Beruflich Dokumente
Kultur Dokumente
ii
Contact Information
The following ways of contacting Bently Nevada are provided for those times when you
cannot contact your local representative:
Mailing Address
Telephone
Fax
Internet
iii
Additional Information
Notice:
This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.
iv
Contents
1. 1900/25 Vibration Monitor Description..................................................... 1
1.1
1.2
Features................................................................................................................................................. 1
Monitor Connections, Indicators, & Controls ........................................................................ 4
2. Installation ...................................................................................................... 6
2.1
2.1 Receiving Inspection.................................................................................................................... 6
2.2
Jumper Settings................................................................................................................................... 6
2.2.1 Setting Relays for Latching or Non-Latching Behavior............................................... 6
2.2.2 Setting Relays for Normally Energized or Normally De-energized Behavior .... 7
2.2.3 Setting Trendmaster 2000 Behavior During 1900/25 Monitor Bypass ............ 8
2.2.4 Internal Jumper Location ......................................................................................................... 9
2.3
Monitor Enclosure ............................................................................................................................... 9
2.4
Configuration Switch SettingS...................................................................................................10
2.4.1 Relay Time Delay ........................................................................................................................10
2.4.2 Alert Relay Alarm Conditions.................................................................................................10
2.4.3 Configuring the Display for English or Metric Units ....................................................11
2.4.4 Initiating Self Test .......................................................................................................................11
2.5
Connecting Remote Reset...........................................................................................................12
2.6
Trendmaster2000 Connections ..................................................................................12
2.6.1 Connecting the Trendmaster 2000 System Cable to the 1900/25 Monitor.13
2.6.2 Trendmaster 2000 Address ...............................................................................................15
2.7
Relay Connections .............................................................................................................................16
2.7.1 Alert Relay Configuration........................................................................................................16
2.7.2 Relay Internal Jumper Settings............................................................................................18
2.7.3 Relay Electrical Connections .................................................................................................18
2.8
Power Connections ........................................................................................................................20
2.8.1 Types of Power Connections.................................................................................................20
2.8.2 Power Electrical Connections ...............................................................................................20
2.9
Field Wiring Diagram........................................................................................................................22
10.
vi
Installation Hardware....................................................................................................................51
Spare Parts.........................................................................................................................................53
1.1 Features
The features of the 1900/25 Vibration Monitor make the monitor more reliable
and easier to use. Many of these features have been used on previous Bently
Nevada monitors and have proven to be useful for protecting machinery. You can
program some of the features of the monitor by using jumpers or the 6-position
Configuration switch.
Some of the non-programmable features are described below.
Transducer separate from monitor - Mounting only the transducer on the machine
requires less space and makes the transducer easier to install on small
machinery. Mounting the monitor away from the machine protects the monitor
from the harsh machine enviroment that is less suitable for electronic
instrumentation. This location makes it easier and safer for plant personnel to
access the monitor.
Digital LCD display - A digital liquid crystal display on the front of the monitor
indicates overall vibration or the Alert or Danger setpoints. Because the monitor is
designed to be mounted close to the machine rather than on the machine, the
monitor can be located where service personel can read it easily.
Status LED indicators - Four LEDs on the front of the monitor indicate the status of
the monitor. These LEDs show whether the monitor is OK, in alarm, or bypassed.
Remote Reset - A front panel reset button and remote reset terminals let you reset
latched relays or flashing LEDs without turning the monitor off. The remote reset
terminals allows the monitor to be reset from a remote location without having to
open the weatherproof enclosure.
Figure 1-2: Location of status LED indicators and LCD display location.
2. Installation
This section describes how to install the 1900/25 Vibration Monitor. It includes
information on how to configure the monitor for your particular application using
the monitor's internal jumpers and the configuration switches on the front panel.
This section also describes how to connect the Accelerometer to the 1900/25
Vibration Monitor.
Section 2 - Installation
JUMPER SETTING
install
remove
W8
Alert nonlatching
W8
Danger latching*
W7
W7
Alert latching*
Danger nonlatching
* Factory default setting
JUMPER SETTING
install
remove
W6
W6
W5
W5
jumper
(W4)
installed*
removed
Yes
No
Enter NOT OK
in the Alarm
List
Yes
No
Section 2 - Installation
Switch 2
Time Delay
Off
Off
3 seconds
Off
On
5 seconds
On
Off
10 seconds
On
On
15 seconds
10
Switch 3
Switch 4
Alert Drive
Off
Off
ALERT
Off
On
ALERT OR NOT OK
On
Off
NOT OK
On
On
DANGER
Section 2 - Installation
Setting
Units
Off
English
Inches/second
On
Metric
Millimetres/second
If an error is detected during self test, an error code will remain on at the end of
the self test. Error codes El and E3 are continually tested for during normal
operation. If a power supply failure occurs, El comes on. If a NOT OK occurs, the
OK LED goes off and E3 comes on. Error code E2, a signal path error, can only be
detected using the self test function. The error codes are shown in Table 2.7.
