Sie sind auf Seite 1von 2

OP Overfill Protection

Tanks

HT-1009



Patented Overfill Protection with Integral Chamber Design


    

Pumpout Port
with Plug
Secondary Tank
Normal Vent

Fill with Drop


Tube Valve
Double-Wall
Monitoring
Pipe & Sensor


  

Highland Tank


OP-Chamber
Primary Tank
E-Vent

Overfill Protector

OP-Chamber Access
Stairs and Platform

Control Panel

Remote Fill Box

Support Saddles
Supply Line with
Suction Drop Tube

Product
Dispenser

Level Sensor
OP Chamber
Concrete
Support Pad
Safety Bollards
as Required

The OP Tank is equipped with a


patented overfill protection system
and integral overfill chamber designed
to capture and store overfills resulting
from mistakes or failures during filling
operations. Unlike other forms of
secondary containment, the OP keeps
the product in the storage tank where it
can be easily recovered and used.

Overfill Protection From:


Malfunctioning overfill limiter
Unattended delivery truck
Malfunctioning vents
Distracted delivery attendant
Malfunctioning gauge
Incorrect inventory record
Malfunctioning alarm

Unmatched Quality & Service

OP Tank Features
In the unlikely event of an overfill, the
Overfill Protector chute directs spills into
the containment chamber which is sized
to contain a spill equal to at least 20% of
the tanks storage volume. The collected
product can be pumped back to the
primary tank, or to another storage tank,
through the pump-out fitting in the top of
the tank. The entire OP Tank system is
UL-listed for flammable and combustible
liquid storage, and does not need to
be cleaned or freed from vapors after
pump-out.

OP Tank Sizing Guide


Spare Fitting

18" Manhole to Primary Tank


per UL-142 over 4,000 gallons

Optional Weld-on
Spill Box

Gauge

Optional Plug

Secondary Tank
Emergency Vent

Primary Tank and


OP-Chamber
Emergency Vent

OP-Chamber
Normal Vent Fitting
Probe Fitting

Supply

Spare Fitting
Normal Vent

Fill

Overflow Ports

Double-wall
Monitoring Pipe
OP-Chamber

Optional Support Saddles


Volume
Gallons

500
1,000
1,000
1,500
2,000
2,500
3,000
4,000
4,000
4,000
5,000
5,000
6,000
6,000
8,000
8,000
10,000
10,000
12,000
12,000
15,000
15,000
20,000
20,000
25,000
30,000
30,000
40,000
50,000

LA
I GH N

TANK
&

.
M F G. C O

Nominal
Inside Dimensions
Diameter
Length

4'-0"
4'-0"
5'-4"
5'-4"
5'-4"
5'-4"
5'-4"
5'-4"
6'-0"
8'-0"
6'-0"
8'-0"
6'-0"
8'-0"
8'-0"
10'-0"
8'-0"
10'-0"
8'-0"
10'-0"
8'-0"
10'-0"
10'-0"
10'-6"
10'-6"
10'-6"
12'-0"
12'-0"
12'-0"

5'-5"
10'-9"
6'-0"
9'-0"
12'-0"
15'-0"
18'-0"
24'-0"
19'-0"
10'-8"
23'-10"
13'-4"
28'-8"
16'-0"
21'-4"
14'-0"
26'-8"
17'-0"
32'-0"
20'-6"
40'-0"
25'-6"
34'-0"
31'-0"
42'-7"
46'-6"
35'-6"
47'-6"
59'-6"

Please visit us at www.highlandtank.com


One Highland Road
4535 Elizabethtown Road
Stoystown, PA 15563 Manheim, PA 17545
P: 814-893-5701
P: 717-664-0600
F: 814-893-6126
F: 717-664-0617

Chamber
Volume
Gallons

*Overall
Tank
Length

156
203
306
306
403
501
612
807
810
814
1,022
1,002
1,216
1,222
1,629
1,664
2,005
2,007
2,412
2,447
3,008
3,035
4,014
4,048
5,019
6,045
6,063
8,037
10,081

7'-1"
12'-11"
7'-10"
10'-10"
14'-5"
18'-0"
21'-8"
28'-10"
22'-10"
12'-10"
28'-8"
16'-0"
34'-5"
19'-3"
25'-8"
16'-10"
32'-0"
20'-5"
38'-5"
24'-8"
48'-0"
30'-8"
40'-10"
37'-3"
46'-6"
55'-10"
42'-8"
57'-0"
71'-5"

958 19th Street


Watervliet, NY 12189
P: 518-273-0801
F: 518-273-1365

OP Tank Options
The OP Tank is available as a UL-2085
Fireguard tank or as a standard single
or double-wall UL-142 horizontal tank.
In addition to our standard features and
options, we can also supply a larger
(above 20%) containment chamber
if greater spill containment is required.
Consult Highland Tank if a larger
(above 20%) spill containment
capability is required.
U.S. Patent No. 5,381,923

2700 Patterson Street


Greensboro, NC 27407
P: 336-218-0801
F: 336-218-1292

2225 Chestnut Street 1510 Stoystown Road


Lebanon, PA 17042 Friedens, PA 15541
P: 717-664-0602
P: 814-443-6800
F: 717-664-0631
F: 814-444-8662
Highland Tank HT1009 07/2014