, or an auxiliary
Danger relay. The relay circuits include arc suppressors to increase relay contact
life expectancy and reduce arcs in hazardouslocations.
Trendmaster 2000 Interface - This interface lets you use the Trendmaster 2000
to access the velocity signal that is obtained when the monitor integrates the
transducer signal generated by the Accelerometer. This allows the vibration data
to be trended and graphes such as spectrum and time base plots to be obtained.
Any potential machine problem can be investegated on-line with the Trendmaster
2000 before going to the machine site.
True peak measurements - The 1900/25 Vibration Monitor uses an analog peak-topeak detector to determine the peak vibration amplitude. This method is more
accurate than methods which measure the RMS level and attempt to convert it to
peak value. The RMS method is poor because it applies the conversion factor for
pure sinusoidal signals even though machinery vibration is rarely a pure sine wave
(see Appendix B).
Timed OK/Monitor Defeat - This special proprietary circuit minimizes the possibility
of false alarms caused by a defective transducer, transducer wiring, or -transducer
power supply.
Power-up Inhibit - This feature minimizes false alarms caused by a transient power
surge or interruption of power.
Monitor Self Test - The monitor conducts a self test which checks the monitor's
power supply voltages and verifies the signal path when you power up the
monitor or when you initiate a self test during operation of the monitor.
Programmable options provide flexibility and a wide range of standard features.
Internal Jumper Options:
Normally Energized/De-energized Relays - The Alert and Danger relays can be be
either normally energized or normally de-energized. The normal condition of a
2

Section 1 - 1900/25 Vibration Monitor Description


relay corresponds to its non-alarm condition. For example, a normally energized
relay would have power on the coil (ARM contacts NO) when it is not in alarm and
would remove power from the coil (ARM contacts NC) when it goes into alarm. Both
relays are independently set.
Latching/Nonlatching Relays - The Alert and Danger relays can be either latching
or nonlatching. Latching alarms must be cleared using the reset button or by
closing a switch between the reset terminals. Nonlatching alarms automatically
reset when the monitor no longer detects an alarm condition. Both relays are
independently set.
Trendmaster 2000 Behavior during BYPASS - When the monitor is switched to
BYPASS, the Trendmaster 2000 host computer indicates NOT OK and does not
collect dynamic data. Since some applications require dynamic data collection
during BYPASS, you can set the monitor so that it collects data even when the
alarms are bypassed.
Front Panel 6-position Configuration Switch Options:
Relay Time Delay - The Alert and Danger relay time delays can be set for 3, 5 , 10,
or 15 seconds. Relay time delay is the amount of time that the vibration level must
be greater than the alarm setpoint level before an alarm trips. The time delay
minimizes false alarms from either "normal" transient vibration or electrical noise
sources. The relay time delay setting applies to both relays as long as both are
configured to activate under an alarm condition.
Alert Relay Configuration - To help you use the monitor for different applications,
the Alert relay can be set to activate under any of the following conditions:
Alert
Alert or NOT OK
NOT OK
Danger (as an auxiliary Danger relay)
Units - You can set the overall vibration level shown on the LCD display to display in
either English (in/s) or metric (mm/s) units. Both units are true zero to peak
measurements, not RMS measurements converted to peak.
Monitor Self Test - A user-invoked self test switch is provided to aid in field
troubleshooting. When you invoke the self test, the signal path and alarm
threshold detection circuits are verified. All LEDs and LCD numerical segments
turn on at the beginning of the self test to verify that they are operating properly.
The power supplies are checked continually.

1900/25 Vibration Monitor Operation and Maintenance Manual

1.2 Monitor Connections, Indicators, & Controls


The connections, LEDs and LCD, and control switches are shown in the next
three figures.

Figure 1-1: Location of monitor connections

Section 1 - 1900/25 Vibration Monitor Description

Figure 1-2: Location of status LED indicators and LCD display location.

Figure 1-3: Location of monitor switches and reset button

1900/25 Vibration Monitor Operation and Maintenance Manual

2. Installation
This section describes how to install the 1900/25 Vibration Monitor. It includes
information on how to configure the monitor for your particular application using
the monitor's internal jumpers and the configuration switches on the front panel.
This section also describes how to connect the Accelerometer to the 1900/25
Vibration Monitor.

2.1 2.1 Receiving Inspection


Inspect the components of the order as soon as you receive them to see if there
was any damage during shipment. Keep all shipping forms and invoices. If any
shipping damage is apparent, file a claim with the carrier and submit a copy to
Bently Nevada Corporation. Include all model numbers and serial numbers with
the claim. We will either repair or replace damaged parts according to the terms
and conditions of the sale.
A plastic cover will be over the display when the monitor is shipped from Bently
Nevada. Remove the cover from the label either when you receive the monitors or
during installation.

2.2 Jumper Settings


Use internal jumpers to program each relay as latching or non-latching and
normally energized or de-energized. Use the Bypass Mode jumper to program
what Trendmaster 2000 does during relay bypass.

2.2.1 Setting Relays for Latching or Non-Latching Behavior


A latching relay stays in an alarm state even after the vibration has dropped
below the setpoint level for that relay. A non latching relay moves from its alarm
state to its non-alarm state once the vibration drops back below the setpoint level
for that relay. Table 2.1 describes how to set jumpers W7 and W8 to control
latching and non latching behavior for the Alert and Danger relays.

Section 2 - Installation

TABLE 2.1: Latching/Non-latching Jumper Settings


OPTION

JUMPER SETTING
install

remove

W8

Alert nonlatching

W8

Danger latching*

W7

W7

Alert latching*

Danger nonlatching
* Factory default setting

2.2.2 Setting Relays for Normally Energized or Normally De-energized


Behavior
The Normally Energized/De-energized option controls whether power is applied
to the relay coil during an alarm state or during a non-alarm condition. For
normally de-energized relays, no power is applied to the relay coil during nonalarm conditions. Power is applied during alarm conditions. For normally
energized relays, power is applied to the relay coil during non-alarm conditions.
Power is removed during alarm conditions. Normally energized relays are useful
when you want to shut a machine off when vibration monitoring stops due to loss
of monitor power. Table 2.2 shows how to set jumpers W5 and W6 for Normally
De-energized or Normally Energized Alert and Danger Relays.

TABLE 2.2: Normally Energized and Normally


De-energized Jumper Setting
OPTION

Alert Normally De-energized*


Alert Normally Energized
Danger Normally De-energized*
Danger Normally Energized

JUMPER SETTING
install

remove

W6

W6

W5

W5

* Factory default setting

1900/25 Vibration Monitor Operation and Maintenance Manual

2.2.3 Setting Trendmaster 2000 Behavior During 1900/25 Monitor


Bypass
With the BYPASS Mode jumper installed the Trendmaster 2000 system responds
to a relay bypass condition at the monitor by placing a NOT OK flag on this point
and placing a time and date message in the alarm list. Even though the relays are
in BYPASS, the monitor remains OK and continues to monitor vibration. The
Trendmaster 2000 system is unable to continue logging data when this jumper is
in, but visibility of a bypass condition is maintained by making it impossible to
place a point in bypass without it being recorded by the Trendmaster 2000.
With the BYPASS Mode jumper removed the Trendmaster 2000 software will not
flag a NOT OK indication for that point and there will not be a date and time log
placed in the alarm list when the monitor is placed into BYPASS. However, the
Trendmaster 2000 software will be able to log vibration data while the monitor
is in relay BYPASS mode.
Table 2.3 shows how to use the Bypass Mode jumper to control how Trendmaster
2000 responds when the monitor is bypassed.

TABLE 2.3: Bypass Mode Jumper Settings


Bypass
mode

Response of Trendmaster 2000 when the monitor's relays are


bypassed

jumper
(W4)

Flag the point


as NOT OK

installed*
removed

Yes
No

Enter NOT OK
in the Alarm
List
Yes
No

Trend vibration when


relays are bypassed
No
yes

* Factory default setting

To determine realistic setpoint values for a machine, we recommend that you


collect data for a few weeks with the relays disabled and the bypass jumper
removed. Use this configuration only long enough to collect sufficient trend data
on the Trendmaster 2000 to determine where to adjust the Alert and Danger
setpoints. After you establish realistic setpoints, install the bypass mode jumper
and return to the normal monitoring mode by placing the relay mode switch in
the NORMAL positrion.

Section 2 - Installation

2.2.4 Internal Jumper Location


Figure 2.1 shows the location of the jumpers on the monitor's circuit board.
To set the jumpers follow these steps:
1. Remove the case cover: Pull the case cover straight up. The inside of the
case cover has a label that summarizes the jumper settings.
2. Locate the five jumpers along the side of the top board (see Figure 2-1).

Figure 2-1: Location of internal jumpers.


3. Remove or insert any of the jumpers that are required for your given
application.
4. Snap the case cover back into place over the printed circuit boards.

2.3 Monitor Enclosure


Use a TYPE 4X enclosure for outdoor and Class 1, Division 2 hazardous areas. If
the monitor will be in a nonhazardous location where it is protected from the
elements, then a weatherproof enclosure is not required. Bently Nevada offers a
nonmetallic Type 4X enclosure (Bently Nevada Part Number 190100-01) or a
stainless steel RFI resistant Type 4X enclosure (Bently Nevada Part Number
03636315) for 1900 monitors. Both have windows on the front so that the LCD
display of the monitor is visible from outside the enclosure. Appendix D provides
ordering information. For more information on Bently Nevada's Type 4X enclosures
for the 1900 monitor, contact your local Bently Nevada sales representative.

1900/25 Vibration Monitor Operation and Maintenance Manual

2.4 Configuration Switch SettingS


Use the 6-position configuration switch on the front panel of the monitor to
program the relay time delays, the alert relay alarm condition, English or metric
units, and to initiate a monitor self test.

2.4.1 Relay Time Delay


Relay time delay is the amount of time that the vibration must continuously
exceed the setpoint before an alarm occurs. Table 2.4 shows the relay time delay
switch settings.

TABLE 2.4: Relay Time Delay Settings


Switch 1

Switch 2

Time Delay

Off

Off

3 seconds

Off

On

5 seconds

On

Off

10 seconds

On

On

15 seconds

2.4.2 Alert Relay Alarm Conditions


Alert relay alarm settings let you configure the Alert relay to be driven by the
following 4 conditions: the Alert setpoint, the Alert setpoint logically OR'ed with
NOT OK, NOT OK, or the Danger setpoint. If you configure the relay to be driven
from NOT OK or the Danger setpoint, the Alert setpoint is no longer used. Table 2.5
shows the Alert relay drive condition settings.

Table 2.5: Alert Relay Alarm


Condition Settings

10

Switch 3

Switch 4

Alert Drive

Off

Off

ALERT

Off

On

ALERT OR NOT OK

On

Off

NOT OK

On

On

DANGER

Section 2 - Installation

2.4.3 Configuring the Display for English or Metric Units


English/Metric Units lets you choose which measurement units are used to display
the overall vibration level on the LCD as shown in Table 2.6. You may need to readjust the zero of the display slightly if you change the units. Refer to section 4.2.1
to calibrate the LCD zero.

Table 2.6: English/Metric


Units Settings
Switch 5

Setting

Units

Off

English

Inches/second

On

Metric

Millimetres/second

2.4.4 Initiating Self Test


Initiate a Self Test by setting switch 6 to the ON position. Return switch 6 to the
OFF position once the test has started. The following actions occur during a
monitor self test, which lasts approximately 30 seconds:

The relays are placed in their non-alarm states.


Numerical segments of the LCD turn on for the duration of the self test.
All LEDS turn on for the first 4 seconds of the self test.
The signal path circuits are tested
The alarm threshold detection circuitry is tested.

If an error is detected during self test, an error code will remain on at the end of
the self test. Error codes El and E3 are continually tested for during normal
operation. If a power supply failure occurs, El comes on. If a NOT OK occurs, the
OK LED goes off and E3 comes on. Error code E2, a signal path error, can only be
detected using the self test function. The error codes are shown in Table 2.7.

11

1900/25 Vibration Monitor Operation and Maintenance Manual

Table 2.7: Self Test Error Codes


Code

Error

E1

Power

E2

Signal Path

A fault exists in the vibration


signal path, the alert or
danger threshold detection
circuits, or the system clock.

E3

NOT OK

The transducer, transducer


cable, or transducer power
supply are not functioning
properly.

Explanation
The internal power supply
voltages are not within
tolerance.

2.5 Connecting Remote Reset


Mounting an external reset switch (or button) at a remote location lets you reset
the monitor without having to open the weatherproof housing. The remote reset
switch can be mounted up to 305 m (1000 ft) from the monitor. Connect the
remote reset switch between the REMOTE RESET A and B contacts. Use a singlepole single-throw (SPST) type switch with normally open contacts which are
momentarily closed by the switch actuator.

2.6 Trendmaster2000 Connections


The Trendmaster 2000 system lets you use an IBM-PC compatible computer to
collect and trend data from as many as 2054 different points. The system also
allows you to analyze vibration data by presenting Timebase and Spectrum plots.
This section shows how to connect the 1900/25 monitor to a Trendmaster 2000
system as a velocity point. Although the 1900/25 monitor can operate without the
Trendmaster 2000 system, the system lets you collect data automatically, then
use the data to generate Trend, Timebase, and Spectrum plots.