11
Error
E1
Power
E2
Signal Path
E3
NOT OK
Explanation
The internal power supply
voltages are not within
tolerance.
12
Section 2 - Installation
13
14
Section 2 - Installation
15
WARNING
A missed trip or false trip can occur if the Alert relay
is used to signal a shutdown. Only the Danger relay,
because it is dedicated to the Danger setpoint, is
intended for machinery protection (shutdown) in the
event of high vibration. The Alert relay is intended for
non-machinery protection functions, such as
annunciating a high vibration condition or a system
fault (NOT OK), or for starting a spare machine in the
event a primary machine is shutdown by the Danger
relay as a result of high vibration in the primary
machine.
16
Section 2 - Installation
Suggested Applications
Notify that the machine is
vibrating at a level
approaching the Danger
setpoint
Notify that the vibration of
the machine is high or that
a fault exists with the
transducer, the transducer
wiring, or the transducer
power supply
Notify that a fault exists
with the transducer, the
transducer wiring, or the
transducer power supply
Start up a spare machine
when the primary machine
is shutdown by the Danger
Relay
17
Normally Energized
closed
open
ARM
ARM
open
closed
closed
open
ARM
ARM
open
closed
If the relay is configured as normally energized then the normally open (NO) and
normally closed (NC) connections are reversed from that shown on the label. Use
normally energized if you want the relay to change state if the monitor loses
power.
18
Wire stripper
Crimp tool
A phillips or straight screwdriver
Crimp type ring or spade lugs
Cable (maximum conductor size: 16 AWG)
Section 2 - Installation
To install the cable to the terminal strip follow these steps:
1.
If an outer jacket is on the relay cable then strip off about 25 mm (1 in) of outer
insulation from the cable.
2.
Strip 6 mm (0.25 in) of insulation from each of the conductors that will be
used by the relay.
3.
Crimp a ring or spade lug to each of the conductors using the crimp tool.
4.
Open the hinged protective cover over the power and relay terminal strip.
5.
Place each lug under the proper screw on the relay terminal strip (see Figure 2-12)
and use the screwdriver to tighten the screw.
6.
19
220 Vac
24 Vdc
CONNECTIONS
1
2
3
1
2
3
1
2
3
Line
Neutral
Ground
Line 1
Line 2/Neutral
Ground
+24 Vdc
Common
Ground
20
Wire stripper
Crimp tool
Section 2 - Installation
To install the cable to the terminal strip follow these steps:
1. If an outer jacket is on the power cable then strip off about 25 mm (1
in) of outer insulation from the cable.
2. Strip 6 mm (0.25 in) of insulation from each of the conductors that will
be connected to the power terminals.
3. Crimp a ring or spade lug to each of the conductors using the crimp
tool.
4. Open the hinged protective cover over the power and relay terminal
strip.
5. Place each lug under the proper screw on the power terminal strip
(see Figure 2-13) and use the screwdriver to tighten the screw.
21
22
3. Monitor Operation
This section describes how to operate the monitor. Included is information about
the displays and indicators and how to interpret the information they provide.
23
DISPLAY
DESCRIPTION
The LCD displays
overall vibration in
units of in/s.
24
E2
E3
25
26
INDICATION
on
off
Monitor is not OK
flashing
ALERT LED
off
on
flashing*
DANGER LED
off
on
flashing*
BYPASS LED
off
on
Monitor is bypassed
Monitor is not OK
* Occurs only when the relay is configured as nonlatching and the
vibration was previously above the setpoint and has returned below the setpoint
for that particular relay.
27
EFFECT ON RELAYS
Relays react to an alarm
condition
28
Figure 3-3: Location of setpoint adjust screws, Display Mode switch and Relay Mode
Switch.
3. Use the small screwdriver to turn the setpoint adjust screw
corresponding to the setpoint that you wish to adjust. Turning the
screwdriver clockwise increases the setpoint. The value on the LCD
changes as the screw is turned. If you adjust the setpoint below the
vibration level the LED for the setpoint will come on.
4. When the desired setpoint level is showing on the LCD, verify that the
LED for that setpoint is off. If the LED is on when the monitor is taken
out of bypass, the relay corresponding to the LED will go into its alarm
state.
