For a winding fault point at 5% from the neutral: I fault = 0.05 xI gf (max) = 50 A
The phase currents I ph increases due to the fault are negligible, and therefore
3I 0 = 0 .
Therefore:
Pickup setting = I gd = 3I 0 I g = (0 I fault ) / CTratio = 0.08 xCT
NOTE: The RGF protection may pickup during external faults with saturation on either
phase CTs or the ground CT. It is recommended to add appropriate time delay to cope
with CT saturation on external faults.