12

Section 2 - Installation

2.6.1 Connecting the Trendmaster 2000 System Cable to the 1900/25


Monitor
Use insulation displacement connector (IDC) cable to connect the Trendmaster
2000 system cable to the monitor.
Use the following tools to attach the cable to the 1900/25 monitor:

Trendmaster 2000 system cable (Bently Nevada part number 8503302-00)


An IDC connector installation tool (Bently Nevada part number 8571801)
A wire stripper to remove insulation from the cable

To attach the IDC connector to the cable, follow these steps:


1. Strip 25 to 32 mm (1 to 1.25 in) of outer insulation and foil from the end of
the cable. Do not strip the insulation from the individual wires in the cable.
2. Remove the snap-on cover from the IDC connector.
3. Use the installation tool shown in Figure 2-5 to attach the connector to the
wires using Figure 2-6 as a guide. Make sure the head that holds the
connector is in the locked position. Load the connector from the left side of
the tool as viewed from the handle end.
4. Check that the wires are inserted all the way to the bottom of the pins and
to the end of the connector. If the wires do not extend to the end, cut the
wires at the connector and install a new connector. Do not reconnect a
connector that has been previously attached to wires. See the appendix on
"Spare Parts" in the Trendmaster 2000 User Guide (Bently Nevada part
number 85000-01) for more details on the connectors.
5. Place the snap-on cover onto the connector.
6. Seat the connector in the Trendmaster 2000 socket on the 1900/25
monitor. There are two sockets for Trendmaster 2000. One of the sockets is
for the cable coming from the Trendmaster 2000 computer. The other
socket is for the line going out to the next 1900 monitor or Transducer
Interface Module (TIM). Refer to Figure 2-10.

13

1900/25 Vibration Monitor Operation and Maintenance Manual

Figure 2-10: Trendmaster 2000 Connections

14

Section 2 - Installation

2.6.2 Trendmaster 2000 Address


Use the 8-position address switch to set a unique address. Appendix C lists the
addresses and corresponding switch settings. Write the address and point name
on a copy of the 1900/25 configuration form (provided in Appendix D). Figure 2-11
shows the positions of the 8 address switches for three different address settings.
Switch number one of the 8-position address switch corresponds to the most
significant bit (MSB) of the address. Switch 8 corresponds to the least significant
bit (LSB). Since zero is an invalid address, do not set all eight switches to the off
position.

Figure 2-11: Sample Trendmaster 2000 address settings.

15

1900/25 Vibration Monitor Operation and Maintenance Manual

2.7 Relay Connections


Alert and Danger relays give two levels of alarm. Use the Alert relay to
annunciate high vibration that is nearing the Danger (shutdown) setpoint. Possible
annunciators include a buzzer, horn, light, or a signal sent to the plant computer.
The Danger relay is dedicated to the Danger setpoint and will go into its alarm
state when the vibration level exceeds the Danger setpoint.

WARNING
A missed trip or false trip can occur if the Alert relay
is used to signal a shutdown. Only the Danger relay,
because it is dedicated to the Danger setpoint, is
intended for machinery protection (shutdown) in the
event of high vibration. The Alert relay is intended for
non-machinery protection functions, such as
annunciating a high vibration condition or a system
fault (NOT OK), or for starting a spare machine in the
event a primary machine is shutdown by the Danger
relay as a result of high vibration in the primary
machine.

2.7.1 Alert Relay Configuration


The Alert relay can be configured in the field to give an alarm condition from one
of four different conditions: Alert setpoint, Alert setpoint logically OR'ed with NOT
OK, NOT OK, and the Danger setpoint. Section 2.5.2 shows how to set this relay.
Table 2.8 lists the Alert relay configurations and the suggested application for each
one.

16

Section 2 - Installation

TABLE 2.13: Suggested Applications for


Different Alert Relay Configurations
Alert Relay
Driven By
alert setpoint
Alert setpoint
OR'ed with OK
relay
OK relay*
Danger
setpoint *

Relay Enters Alarm


State When
vibration level exceeds
the Alert setpoint
vibration level exceeds
the Alert setpoint or the
monitor is not OK
the monitor is not OK
vibration level exceeds
the Danger setpoint

Suggested Applications
Notify that the machine is
vibrating at a level
approaching the Danger
setpoint
Notify that the vibration of
the machine is high or that
a fault exists with the
transducer, the transducer
wiring, or the transducer
power supply
Notify that a fault exists
with the transducer, the
transducer wiring, or the
transducer power supply
Start up a spare machine
when the primary machine
is shutdown by the Danger
Relay

* The Alert setpoint is ignored in these Alert relay configurations;


however, the Alert LED will illuminate when the Alert relay is in its alarm
state.

17

1900/25 Vibration Monitor Operation and Maintenance Manual

2.7.2 Relay Internal Jumper Settings


Section 2.2.4 shows how to set the Relay option. Table 2.9 summarizes the effect
of the Relay option.

TABLE 2.14: Relay Connections by Normally


Energized/De-energized Jumper Settings
TERMINAL

RELAY OPTION SETTING (state of


the relay with no alarm)
Normally Deenergized

Normally Energized

closed

open

ARM

ARM

open

closed

closed

open

ARM

ARM

open

closed

If the relay is configured as normally energized then the normally open (NO) and
normally closed (NC) connections are reversed from that shown on the label. Use
normally energized if you want the relay to change state if the monitor loses
power.

2.7.3 Relay Electrical Connections


The following tools and supplies are required for connecting cable to the relay
terminal strip:

18

Wire stripper
Crimp tool
A phillips or straight screwdriver
Crimp type ring or spade lugs
Cable (maximum conductor size: 16 AWG)

Section 2 - Installation
To install the cable to the terminal strip follow these steps:
1.

If an outer jacket is on the relay cable then strip off about 25 mm (1 in) of outer
insulation from the cable.

2.

Strip 6 mm (0.25 in) of insulation from each of the conductors that will be
used by the relay.

3.

Crimp a ring or spade lug to each of the conductors using the crimp tool.

4.

Open the hinged protective cover over the power and relay terminal strip.

5.

Place each lug under the proper screw on the relay terminal strip (see Figure 2-12)
and use the screwdriver to tighten the screw.

6.

Close the hinged protective cover over the terminal strip.

Figure 2-12: Alert and Danger Relay Connections

19

1900/25 Vibration Monitor Operation and Maintenance Manual

2.8 Power Connections


The power supply options are 110/220 AC and HVDC, or +24 Vdc. All monitors,
regardless of the type of power supply that is chosen, are protected by an internal
fuse.

2.8.1 Types of Power Connections


Connect power to the monitor as shown in Table 2.10.

TABLE 2.15: Monitor Power Connections


INPUT VOLTAGE
110 Vac

220 Vac

24 Vdc

CONNECTIONS
1
2
3
1
2
3
1
2
3

Line
Neutral
Ground
Line 1
Line 2/Neutral
Ground
+24 Vdc
Common
Ground

2.8.2 Power Electrical Connections


Use these tools and supplies to connect cable to the power terminal strip:

20

Wire stripper

Crimp tool

A phillips or straight screwdriver

Crimp type ring or spade lugs

3 conductor cable (maximum conductor size: 16 AWG)

Section 2 - Installation
To install the cable to the terminal strip follow these steps:
1. If an outer jacket is on the power cable then strip off about 25 mm (1
in) of outer insulation from the cable.
2. Strip 6 mm (0.25 in) of insulation from each of the conductors that will
be connected to the power terminals.
3. Crimp a ring or spade lug to each of the conductors using the crimp
tool.
4. Open the hinged protective cover over the power and relay terminal
strip.
5. Place each lug under the proper screw on the power terminal strip
(see Figure 2-13) and use the screwdriver to tighten the screw.

Figure 2-13: Power Connections


6. Close the hinged protective cover over the terminal strip.

21

1900/25 Vibration Monitor Operation and Maintenance Manual

2.9 Field Wiring Diagram


A typical field wiring diagram is shown below.