5. Place the Display Mode switch into the Normal position.
6. Slide the Relay Mode switch into the Normal position by using the small
screwdriver.
29
30
The monitor is powered up, the OK LED is on, and the LCD is displaying a
valid vibration reading.
The electrical connections to the monitor are in good condition and have no
corrosion or loose wires.
The weatherproof enclosure is still properly sealed and does not contain any
moisture.
The Alert and Danger setpoints are properly set and the relay time delays
and Alert relay drive settings are correct.
During this inspection you should also exercise the self test function of the
1900/25 Vibration Monitor.
If a Trendmaster 2000 is being used, it will uncover most NOT OK conditions that
exist with the 1900/25 Vibration Monitor and the accelerometer. A periodic
inspection of the monitor and transducer may catch a potential problem before it
degrades to the point that the Trendmaster 2000 displays it as a NOT OK or NO
DATA.
31
32
A power source for the monitor being calibrated (110 Vac, 220 Vac, or +24
Vdc).
Two 3 kQ resistors.
33
A power source for the monitor being calibrated (110 Vac, 220 Vac, or +24
Vdc).
34
A calibrated sinewave generator that can generate-a floating 1.0 Vms sinewave at
572 Hz. (The output must be floating. Neither one of the two terminals of the
sinewave output can be grounded.)
Four 3 kQ resistors
5. Attach the four 3 kQ resistors, the short lengths of wire, and the
sinewave generator as shown in Figure 4-2.
6. Power the monitor and wait for it to complete self test. After the
power up cycle has finished, the green OK LED will flash indicating that
the monitor is now completely powered up and OK. To stop the
flashing push the reset button.
35
36
4.3 Troubleshooting
Use Table 4.3 to help solve problems encountered while using the 1900/25
Vibration Monitor. If the solutions suggested in this table do not solve your
problem, contact your nearest Bently Nevada Product Service Representative.
Possible Solution
37
Problem
Possible Solution
The input to the LCD circuit is above full scale. Check the
input vibration with a portable vibration analyzer, or the
buffered transducer output to verify that the vibration is higher
than 1.999 in/s.
Trendmaster 2000
indicates a "NO DATA"
for a 1900/25 point.
Trendmaster 2000
indicates a "NOT OK," but
the monitor's OK LED is on.
Verify that the the bypass mode jumper (W4) is in and that
the monitor is bypassed. If these two conditions exist then
there is not problem because with the W4 jumper installed
Trendmaster 2000 will indicate a "NOT OK" when the monitor
is bypassed.
38
Problem
E3 error is displayed on
LCD (NOT OK Condition
detected).
Possible Solution
Verify that connectors are firmly seated and free of corrosion
Verify transducer is properly wired
Verify no shorts exist between wires at connector
Verify that the transducer power supply is working properly
by measuring the voltage between transducer PWR(RED) and
COM(BLK). Acceptable range is 4.9 to 5.2 Vdc
Verify that the transducer cable is working properly by
replacing it with a known good cable
Verify that the transducer is working properly by either
replacing it with a known good transducer or by testing the
existing transducer for proper operation on a shake table.
39
5. Appendix A - Performance
Specifications
5.1 1900/25 Monitor Specifications
Note: Operation outside the specified limits will result in false readings or loss of
machine monitoring.
5.20 in
(132 mm)
Width:
5.20 in
(132 mm)
Depth:
2.80 in
(71.1mm)
Weight:
0.85 1b
(400 g)
40
Operating:
Storage:
95% noncondensing
41
DC Voltage:
Current:
Frequency:
DC or 47 Hz to 440 Hz
Low DC Version
Voltage:
18 Vdc to 36 Vdc
Current:
180 W, 1800 VA
28 Vdc at 6 A
300 Vac at 6 A
750 Vms
Contact to Coil:
1500 Vmo
100,000,000 operations
Electrical:
Insulation Resistance:
Note: Full scale is limited by maximum input above 614 Hz. The Maximum input is
2 volts peak, or 20 g peak. 20 g peak at 614 Hz is equivilant to 2 in/second peak.
For frequencies above 614 Hz, the maximum full scale range is equal to
(1228/frequency) in/s.
42
5.1.6 Accuracy
Percent of full scale range.
Liquid Crystal Display
3% for 30 Hz to 4 kHz
-30%, +3% for 8 to 30 Hz.
Buffered output
3% for 30 Hz to 4 kHz.
-30%, +3% for 8 to 30 Hz.
Trendmaster
2000 Output
3% for 30 Hz to 1 kHz.
-30%, +3% for 8 to 30 Hz.
