FEATURES
PT1000 or NTC20k
temperature sensing element
High accuracy
SPECIFICATION
Nominal value
PT1000
NTC20k
Accuracy
PT1000
GENERAL
These Immersion temperature sensors are used in the
following hot or cold water control systems
Excel 5000
MicroniK 200
MicroniK 100
Excel Classic
Excel Plus
High Performance Excel Plus
Excel EMC
NTC20k
Sensitivity
PT1000
NTC20k
Response time
with brass well
1000 at 0 C
20 k at 25 C
IEC751 Class B
0.3 K +0.5% |t| (t in C)
0.3 K +1% |t - 25 C| (t in C)
3.85 / K
-934.5 / K at 25 C (non-linear)
0.5
0.5
EN0B-0363GE51 R0206
Models
OS-no.
VF20T
VF20L
VF20NT
VF20LN
Sensing
range
Sensor type
-25...+130 C
NTC 20 k
-25...+150 C
T7413A1009
-25...+130 C
PT1000
T7413A1041
T7413A1058
WPF20T
NTC 20 k (two sensors)
WPF20L
*When a stainless steel immersion well is used.
-25...+150 C*
-25...+130 C
Length in mm (inches)
L1
T1
185 (7.28)
152 (5.98)
338 (13.30) 305 (12.00)
185 (7.28)
152 (5.98)
338 (13.30) 305 (12.00)
VFHT
VFL
VFNT
VFLN
193 (7.59)
160 (6.29)
VFHT
185 (7.28)
338 (13.30)
185 (7.28)
338 (13.30)
152 (5.98)
305 (12.00)
152 (5.98)
305 (12.00)
Immersion
well
not included
VFHT
VFL
Immersion Well
Order-no.
Length mm (inch) T2
VFHT
135 (5.31)
VFL
300 (11.81)
VFNT
VFLN
135 (5.31)
300 (11.81)
Immersion well
Pmax
15 bar
8 m/s
3 m/s
25 bar
DIMENSIONS
50 (1.97)
L1
6 (0.23)
33 (1.3)
65
(2.55)
T1
7 (0.28)
SW 22
12
(0.47)
25 (0.98)
T2
EN0B-0363GE51 R0206
15 m/s
6 m/s
INSTALLATION
Wiring run
Sensor to controller
Maximum length
200 m (660 ft)
Type of wire
2
0.5 mm (AWG20)
2
1.0 mm (AWG17)
2
1.5 mm (AWG15)
ELECTRICAL CONNECTION
The wiring of the temperature sensor must be in accordance
with the overall wiring circuit diagram.
The terminals are not polarized. Thus, connecting the wires
in reverse will not result in any malfunction.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: