2x150MWCOALBASEDTHERMALPOWERPROJECT
M/SSHREECEMENTLTD.,
BEAWAR,RAJASTHAN(INDIA)
SHORTCIRCUITFORCEFOREQUIPMENT
INTERCONNECTION
DocNo.
3VYN291401A.R0
Sheet1of17
SHORTCIRCUITFORCEFOR
EQUIPMENTINTERCONNECTION
OWNER
M/SSHREECEMENTLTD.
OWNERSENGINEER
EvonikEnergyServices(I)Pvt.Ltd.,
Noida
EPCCONTRACTOR
CetharVesselsLimited,
Tiruchirapalli
eBOPCONTRACTOR
ABBLimited,Faridabad
R0
21.04.2010
RK/RM
Rev
No.
Date
Prepared
by
Reviewed
by
Approved
by
Remarks
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP.
ABBLIMITED
2x150MWCOALBASEDTHERMALPOWERPROJECT
M/SSHREECEMENTLTD.,
BEAWAR,RAJASTHAN(INDIA)
SHORTCIRCUITFORCEFOREQUIPMENT
INTERCONNECTION
DocNo.
3VYN291401A.R0
Sheet2of17
REVISIONSTATUSSHEET
REV.NO.
DATE
DESCRIPTION
R0
21.04.2010
FORAPPROVAL
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP.
I System Data:
1.1 Nominal System voltage in kV
1.2 System short circuit current in A
1.3 Factor for peak short circuit current
1.4 Phase spacing in m
=
(I"k3) =
()
(a m) =
(f)
400
40000
1.81
7
50
YES
II Conductor data:
2 1 Busbar selected
2.1
(Do)
114.3
mm
(Di)
97.18
mm
(A)
2844
sq.mm
(J)
4.00E-06
m^4
2.6 Weight
(m')
7.678
kg/m
(E)
6.57E+10 N/ sq.m
III Reference
3.1 IEC 865 -1(1993): short circuit current calculation effects
Page 3 of 17
3VYN291401A-R0
IV Legend:
Symbol
Unit
I"k3
Amps
Ip3
Amps
am
Do
VF
4.8 Ratio of stress for a main conductor with or with out three
phase auto reclosing (As per equation in page no. 109 of
IEC 865 -1(1993))
Vr
fc
Hz
Fm
kg
kg
Fd
kg
N/m
m^4
Page 4 of 17
3VYN291401A-R0
Formulae Used
5.2
= I"k3 x k
x Sqr(2)
Amps
(Fm)
= x Sqr(3) x ( Ip3) x l
2x 2 p
x 9.81 x am
kg
(Fd)
= Vf x Vr x a x Fm
kg
(fc)
5.5 Calculation of VF
As per IEC 865-I (Page-107)
fc/f
<0.04
0.04......0.8
0.8.......1.2
1.2.........1.6
1.6.......2.4
2.4......2.74
2.74......3.0
3.0........6.0
>6
x
l
Sqr ( E J /m') Hz
VF
0.232+3.52*EXP(-1.45*k)+0.166*LOG10(fc/f)
MAX(0.839+3.52*EXP(-1.45*k)+0.6*LOG10(fc/f),2.38+6*LOG10(fc/f))
1.8
1.23+7.2*LOG10(fc/f)
2.7
8.59-15.5*LOG10(fc/f)
8.59-15.5*LOG10(fc/f)
1.5-0.646*LOG(fc/f)
1
5.6 Calculation of Vr
fc/f
<=0.05
>0.05 and <1
>=1
Vr
1.8
1-0.615Log(fc/f)
1
Page 5 of 17
3VYN291401A-R0
VI Support Arrangement
Refer Figure 1
6.1 Equipment Dimension (Terminal to Terminal) in m
4.8 m
Left
9
Right
10.5
4.821
FIXED
SIMPLE
SIMPLE
FIXED
(L)
VII Calculation
7.1 Peak short circuit current
Ip3
102389
Left
0.625
Right
0.375
0.375
0.625
7.4 Factor b
0.73
0.73
7.5 Factor
2.45
2.45
4.19
8.1
Fm
110.79
214.18
fc
25.824
6.9099
fc / f
0.5165
0.1382
VF =
1.0128
0.6692
VR =
1.1765
1.5286
0.625
0.375
82.505
82.164
7.12 Factor a
7.13 Dynamic force (Bending Force) (kg)
7.14 Total Dynamic force due to Left & Right spans
Page 6 of 17
Fd =
=
164.67 kg
3VYN291401A-R0
Page 7 of 17
3VYN291401A-R0
VI Support Arrangement