Alert:
Danger:
Bypass:
Configuration Switch:
44
Fullscale Range:
Overrange:
Frequency Response:
10 Hz to 1 kHz
Galvanic isolation:
Code
00000001
00000010
00000011
00000100
00000101
00000110
00000111
00001000
00001001
00001010
00001011
00001100
00001101
00001110
00001111
00010000
00010001
00010010
00010011
00010100
00010101
00010110
00010111
00011000
00011001
00011010
00011011
00011100
00011101
00011110
00011111
00100000
1 = Switch ON
Address
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Code
00100001
00100010
00100011
00100100
00100101
00100110
00100111
00101000
00101001
00101010
00101011
00101100
00101101
00101110
00101111
00110000
00110001
00110010
00110011
00110100
00110101
00110110
00110111
00111000
00111001
00111010
00111011
00111100
00111101
00111110
00111111
01000000
0 = Switch OFF
Address
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
Code
01000001
01000010
01000011
01000100
01000101
01000110
01000111
01001000
01001001
01001010
01001011
01001100
01001101
01001110
01001111
01010000
01010001
01010010
01010011
01010100
01010101
01010110
01010111
01011000
01011001
01011010
01011011
01011100
01011101
01011110
01011111
01100000
Address
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
Code
01100001
01100010
01100011
01100100
01100101
01100110
01100111
01101000
01101001
01101010
01101011
01101100
01101101
01101110
01101111
01110000
01110001
01110010
01110011
01110100
01110101
01110110
01110111
01111000
01111001
01111010
01111011
01111100
01111101
01111110
01111111
10000000
10000001
10000010
10000011
10000100
10000101
1 = Switch ON
Address
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
Code
10001000
10001001
10001010
10001011
10001100
10001101
10001110
10001111
10010000
10010001
10010010
10010011
10010100
10010101
10010110
10010111
10011000
10011001
10011010
10011011
10011100
10011101
10011110
10011111
10100000
10100001
10100010
10100011
10100100
10100101
10100110
10100111
10101000
10101001
10101010
10101011
10101100
0 = Switch OFF
Address
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
Code
10101111
10110000
10110001
10110010
10110011
10110100
10110101
10110110
10110111
10111000
10111001
10111010
10111011
10111100
10111101
10111110
10111111
11000000
11000001
11000010
11000011
11000100
11000101
11000110
11000111
11001000
11001001
11001010
11001011
11001100
11001101
11001110
11001111
11010000
11010001
11010010
11010011
47
Address
134
135
214
215
216
217
218
219
220
221
222
223
224
225
226
227
48
Code
10000110
10000111
11010110
11010111
11011000
11011001
11011010
11011011
11011100
11011101
11011110
11011111
11100000
11100001
11100010
11100011
1 = Switch ON
Address
173
174
228
229
230
231
232
233
234
235
236
237
238
239
240
241
Code
10101101
10101110
11100100
11100101
11100110
11100111
11101000
11101001
11101010
11101011
11101100
11101101
11101110
11101111
11110000
11110001
0 = Switch OFF
Address
212
213
242
243
244
245
246
247
248
249
250
251
252
253
254
255
Code
11010100
11010101
11110010
11110011
11110100
11110101
11110110
11110111
11111000
11111001
11111010
11111011
11111100
11111101
11111110
11111111
49
50
190100-01
03636315
104795-01
04344054
51
03813106
26650-01
26650-03
03839240
1/4 inch NPT cable seal; 0.200 to 0.265 inch diameter (5.0 to
6.7 mm) for use in sealing transducer cable entry to
weatherproof enclosure. One required per each cable entry
to housing.
03870190
106924 AXX
Option Decription
A:
Maximum length:
Armor Fittings
52
03840496
03840495
00523104
Jumpers
The internal jumpers are used to set relay options such as latching or nonlatching
relays and normally energized or de-energized relays.
00500143
Manual
Spare manuals may be useful to allow other engineers or technicians, involved in
the installation, operation, or maintenance of the 1900/25 Vibration Monitor, to
have their own copy.
190125-01
53
The table below lists the approval drawings in the order they appear.
APPLICATION NOTE
When the accelerometer is used with barriers
in an intrinsically safe installation, the
transducer common is connected to the
barrier's earth ground. Since the transducer
common is also connected to the power input
common inside the 1900/25, care must be
taken to avoid a ground loop which could arise
from connecting the power input common to
earth ground. Note that the approval drawings
for the 89129 and 190520 Accelerometers
require that the total earth ground loop
impedance at the barrier be less than one
ohm.
DRAWING TITLE
54
DRAWING NUMBER
NUMBER OF SHEETS
1900/25 Installation
Approval Drawing
105352
107585