Figure 2-14: Typical 1900/25 field wiring installation.

22

Section 3 - Monitor Operation

3. Monitor Operation
This section describes how to operate the monitor. Included is information about
the displays and indicators and how to interpret the information they provide.

3.1 Monitor Display


The liquid crystal display (LCD) on the front panel of the 1900/25 monitor shows
vibration data in either English or Metric units. The display can also show the
current Alert and Danger setpoint levels and error codes.

3.1.1 English or Metric Display Units


Velocity units can be displayed on the LCD in either English units (in/s), or in Metric
units (mm/s). Figure 3-1 shows the arrow on the right side of the LCD that points
to the units which the display is currently using. Change the velocity units by
setting switch 5 to the desired units on the 6-position configuration switch You
may need to re-adjust the zero of the display slightly if you change the units.
Refer to section 4.2.1 to calibrate the LCD zero.

Figure 3-1: Location of English and Metric LCD unit indicators.

23

1900/25 Vibration Monitor Operation and Maintenance Manual

3.1.2 The Display Mode Switch


Setpoint levels can be shown on the display by using the three-position Display
Mode switch. The positions of the Display Mode switch are Normal, Alert, and
Danger. Table 3.1 shows the effects of the Display Mode on the LCD.

Table 3.1: Display Mode Switch


SWITCH SETTING

DISPLAY

DESCRIPTION
The LCD displays
overall vibration in
units of in/s.

The LCD displays the


Alert Setpoint in
units of in/s.

The LCD displays the


Danger Setpoint in
units of in/s.

24

Section 3 - Monitor Operation

3.1.3 Display Error Codes


Error codes are displayed on the left side of the LCD as shown in Figure 3-2. If an
error is detected the appropriate error code is displayed on the LCD. There are
three error codes:
E1

Power supply error (continuously checked)

E2

Signal path error (checked only during self test)

E3

NOT OK error (continuously checked).

The Maintenance and Troubleshooting section, Section 4, contains information


about how to resolve these errors.

Figure 3-2: Location of Error Indicators.


Error code E1 indicates a power supply error. The regulated power supplies inside
the 1900/25 monitor are continuously checked. If they fall outside of the
acceptable power supply range the monitor displays the El error code. An El error
could be caused by a poor power source external to the monitor, or a fault could
exist within the monitor itself.

25

1900/25 Vibration Monitor Operation and Maintenance Manual


Error code E2 is caused by a fault in the signal path. A signal path fault can only
be detected during a user initiated self test. If a signal path error is detected during
a self test, then an E2 error code will be shown on the LCD display. The signal path
check, which is made during self test, verifies that the peak-to-peak detector and
the setpoint threshold detectors are working properly. A signal path error could
mean that there is an internal fault within the 1900/25 monitor.
Error code E3 occurs when the monitor goes into a NOT OK situation. The monitor
continuously verifies that the system is OK. If it detects that a transducer input
signal is outside the expected range a NOT OK will result. A NOT OK may be
caused by faulty transducer field wiring, a bad transducer, or a bad connection.

26

Section 3 - Monitor Operation

3.2 LED Indicators


Four LED indicators on the 1900/25 monitor front panel show the status of the
monitor. They indicate whether the monitor and transducer are OK, if either the
Alert or Danger relay is in alarm, and whether the relays are bypassed. Table 3.2
summarizes how the LED operate.

Table 3.2: LED Indicators


OK LED

INDICATION

on

Monitor is operating properly and receiving a valid


transducer signal

off

Monitor is not OK

flashing
ALERT LED

Monitor was not OK and then returned to OK


INDICATION

off

Alert condition not detected

on

Alert condition detected. (Section 2.4.2 describes the 4


Alert relay configurations and explains how to configure
the relay.)

flashing*
DANGER LED

Alert condition was detected but is no longer present


INDICATION

off

The vibration level is less than the Danger setpoint

on

The vibration level is exceeding the Danger setpoint

flashing*
BYPASS LED
off

The vibration level has exceeded the Danger setpoint


and is now less than the Danger setpoint
INDICATION
Monitor is operating normally

on

Monitor is bypassed
Monitor is not OK
* Occurs only when the relay is configured as nonlatching and the
vibration was previously above the setpoint and has returned below the setpoint
for that particular relay.

27

1900/25 Vibration Monitor Operation and Maintenance Manual

3.3 Relay ModeSwitch


The Relay Mode switch lets you inhibit relays by placing the monitor in bypass.
The Relay Mode switch has two positions, Normal and Bypass. Table 3.3 describes
the behavior of the Relay Mode switch.

Table 3.3: Relay Mode Switch


SWITCH SETTING

EFFECT ON RELAYS
Relays react to an alarm
condition

Relays do not react to an alarm


condition and the Bypass LED
comes on. Alert and Danger
LEDs continue to track alarm
conditions in a nonlatching
manner. If relays are activated
before the switch is set, they will

3.4 Setpoint Adjustment


Adjust the Alert and Danger setpoints by using the adjustment screws recessed
in the front panel of the monitor. The adjustment range for the Alert and Danger
setpoints is 2.54 to 50.8 mm/s (0.1 to 1.9 in/s). Use the LCD display to view the
setpoint value while adjusting it.
Place the monitor in bypass while adjusting the setpoint so the relays will not
activate accidentally. With the monitor placed in bypass, the Alert or Danger LED
will come on when the corresponding setpoint is adjusted below the vibration
level. If the monitor is taken out of bypass with one or both of these LEDs on, the
corresponding relays will activate as soon as the monitor is taken out of bypass.

28

Section 3 - Monitor Operation


Use a small screwdriver to adjust the setpoints. Figure 3-3 shows the location of
the switches and adjustment screws used in this prodedure.
Adjust the setpoints according to the following steps:
1. Place the monitor into Bypass by sliding the Relay Mode switch to the
Bypass position with the small screwdriver. The Bypass LED will come
on.
2. Slide the Display Mode switch to either the Alert or Danger position;
depending on which setpoint you wish to adjust.

Figure 3-3: Location of setpoint adjust screws, Display Mode switch and Relay Mode
Switch.
3. Use the small screwdriver to turn the setpoint adjust screw
corresponding to the setpoint that you wish to adjust. Turning the
screwdriver clockwise increases the setpoint. The value on the LCD
changes as the screw is turned. If you adjust the setpoint below the
vibration level the LED for the setpoint will come on.
4. When the desired setpoint level is showing on the LCD, verify that the
LED for that setpoint is off. If the LED is on when the monitor is taken
out of bypass, the relay corresponding to the LED will go into its alarm
state.
5. Place the Display Mode switch into the Normal position.
6. Slide the Relay Mode switch into the Normal position by using the small
screwdriver.
29

1900/25 Vibration Monitor Operation and Maintenance Manual

3.5 Resetting the Monitor


Use reset to unlatch a latched relay or to stop a flashing LED. You can reset the
monitor by pushing the Reset switch on the front panel or by pressing a remote
reset button that is connected to the remote reset terminals.
Remote reset can be accomplished by wiring a normally opened, momentarily
closed switch or button to the remote reset terminals. The remote reset contact
can be 33 m (1000 ft) from the monitor. The remote reset feature of the 1900/25
lets you reset the monitor without opening the enclosure containing the monitor.

