A.1.1 The Generator shall provide the Grid Owner following general information about
the power station:
(a) Location map/site map showing major components of the power station: YES
(b) Approximate construction period: 4 Years
(c) Total installed capacity in MW: 24.15 MW
(d) Number and size of generating units: 2 Numbers; 14.18 MVA each
(e) Transmission voltage and point of connection with Grid: 132 kV, Singati,
Dolakha
A.1.2 The following data on each generating unit shall be provided by the Generator
(a)
(b)
(c)
(d)
Generator Transformer
(i)
(ii)
(iii)
(iv)
(v)
7%
A.1.3 If the Distribution has any Embedded Generating Plant, the Generator through the
Distributor shall provided the Grid Owner all information mentioned in Articles
A.1.1 and A.1.2 above
A.2
GRID DATA
(This data is consolidated by the Grid Owner)
A.2.1 The Grid Owner shall be responsible for collecting following general data from its
various offices:
(a)
(b)
(c)
(d)
(e)
(f)
A.3
A.3.1 The User shall furnish following details of the User System at the Connection
Point to the Grid Owner:
(a)
(b)
(c)
(d)
(e)
A.3.2 If the substation in the User System is connected to the Grid through overhead
lines and/or underground cables, the User shall submit to the Grid Owner
following details on these lines:
(a)
Bear Conductor:i)
Aluminum Strands: 30
ii)
Aluminum Strand Diameter (mm): 3.35
iii)
Steel Strand: 7
iv)
Steel Strand Diameter (mm): 3.35
v)
Overall Conductor Diameter (mm): 23.45
vi)
Resistance at 20 C (/km): 0.11
vii)
Weight of Conductor (kg/km): 1219
viii) Current Carrying Capacity (A) for temperature rise of 30 C: 570
ix)
Current Carrying Capacity (A) for temperature rise of 40 C: 640
(f)
A.3.3 If the User System is connected through a transformer, following details of the
transformer shall be provided to the Grid Owner:
Not applicable
(a)
Rated MVA:
(b)
Rated primary and secondary voltage (kV):
(c)
Winding arrangement:
(d)
Tap changer type, number of steps, and size:
(e)
Positive sequence resistance and reactance at max., min. and nominal tap
position:
(f)
Zero sequence reactance for three-legged core-type transformer:
(g)
BIL value (kv):
A.3.4 The User shall provide the Grid Owner with following details on switchgear,
circuit breakers and disconnect switches installed at the Connection Point or the
substation at the User System:
Not applicable
(a)
Rated voltage (kV):
(b)
Rated continuous maximum current:
(c)
Rated symmetrical RMS short circuited current (kV):
(d)
BIL value (kV):
A.3.5 If the User System is equipped with capacitors, reactors, static var compensators),
following details of these equipment shall be supplied to the Grid Owner:
(a)
(b)
(c)
(d)
A.3.6 For User System with loads above one MW, the following information shall be
proved by the User to the Grid Owner:
(a) Type of load (furnace load, rolling mills, traction loads, pumping loads or
other industrial loads):
(b) Rated voltage and phase:
(c) Number and size of large motors and type of drives and control arrangements:
(d) Sensitivity of load to voltage and frequency:
(e) Maximum harmonic content of load:
(f) Average and maximum phase unbalance of load:
(g) Short circuit level at Connection Point due to load and also Embedded
Generators, if any:
APPENDIX B
DETAILED PLANNING DATA
for
KHAREKHOLA HYDROELECTRIC PROJECT
DOLAKHA
B.1
B.1.3
Description:
Self-excited, self-regulated, water-cooled, three phase, salient poles rotor, brushless,
synchronous, built in accordance with IEC standard generators will be used. A lube oil
module for the generator bearings is used. A shaft driven oil pump on the generators to
reduce the dependence on DC batteries for safe shutdown during trip events will be tried
in detail design stage (Table below).The generators will have capacity to incorporate
sufficient flywheel inertia to achieve stable frequency control when running in isolated
mode.
Table
Parameters
Number of units
Rating
Power Factor
Cooling
Synchronous Speed
Frequency
Rated Voltage
Neutral Grounding
Rotor and stator insulation
Efficiency
B.1.3.1
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
(k)
(l)
(m)
Value
2
14.17 MVA
0.85
TEWAC (Totally Enclosed Water Air Cooling)
600 r/min
50 Hz
11 kV
resistive grounding via grounding transformer
Class F
98%
(n)
(o)
(p)
(q)
(r)
(s)
(t)
(u)
(v)
(w)
(x)
(y)
B.1.3.2
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
Description:
The automatic voltage regulator (AVR) shall have the following features:
a. Two auto channel with one manual mode for voltage control
b. Voltage / frequency during accelerating and decelerating of machine
c. Power factor / KVAR control mode
d. Reactive power shedding
e. KVAR limit
f. Quadrative drop characteristic for parallel operation with other machines of Nepal
g. Integrated Power System grid.
h. Short circuit maintenance
i. Diode failure indication
Besides these, equipment for limiting and regulating (both automatic / manual mode) on
generator rotor current shall be included. Voltage setting devices and necessary control
switches shall be included. This equipment shall be of a tropical design and shall work
satisfactorily at a temperature of maximum 40C.