Refer Figure 2
6.1 Equipment Dimension (Terminal to Terminal) in m
4.821 m
(L)
Left
12
Right
9
0.55
4.8
SIMPLE
SIMPLE
FIXED
FIXED
102389
VII Calculation
7.1 Peak short circuit current
Ip3
Left
0.375
Right
0.375
0.625
0.625
7.4 Factor b
0.73
0.73
7.5 Factor
2.45
2.45
9.315
4.189
Fm
246.31
110.77
fc
5.2249
25.836
fc / f
0.1045
0.5167
VF =
0.5964
1.0129
VR =
1.6032
1.1763
0.375
0.375
88.317
49.492
7.12 Factor a
7.13 Dynamic force (Bending Force)
Fd =
Page 8 of 17
137.81 kg
3VYN291401A-R0
Page 9 of 17
3VYN291401A-R0
VI Support Arrangement
Refer Figure 3
6.1 Equipment Dimension (Terminal to Terminal) in m
0.55 m
(L)
Left
12
Right
5.5
4.82
4.8
FIXED
SIMPLE
SIMPLE
FIXED
VII Calculation
7.1 Peak short circuit current
Ip3
102389
Left
0.625
Right
0.375
0.375
0.625
7.4 Factor b
0.73
0.73
7.5 Factor
2.45
2.45
9.318
2.827
Fm
246.39
74.7526
fc
5.2215
56.7273
fc / f
0.1044
1.13455
VF =
0.5962
1.8
VR =
1.6034
7.12 Factor a
7.13 Dynamic force (Bending Force)
7.14 Total Dynamic force due to Left & Right spans
Page 10 of 17
Fd =
=
0.625
0.375
147.22
50.458
197.67 kg
3VYN291401A-R0
Page 11 of 17
3VYN291401A-R0
VI Support Arrangement
Refer Figure 4
6.1 Equipment Dimension (Terminal to Terminal) in m
0m
(L)
Left
10.5
Right
0
4.8
FIXED
SIMPLE
VII Calculation
7.1 Peak short circuit current
Ip3
102389
Left
0.625
Right
0
0.375
7.4 Factor b
0.73
7.5 Factor
2.45
8.1
Fm
214.18
fc
6.9099
fc / f
0.1382
VF =
0.6692
VR =
1.529
7.12 Factor a
7.13 Dynamic force (Bending Force)
7.14 Total Dynamic force due to Left span
Page 12 of 17
Fd =
=
0.625
136.94
136.94 kg
3VYN291401A-R0
Page 13 of 17
3VYN291401A-R0
Page 14 of 17
Sl.No.
FIXED
0 SIMPLE
FIXED
FIXED
10.5
12
12
Left
5.5
10.5
Right
Eqpts(m)
Right
Support
Left
SIMPLE FIXED
SIMPLE
Right
Distance between
Other Equipment
FIXED
400kV Isolator
Left
Equipment Support
8.1
9.318
9.315
4.19
Left
2.827
4.189
8.1
Right
Length(m)
Effective
Right
214.2
246.4 74.753
246.3 110.77
110.8 214.18
Left
Fm (Kg)
Left
Right
Right
VF
6.91
0 0.6692
1.8
25.8
Left
fc (Hz)
Right
Left
Right
Fd (Kg)
(Kg)
Total Fd
1.529
1.603
0 136.94
1 147.22
137.809
0 136.9396
50.458 197.6749
Left
Vr
3VYN291401A-R0
40000
(i.e. 40 kA)
4. CALCULATION
Refer Figure No.5
Electromagnetic force on conductor (TWIN Moose ACSR)
(Short circuit force)
(F')
=
34.29 N/m
=
3.5 Kg/m
Force on CVT (15.13m span)
Force on LA (14.75m span)
Page 15 of 17
=
=
52.96 Kg
51.63 Kg
3VYN291401A-R0
Page 16 of 17
3VYN291401A-R0
PART A
1.
Calculation of Short Circuit force on Equipments with 4'' IPS Al. Tube
Isolator
Force for 400kV
2.
PART B
197.67 kg
136.94 kg
CVT
Force for 400kV
1.
137.81 kg
1.
Current Transformer
Force for 400kV
4.
164.67 kg
Circuit Breaker
Force for 400kV
3.
52.96 kg
51.63 kg
LA
Force for 400kV
Page 17 of 17
3VYN291401A-R0