3.6 Buffered Transducer Output


Use the buffered transducer output to obtain the raw integrated transducer
signal. The sensitivity of the buffered transducer zero to peak output is 500
mV/in/s (19.7 mV/mm/s). The buffered transducer output coaxial connector is
located on the front panel of the monitor. Use this connector to attach diagnostic
equipment such as an oscilloscope or a recorder to the buffered velocity signal.

3.7 Initiating a Self Test


Self test is initiated by moving switch 6 of the 6-position Configuration switch to
the on position. Once the self test begins, move the switch back to the off
position. Self test lasts approximately 30 seconds.
When self test begins all the LEDs and numerical segments of the LCD turn on to
visually verify that they operate properly. During self test the relays stay in the
state they were in at the start of self test. During self test the power supplies are
checked, the signal path is verified, and the alarm detection circuitry is tested.
If any part of self test fails, an error code is displayed on the LCD. Error code El
corresponds to a power supply circuit failure. Error code E2 is a signal path or
alarm detection circuit failure. Error code E3 occurs when the monitor is NOT OK.
The monitor checks errors El and E3 continuously, not just during self test. Error
E2, a signal path failure, can only be checked during self test, and will remain on
until the monitor is reset even if the failure no longer exists.

30

Section 4 - Maintenance & Troubleshooting

4. Maintenance & Troubleshooting


This section describes how to maintain and trouble shoot your 1900/25 monitor.
Instructions on how to adjust the LCD's zero potentiometer and the Trendmaster
2000 interface's gain adjust potentiometer are included if this procedure should
ever become necessary. If you encounter a problem with the 1900/25 monitor, use
the troubleshooting table at the end of this section before you contact a Bently
nevada Product Service representative.

4.1 General Maintenance


Although the 1900/25 Vibration Monitor is a low maintenance instrument, we
recommend that you inspect the monitor every three to six months to verify that
the monitor is in good working order and that reliable machinery protection is being
provided. Inspect the following items:

The monitor is powered up, the OK LED is on, and the LCD is displaying a
valid vibration reading.

The electrical connections to the monitor are in good condition and have no
corrosion or loose wires.

The weatherproof enclosure is still properly sealed and does not contain any
moisture.

The Alert and Danger setpoints are properly set and the relay time delays
and Alert relay drive settings are correct.

During this inspection you should also exercise the self test function of the
1900/25 Vibration Monitor.
If a Trendmaster 2000 is being used, it will uncover most NOT OK conditions that
exist with the 1900/25 Vibration Monitor and the accelerometer. A periodic
inspection of the monitor and transducer may catch a potential problem before it
degrades to the point that the Trendmaster 2000 displays it as a NOT OK or NO
DATA.

31

1900/25 Vibration Monitor Operation and Maintenance Manual

4.2 Monitor Adjustments


Two circuits of the 1900/25 monitor may require adjustment. Since these
circuits are set at the factory, they should not require adjusting during installation.
However, if you suspect that the monitor is out of adjustment, use the following
two procedures to adjust these circuits in the monitor.

4.2.1 LCD Zero Adjustment


Use this procedure to adjust the LCD to read zero when no transducer is
connected. Because of the noise floor of the transducer, the monitor will display a
low value, less than 0.010 in./s (0.254 mm/s), when a transducer is connected and
no vibration is present. This adjustment does not affect the full scale range of the
monitor.
Adjust the LCD at an electronics workbench rather than at the installation site. A
qualified electronics technician or engineer should perform the calibration. If you
are not capable of performing this procedure, contact your nearest Bently Nevada
sales office and arrange either to send the monitor in for calibration or have
Product Service come to your facility and perform this procedure.
Setting the LCD zero requires the following tools and parts:

32

A small straight blade screwdriver.

A power source for the monitor being calibrated (110 Vac, 220 Vac, or +24
Vdc).

A 3-conductor cable for attaching the power source to the monitor.

Two 3 kQ resistors.

Several 50 mm (2 inch), 18 AWG wires.

Section 4 - Maintenance & Troubleshooting


The calibration procedure for the LCD is described in the following steps:

1. Remove the case cover by placing pressure with a screwdriver, or


similar object, between the case cover and base.
2. Locate the LCD zero adjust potentiometer labeled R20. It is next to the
dip switch on the top circuit board.
3. Connect the resistors and 18 AWG wires to the transducer terminal
strip according to the circuit shown in Figure 4-1.

Figure 4-1: LCD zero calibration connections.

33

1900/25 Vibration Monitor Operation and Maintenance Manual


4. Connect the 3-conductor cable to the monitor power terminal strip and
plug the other end of the cable into the proper power source. Wait 30
seconds for the monitor to complete its power up and self test
functions. After the power up cycle has finished the green OK LED will
flash indicating that the monitor is now completely powered up and OK.
To stop the flashing push the reset button.
5. Turn the zero adjust potentiometer until the LCD display reads zero.
6. Unplug the power cable from the power source.
7. Disconnect the power cable from the power supply terminal strip.
8. Disconnect the resistors and jumper wires from the transducer terminal
strip.
9. Snap the case cover back into place over the printed circuit boards.
The zero point of the LCD is now properly set. There is no span adjustment for
the LCD display. This zero adjust procedure zeros the LCD display for the monitor
only. Once a transducer is connected to the monitor, a low value LCD reading, less
than 0.250 mm/s (0.010 in/s), will be present when no vibration is present. This
reading results from the electrical noise floor of the transducer and monitor
system.

4.2.2 Adjustment of the Monitor's Trendmaster 2000 Interface


The gain of the analog signal from the monitor to Trendmaster 2000 can be
adjusted by using one of the potentiometers on the bottom circuit board. Gain
adjustment should be done by a skilled electronics technician or engineer at an
electronics workbench rather than at the installation site. The procedure to adjust
this interface requires the following tools and equipment:

A small straight blade screwdriver.

A power source for the monitor being calibrated (110 Vac, 220 Vac, or +24
Vdc).

A 3-conductor cable for attaching the power source to the monitor.

One of the following TIM testers:


(Preferred method) Snapshot TIM tester (PDC 250) or Snapshot for Win CE
(PDC550) with TIM tester update, and TIM Tester cable with ProTIM-C
connector replaced with an IDC connector. or(Optional method) TIM Tester (Bently Nevada P/N 87303-01) and a short
length of Trendmaster 2000 system cable with IDC connectors installed on
both ends of the cable. (A short piece of system cable is included with the
TIM tester).

34

Section 4 - Maintenance & Troubleshooting

A calibrated RMS voltmeter

A calibrated sinewave generator that can generate-a floating 1.0 Vms sinewave at
572 Hz. (The output must be floating. Neither one of the two terminals of the
sinewave output can be grounded.)

Four 3 kQ resistors

Several 50 mm (2 inch), 18 AWG wires

Adjust the Trendmaster 2000 interface according to the following steps:


1. Remove the case cover by applying pressure with a screwdriver, or
similar object, between the case cover and the base.
2. Locate the Trendmaster 2000 gain adjust potentiometer on the
bottom circuit board. The potentiometer is labeled R21 and is
located next to the Trendmaster 2000 connectors.
Using a Snapshot TIM tester or Snapshot
for Win CE...

Using a TIM tester (Bently part number 8730301)

3. Connect the Snapshot TIM Tester to the


Trendmaster 2000 interface connector using
the snapshop TIM tester cable with the IDC
connector.

3. Connect the TIM tester to the Trendmaster


2000 interface connector using the short
length of system cable supplied with the TIM
tester.

4. Go to Service Tools and launch the TIM


Tester application. Press the Select Address
button (F2) and enter the address of the
1900/25 monitor and press Enter.

4. Set the address switches on the TIM tester


to the address setting on the 1900/25
Vibration Monitor.

5. Attach the four 3 kQ resistors, the short lengths of wire, and the
sinewave generator as shown in Figure 4-2.
6. Power the monitor and wait for it to complete self test. After the
power up cycle has finished, the green OK LED will flash indicating that
the monitor is now completely powered up and OK. To stop the
flashing push the reset button.

35

1900/25 Vibration Monitor Operation and Maintenance Manual

Figure 4-2: Trendmaster 2000 gain adjust circuit.


Using a Snapshot TIM tester or Snapshot
for Win CE...

Using a TIM tester (Bently part number


87303-01)

7. Press Enter on the Snapshot TIM Tester


to begin Free Run.

7. Place the MODE switch on the TIM tester in


the DATA position and press the XMIT button.

8. Turn the sinewave generator on and adjust the output of the


generator for a 1.0 Vms at 572 Hz.
9. Measure the output on the Buffered Transducer output connector
using the RMS voltmeter. The meter should read 0.50 Vms. If it does
not, adjust the output of the sinewave generator either up or down
until the buffered transducer output is 0.50 V^.
10. Attach the RMS voltmeter between the SIG+ and SIG- binding post
of the Snapshot TIM Tester (or TIM tester p/n 87303-01). The
reading on the voltmeter should be 1.2 V^. If it is not, adjust the
gain adjust potentiometer up or down until the voltmeter reads 1.2
V^.

36

Section 4 - Maintenance & Troubleshooting


11. Unplug the power cable from the power source.
12. Disconnect the power cable from the power supply terminal strip.
13. Disconnect the resistors, jumper wires and sinewave generator from
the transducer terminal strip.
14. Disconnect the Snapshot TIM Tester (or TIM tester p/n 87303-01)
from the monitor.
15. Snap the case cover back into place over the printed circuit boards.

4.3 Troubleshooting
Use Table 4.3 to help solve problems encountered while using the 1900/25
Vibration Monitor. If the solutions suggested in this table do not solve your
problem, contact your nearest Bently Nevada Product Service Representative.

Table 4.2: Troubleshooting


Problem

Possible Solution

Monitor will not power up


or there is a power supply
error code, E1, on the LCD

The monitor has power,


but the OK light will not
come on.

The LCD is not reading the


proper value
or
The signal path error, E2 is
displayed on the LCD after
running a self test on the
monitor.

Verify that input power source is properly connected to


the monitor.
Verify that any circuit breakers on the power source are
not tripped and that the proper voltage exists on the
power input terminals of the monitor.
Check the transducer cable and connectors for opens
and shorts.
Replace the transducer with a known good transducer.

Verify that the Display Mode switch is in the proper


position.
Check that the LCD has its zero value properly calibrated.
(See Section 4.2.1).
Verify that the transducer is working properly by either
replacing it with a known good transducer or by testing the
existing transducer for proper operation on a shake table.
Check that the instrument you use to verify the monitor's
reading uses the same analog peak to peak divided by 2
measurment that the 1900/25 uses (see Appendix G).

37

1900/25 Vibration Monitor Operation and Maintenance Manual

Problem

Possible Solution

The LCD is blank, except for


the leftmost digit is
displaying a 1.

The input to the LCD circuit is above full scale. Check the
input vibration with a portable vibration analyzer, or the
buffered transducer output to verify that the vibration is higher
than 1.999 in/s.

The relays do not appear to


activate when the
vibration exceeds the
setpoint
or
The annunciator or
machine that the relay is
connected to is not
affected by an alarm
condition at the monitor.

Verify that the setpoints are set properly.


Make sure that the monitor is not in Bypass (BYPASS LED is
off) and that the OK LED is illuminated.
If the Alert relay is the problem, then verify that the drive
condition for the relay is properly set on the Configration
DIP switch.
Test the relay. Before testing either relay disconnect it from
any machinery that would be affected by the relay
changing state. To test the relay, lower the setpoint below
the current vibration level and verify that the relay goes
into its alarm state.
Verify that the cable between the monitor's relay terminals
and the device the relay is connected to is correct. If the
relay is being used to drive an external relay or device, such
as a motor control relay or a buzzer, then verify that the
external relay or device is working properly.

Trendmaster 2000
indicates a "NO DATA"
for a 1900/25 point.

Verify that the address on the monitor and the address


setting and SPA line number in the Trendmaster 2000
software for that particular point agree.
Check the Trendmaster 2000 system cable for opens and
shorts between 1900/25 monitor and the Trendmaster
2000 system computer.

Trendmaster 2000
indicates a "NOT OK," but
the monitor's OK LED is on.

Verify that the the bypass mode jumper (W4) is in and that
the monitor is bypassed. If these two conditions exist then
there is not problem because with the W4 jumper installed
Trendmaster 2000 will indicate a "NOT OK" when the monitor
is bypassed.

38

Section 4 - Maintenance & Troubleshooting

Problem
E3 error is displayed on
LCD (NOT OK Condition
detected).

Possible Solution
Verify that connectors are firmly seated and free of corrosion
Verify transducer is properly wired
Verify no shorts exist between wires at connector
Verify that the transducer power supply is working properly
by measuring the voltage between transducer PWR(RED) and
COM(BLK). Acceptable range is 4.9 to 5.2 Vdc
Verify that the transducer cable is working properly by
replacing it with a known good cable
Verify that the transducer is working properly by either
replacing it with a known good transducer or by testing the
existing transducer for proper operation on a shake table.

39

1900/25 Vibration Monitor Operation and Maintenance Manual

5. Appendix A - Performance
Specifications
5.1 1900/25 Monitor Specifications
Note: Operation outside the specified limits will result in false readings or loss of
machine monitoring.

5.1.1 Mechanical Specifications


Dimensions (see Figure A-l):
Length:

5.20 in

(132 mm)

Width:

5.20 in

(132 mm)

Depth:

2.80 in

(71.1mm)

Weight:

0.85 1b

(400 g)

5.1.2 Environmental Specifications Temperature Range:

40

Operating:

-20C to +70C (-4T to 176T)

Storage:

-30C to +90C (-22T to 194T)

Maximum Relative Humidity:

95% noncondensing

Section 5 - Appendix A - Performance Specifications

Figure A-1: 1900/25 Mechanical Dimensions.

41

1900/25 Vibration Monitor Operation and Maintenance Manual

5.1.3 Monitor Power Specifications


AC/HDC Version
AC Voltage:

8 5 Vacm to 264 Vacm

DC Voltage:

110 Vdcto 370 Vdc

Current:

less than 0.12 A Max

Frequency:

DC or 47 Hz to 440 Hz

Low DC Version
Voltage:

18 Vdc to 36 Vdc

Current:

less than 0.3 A Max

5.1.4 Relay Specifications


Relay Contact Ratings (noninductive load):
Maximum Switched Power:

180 W, 1800 VA

Maximum DC Voltage & Current:

28 Vdc at 6 A

Maximum AC Voltage & Current:

300 Vac at 6 A

Relay Dielectric Strength (at sea level):


Contact to Contact:

750 Vms

Contact to Coil:

1500 Vmo

Relay Life Expectancy:


Mechanical:

100,000,000 operations

Electrical:

180,000 operations at 6 A, 120 Vac

Insulation Resistance:

100,000,000 Q minimum at 20C,


500 Vdc, 50% relative humidity

5.1.5 Signal Conditioning


Fullscale Range:

2 in/spk (50.8 mm/spk)

Note: Full scale is limited by maximum input above 614 Hz. The Maximum input is
2 volts peak, or 20 g peak. 20 g peak at 614 Hz is equivilant to 2 in/second peak.
For frequencies above 614 Hz, the maximum full scale range is equal to
(1228/frequency) in/s.

42

Section 5 - Appendix A - Performance Specifications


Frequency Response:
High Pass Corner:

3 dB corner at 8 Hz. Less than 1% error due to high


pass corner for frequency above 30 Hz.

Low Pass Corner:

Greater than 4 kHz. Less than 1% error due to low


pass corner for frequency below 4 kHz.

5.1.6 Accuracy
Percent of full scale range.
Liquid Crystal Display

3% for 30 Hz to 4 kHz
-30%, +3% for 8 to 30 Hz.

Buffered output

3% for 30 Hz to 4 kHz.
-30%, +3% for 8 to 30 Hz.

Trendmaster
2000 Output

3% for 30 Hz to 1 kHz.
-30%, +3% for 8 to 30 Hz.

5.1.7 LED Indicators


OK:

One constant ON green LED indicates OK condition


of monitor, transducer, and field wiring. Constant OFF
indicates NOT OK condition. OK LED flashing at 2 Hz
indicates monitor has been NOT OK, but is now OK.

Alert:

One yellow LED indicates an Alert condition. Flashing


at 2 Hz indicates an Alert condition has occurred and
then gone away (only occurs if the Alert relay is
configured as nonlatching).

Danger:

One of the two red LEDs indicates a Danger


condition. Flashing at 2 Hz indicates a Danger
condition has occurred and then gone away (only
occurs if the Danger relay is configured as
nonlatching).

Bypass:

The other red LED indicates the monitor is in BYPASS


mode.

5.1.8 Monitor Controls


Display Mode Switch:
Relay Mode Switch:

Three positions: Normal, Alert Setpoint, and Danger


Setpoint. Controls what is shown on LCD display.
Two positions, Normal and BYPASS, control whether
the monitor is in normal or Bypass mode.
43

1900/25 Vibration Monitor Operation and Maintenance Manual


Reset Button:

Push to reset latched relays and flashing LEDs.

Configuration Switch:

Used to set Alert and Danger Relay Time Delay, Alert


relay drive conditions, English or metric display units,
and to initiate a monitor self test.

5.1.9 Trendmaster 2000 Interface Specifications

44

Fullscale Range:

2 in/spk (50.8 mm/spk)

Overrange:

2.5 in/spk (63.5 mm/spk)

Frequency Response:

10 Hz to 1 kHz

Galvanic isolation:

Optical, 1000 Vac, 707 Vdc.

Section 6 - Appendix B - Peak Detection Methods

6. Appendix B - Peak Detection Methods


Understanding the methods for peak to peak amplitude detection of a vibration
signal can help you understand why the 1900/25 Vibration Monitor is more
accurate than some other monitors and why the readings of the 1900/25 and the
Trendmaster 2000 can differ slightly under certain circumstances. This appendix
summarizes the typical methods of detecting peak to peak amplitude and then
compares the relative value of each one.

6.1 Peak Detector Theory


Three methods of peak detection are commonly used in vibration measurment
instruments - the simple peak method, the peak-to-peak divided by 2 method, and
RMS converted to peak method. The most accurate method for detecting the peakto-peak amplitude of vibration signals is the peak-to-peak divided by 2 method.
A simple peak detector circuit will find the maximum positive peak of a waveform.
Over some period of time, usually about one second, the peak value held by the
circuit decays so the circuit can obtain the next peak value. A peak detection
scheme using only a positive peak detector is less accurate because it assumes
that the vibration signal has equal positive and negative peaks. When measuring
an input vibration signal with a small positive peak and a large negative peak, for
example, this detector erroneously indicates a low vibration amplitude. Since
complex machine vibration signals are rarely symmetrical, a detector that
measures both positive and negative peaks is more accurate.
Peak-to-peak divided by 2 detection is a better method and is used by Bently
Nevada monitors for velocity or acceleration signals. This method finds both the
positive and negative peaks of the input signal and adds them together to get a
peak-to-peak value. Since peak value is the standard for vibration data displayed
in velocity units, the monitor divides the peak-to-peak value by two, resulting in
the peak value of the signal. The peak values held by this circuit also decay so the
circuit can detect future peaks. The peak-to-peak divided by two method ensures
that all the vibration signal from a machine, both positive and negative, is measured
and the result accurately reflects the overall vibration of the machine.
Another peak detection method is RMS converted to peak, which uses a true
RMS detection circuit to find the RMS value of the input signal, then applies a
conversion factor to find the peak value. Although some applications may call for
RMS measurements, this method is poor for determining true peak values because
the relation between RMS and peak values depends on the shape of the signal.
Typically, instruments convert RMS to peak by dividing by V2, which is only accurate
for a pure, symmetrical sinusoid. Since complex machine vibration signals are
rarely pure or symmetrical sine waves, the peak value obtained from this method
is usually in error.
45

1900/25 Vibration Monitor Operation and Maintenance Manual

7. Appendix C - Trendmaster 2000


Address Settings
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
46

Code
00000001
00000010
00000011
00000100
00000101
00000110
00000111
00001000
00001001
00001010
00001011
00001100
00001101
00001110
00001111
00010000
00010001
00010010
00010011
00010100
00010101
00010110
00010111
00011000
00011001
00011010
00011011
00011100
00011101
00011110
00011111
00100000

1 = Switch ON
Address
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64

Code
00100001
00100010
00100011
00100100
00100101
00100110
00100111
00101000
00101001
00101010
00101011
00101100
00101101
00101110
00101111
00110000
00110001
00110010
00110011
00110100
00110101
00110110
00110111
00111000
00111001
00111010
00111011
00111100
00111101
00111110
00111111
01000000

0 = Switch OFF
Address
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96

Code
01000001
01000010
01000011
01000100
01000101
01000110
01000111
01001000
01001001
01001010
01001011
01001100
01001101
01001110
01001111
01010000
01010001
01010010
01010011
01010100
01010101
01010110
01010111
01011000
01011001
01011010
01011011
01011100
01011101
01011110
01011111
01100000

