Beruflich Dokumente
Kultur Dokumente
TABLE OF CONTENTS
Exercise 18.1 Functional Designer ........................................................................................................................................... 18.1-1
18.1.1 General Information............................................................................................................................................... 18.1-3
18.1.1.1 Objectives........................................................................................................................................................ 18.1-3
18.1.2 Exercise Steps ........................................................................................................................................................ 18.1-4
18.1.2.1 Create a Function Diagram for the Tank1 area .............................................................................................. 18.1-4
18.1.2.2 Create a Document aspect for the description................................................................................................ 18.1-4
18.1.2.3 Create control functionality ............................................................................................................................ 18.1-4
18.1.2.4 Allocate diagram to the application................................................................................................................ 18.1-5
18.1.2.5 Download ........................................................................................................................................................ 18.1-5
18.1.2.6 Test the loop.................................................................................................................................................... 18.1-5
18.1.2.7 Advanced Exercise ......................................................................................................................................... 18.1-5
18.1-1
18.1-2
FIC1
Exercise 18.1
FT1
FCV1
V1
TT1
M1
LH
TIC1
TCV1
LL
LT1
V2
18.1.1.1 Objectives
You will:
Configure the filling Flow Control Loop FIC1 using the Functional Designer
Download and test the loop in On-line mode and from the Functional Diagram
18.1-3
Description
Flow transmitter
Flow controller
Flow control valve
Type
AnalogInCC
PidCC
AnalogOutCC
4. For each module please assign the name and description to the parameter of
the control. Use the Connection Bar for this (you have to enable the bar first).
5. The PID FC1_FIC1 should start in auto mode. Please setup this.
6. Connect the modules:
From
To
FC1_FT1.Out
FC1_FIC1.Pv
FC1_FIC1.Out
FC1_FCV1.In
7. Browse for the CBM signal object in the Structure Browser (Object Types
Control System AC800M/C Connect CBM_Signals).
8. Create a analog input signal (CBM_AIS) and connect it to
FC1_FT1.AnalogInput. Name the signal FC1_FT1_In (context menu
Name).
9. Create a analog output signal (CBM_AOS) and connect it to
FC1_FCV1.AnalogOutput. Name the signal FC1_FCV1_Out.
10. Create the Interaction Parameter variables for the modules. Please do this with
Variable objects.
Variable name
Datatype
Control Module
FC1_FIC1_IPar
PidCCPar
FC1_FIC1
FC1_FT1_IPar
AnalogInCCPar
FC1_FT1
FC1_FCV1_IPar AnalogOutCCPar
FC1_FCV1
18.1-4
18.1.2.5 Download
Download the application Tank1 into the controller
18.1-5