B.1.3.3
Description:
This shall be a single cubicle for each turbine, consisting of a Digital Electronic Governor
with PID action while running on isolated as well as on Load Sharing Module, driver
cards for the hydraulic proportional valves, some basic control and display functions, and
starters for both the Lube oil motor and the HCM motor. The governor will control the
speed of the turbine via modulation of the deflector. The governing system should be
highly accurate and rugged. The turbine could be started locally from this panel, but will
normally receive control signals from the control panel located in the control room. The
turbine governor system will include the following control functions:
Frequency control
Load control
Main inlet valve control
Spear (needle) control
Jet deflector control
Manual mode operation
Local and remote operation
The governor system will consist of the following main units:
Digital turbine governor
Hydraulic control unit
Oil pressure system
Accumulator system
Mechanical/hydraulic over-speed trip device
(a)
(b)
(c)
(d)
(e)
(f)
(g)
B.1.3.4
(a)
(b)
(c)
B.1.4
Description:
GENERATION LEVEL
6.6 kV switchgears shall be located at the first floor near the control room. Together with
switchgear components (like CBs, CTs, PTs etc.), these switchgear panels will have inbuilt bus
bar cabinets housed in its back. Each generators output terminals shall be connected to this
3.3 kV bus bar system with XLPE cable of adequate size. The switchgear and other protection
and control components will accompany them in the switchgear panel to complete the
incoming generation power circuit. Individual Switchgear panels for each generator incomer,
outgoing feeder and bus coupler will be provided to complete the generation level switchgear
system. This switchgear system will work in co-ordination with the control panels
accommodated in the control room.
STATION SUPPLY
An indoor type, 150 kVA, 3.3/0.4/0.23 kV, 50 Hz, ONAN, DYn11 distribution transformer
shall be used for feeding power to power house lighting, battery charging, governor oil pumps,
air conditioning, power house crane, supply for housing etc. The station supply transformer
will be connected to 3.3 kV bus bar system through HT DO or ACB fuse and this fuse is the
only major protection to this station transformer (especially in the primary side).
HIGH VOLTAGE SWITCHYARD
A 33 MVA (at 10% additional load case and 30 MVA at normal case), 3.3/132 kV outdoor
type switchyard shall be constructed near the powerhouse to evacuate the generated power.
The switchyard components shall be suitable for hot, humid and moderately polluted
environment. The switchgear system for this switchyard shall be equipped with proper ratings
of Circuit breakers, Current transformers, potential transformers, disconnecting switches with /
without earthing and Lightening Arrestors and synchronous check relay etc. for both 3.3 kV
and 132 kV incoming and outgoing circuits. The switchgear system here will work in
coordination with the associated control panels accommodated in the control room and shall
ensure the overall protection of the switchyard.
B.1.4.1
a)
b)
c)
d)
e)
f)
g)
h)
i)
Description:
The main transformer will be of single phase, 50 Hz, 33MVA, 3.3 kV / 132 kV oil immersed,
naturally self-cooled core type, double wound with copper winding continuously rated and
arranged with vector group of Ynd11 with the neutral brought out on the star side.
Transformer shall be contained in a mild steel plate of radiator-cooled tank and shall in general
conform to IEC or equivalent International Standard. The temperature rise as measured in oil
and the winding by resistance measurement shall not exceed 50 degrees Cover an ambient
temperature of 40 degrees C. The flux density at rated conditions shall be 1.60 Tesla. The
coolers / radiators shall be designed for continuous overload capacity of 20percentile. The
transformer bushings shall be suitable for high pollution type.
Tapings shall be provided on HV winding side to obtain a variation of + 10% to - 10% in steps
of 1.875% each. These tapping shall be controlled by an externally operated OFFLOAD TAP
CHANGER. The transformer shall be finished with standard enamel / epoxy paintof a shade
corresponding to IEC or equivalent international Standard. 132 kV power transformers shall
be provided with following protections.
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
xi.
B.1.4.2
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(a)
B.1.4.3
Description:
The communication system should meet the demands of the power system for its safe and
economical operation. Because of very small size of the plant and very high cost of PLCC as
B.2.1 General
B2.1.1 Single line diagram of Distribution System (Showing distribution lines
from points of Connection with the Transmission System, 132/33/11 kV substations, 11/0.4 kV sub-stations, consumer bus if fed directly from the
Transmission System.)
B.2.2 Loads
Connected load with details on numbers of consumers category wise, details of
loads of one (1) 1 MW and above;
Information on diversity of load and coincidence factor;
Daily demand profile; and
Cumulative demand profile of Distribution System.
Estimated length of Transmission Line from the Generation Plant/Switchyard at Chamar
at Chankhu VDC in Dolakha to Sub-Station at Singhati, the proposed site for connection
point and transmission line for power evacuation for KHEP is around 9.8 km based on
the information from upgraded feasibility study.
Nepal Electricity Authority
Transmission Line Substation Construction Department
Connection Points and related Transmission Line for power evacuation
Sn
1.
Name of HEP
Projects
Khare
Plant Size
(MW)
6.4
Connection
Substation
Singati
A.2
GRID DATA
(a)
(b)
(c)
(d)
(e)