Section 7 - Appendix C - Trendmaster 2000 Address Settings

Address
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133

Code
01100001
01100010
01100011
01100100
01100101
01100110
01100111
01101000
01101001
01101010
01101011
01101100
01101101
01101110
01101111
01110000
01110001
01110010
01110011
01110100
01110101
01110110
01110111
01111000
01111001
01111010
01111011
01111100
01111101
01111110
01111111
10000000
10000001
10000010
10000011
10000100
10000101

1 = Switch ON
Address
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172

Code
10001000
10001001
10001010
10001011
10001100
10001101
10001110
10001111
10010000
10010001
10010010
10010011
10010100
10010101
10010110
10010111
10011000
10011001
10011010
10011011
10011100
10011101
10011110
10011111
10100000
10100001
10100010
10100011
10100100
10100101
10100110
10100111
10101000
10101001
10101010
10101011
10101100

0 = Switch OFF
Address
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211

Code
10101111
10110000
10110001
10110010
10110011
10110100
10110101
10110110
10110111
10111000
10111001
10111010
10111011
10111100
10111101
10111110
10111111
11000000
11000001
11000010
11000011
11000100
11000101
11000110
11000111
11001000
11001001
11001010
11001011
11001100
11001101
11001110
11001111
11010000
11010001
11010010
11010011
47

1900/25 Vibration Monitor Operation and Maintenance Manual

Address
134
135
214
215
216
217
218
219
220
221
222
223
224
225
226
227

48

Code
10000110
10000111
11010110
11010111
11011000
11011001
11011010
11011011
11011100
11011101
11011110
11011111
11100000
11100001
11100010
11100011

1 = Switch ON
Address
173
174
228
229
230
231
232
233
234
235
236
237
238
239
240
241

Code
10101101
10101110
11100100
11100101
11100110
11100111
11101000
11101001
11101010
11101011
11101100
11101101
11101110
11101111
11110000
11110001

0 = Switch OFF
Address
212
213
242
243
244
245
246
247
248
249
250
251
252
253
254
255

Code
11010100
11010101
11110010
11110011
11110100
11110101
11110110
11110111
11111000
11111001
11111010
11111011
11111100
11111101
11111110
11111111

Section 8 - Appendix D - 1900/25 Monitor Configuration Form

8. Appendix D - 1900/25 Monitor


Configuration Form
The following page contains a form that can be used to record internal jumper
settings, configuration switch settings, and setpoints for the 1900/25 monitor.
Also the form has space to record Trendmaster 2000 software settings for the
1900/25 point.

49

1900/25 Vibration Monitor Operation and Maintenance Manual


1900/25 Vibration Monitor Configuration Form

50

Section 9 - Appendix E - Accessories and Spare Parts

9. Appendix E - Accessories and Spare


Parts
9.1 Installation Hardware
The following items listed below can be used as part of the installation of the
1900/25 Vibration Monitor.
Weatherproof Enclosure
A weatherproof enclosure protects the 1900/27 Vibration Monitor from wet and
corrosive environments. Two enclosures are listed below. When properly installed,
these weatherproof enclosures will meet Type 4X specifications.
Constructed of thermoplastic polyester resin (PBT), the 190100-01 weatherproof
enclosure has a clear polycarbonate cover to allow viewing of the LCD display
and status LEDs.
When properly installed, the 03636315 RFI Resistant Enclosure protects the
1900/25 monitor from strong radio signals generated from hand-held
transmitters. It consists of a stainless steel body and a door with a metal screened
window. Along with the 190520 Accelerometer and properly grounded conduit, this
housing can significantly reduce the possibility of nuisance alarms caused by radio induced
signals.

190100-01

Weatherproof enclosure for one 1900/27 Vibration Monitor.

03636315

Weatherproof RFI shielded enclosure for one 1900/27


Vibration Monitor.

104795-01

Back panel for 03636315 housing.

04344054

Screws for 03636315 housing back panel.

51

1900/25 Vibration Monitor Operation and Maintenance Manual


Fittings
03813103

3/4 inch NPT chrome plated zinc hub fitting.

03813106

1-1/4 inch NPT chrome plated zinc hub fitting.

26650-01

3/4 inch to 1/2 inch NPT reducer.

26650-03

1-1/4 inch to 1 inch NPT reducer.

03839240

1/4 inch NPT cable seal; 0.200 to 0.265 inch diameter (5.0 to
6.7 mm) for use in sealing transducer cable entry to
weatherproof enclosure. One required per each cable entry
to housing.

03870190

fitting for connecting 1/2 inch NPS female liquid tight


conduit to 1/2-14 NPS transducer cap option.

Cable Armor and Fittings


Cable armor can be used to make the transition from the transducer to Sealtite
flexible conduit or rigid conduit.
Armor
3/8 inch Teflon coated stainless steel armor

106924 AXX
Option Decription
A:

Armor length option in feet

Order in increments of 10 feet (3.0 metres).


Minimum length:

3.0 metres (10 feet)

Maximum length:

27 metres (90 feet)

Armor Fittings

52

03840496

Armor to 1/2 inch NPS female conduit fitting for connection


to 1/2 inch NPS transducer cap option.

03840495

Armor to 3/4 inch conduit fitting

Section 9 - Appendix E - Accessories and Spare Parts

9.2 Spare Parts


An on-site supply of spare parts allows for immediate and efficient maintenance
or expansion of your 1900/25 Vibration Monitor System. Bently Nevada
recommends that the following components be available as spare parts.
IDC cable connectors
An insulation displacement connector (IDC) is required for connecting the
Trendmaster 2000 system cable to the 1900/25 Vibration Monitor.
00523103

5 pin, 18 AWG (1.0 mm2) IDC connector

00523104

cover for the above connector

Jumpers
The internal jumpers are used to set relay options such as latching or nonlatching
relays and normally energized or de-energized relays.
00500143

single 2 pin jumper

Manual
Spare manuals may be useful to allow other engineers or technicians, involved in
the installation, operation, or maintenance of the 1900/25 Vibration Monitor, to
have their own copy.
190125-01

1900/25 Operation and Maintenance Manual

53

1900/25 Vibration Monitor Operation and Maintenance Manual

10. Appendix F - Hazardous Area


Approvals
Canadian Standards Association Approvals
The 1900/25 vibration monitor is CSA NRTL/C approved for Class 1, Division 2,
Groups A,B,C,D hazardous areas when installed per drawing 105352.

The table below lists the approval drawings in the order they appear.

APPLICATION NOTE
When the accelerometer is used with barriers
in an intrinsically safe installation, the
transducer common is connected to the
barrier's earth ground. Since the transducer
common is also connected to the power input
common inside the 1900/25, care must be
taken to avoid a ground loop which could arise
from connecting the power input common to
earth ground. Note that the approval drawings
for the 89129 and 190520 Accelerometers
require that the total earth ground loop
impedance at the barrier be less than one
ohm.

DRAWING TITLE

54

DRAWING NUMBER

NUMBER OF SHEETS

1900/25 Installation
Approval Drawing

105352

CSA Intrinsically Safe


Approval Drawing

107585

Das könnte Ihnen auch gefallen