Beruflich Dokumente
Kultur Dokumente
Pages
HUGHES KFDS ............................................................................................................. 12
HYDRIL DIVERTER FS 21-500 ..................................................................................... 13
MARINE RISER SYSTEM ............................................................................................. 13
TELESCOPIC JOINTS .................................................................................................. 14
MARINE RISER HANDLING EQUIPMENT ................................................................... 15
MARINE RISER SYSTEM FAILURE ............................................................................. 15
BALL JOINTS, FLEX JOINTS, RISER ADAPTERS ...................................................... 16
FIGURES 1 THRU 22 .................................................................................... 17 thru 129
DIVERTER SYSTEM
CHAPTER 1
1-1
Chapter 1
CHAPTER ONE
Diverter System
he diverter system is designed to divert shallow gas kicks away from the rig and personnel.
The system provides some protection prior to setting the casing string which the wellhead
and B.O.P. stack are installed on.
Any wellbore kick would be diverted through vent lines to the opposite extremities of the vessel,
either port and starboard or fore and aft. The valves in the vent lines must be fully opening and be
selectively sequenced in operation, thereby preventing total shut in of the wellbore, which could
breakdown the weak shallow formations.
The flowline carries the return wellbore fluid flow to either the trip tank, the shale shakers, the
degasser or overboard depending on the drilling operation. Trip tank, shale shaker and degasser
isolation valves are provided to direct the flow as required.
The vent lines tee off the flowline, and vent line isolation valves are provided to direct the flow to
the desired vent line. Vent line selection is dependant upon the prevailing wind direction.
The ideal diverter vent line would be designed without bends, would be as large as practically
possible and be internally flush, thereby keeping back pressure on the wellbore to a minimum.
Since the ideal is not always practical the, API RP64 1991 edition, recommends a minimum vent
line I.D. of 10 inches, with a preferred minimum I.D. of 12 inches or larger for floating vessels.
Figure 1 shows example vent/flowline installations.
HUGHES KFDS
Figures 2 and 2A show the Hughes KFDS diverter system which is the most commonly used.
This system consists of a fixed housing located below the rotary table, with the return mud
flowline permanently attached. A diverter assembly, which contains a hydraulic outer packer, a
removable packer insert which closes and seals around the drill pipe, radial flowline seals and a
mechanism for locking the removable packer insert in place.
All the valves in the system are selectively sequenced in operation. Selective sequencing ensures that when the diverter close function is selected firstly, both vent line isolation valves open
and secondly, the shale shaker and trip tank valves close. This valve sequence is completed prior
to the hydraulic closing pressure being applied to the outer packer and is designed to prevent
total shut in of wellbore pressure, which could result in formation breakdown.
Figure 3 shows a closing pressure graph. It can be seen that the minimum closing pressure
required to effect a seal on 5 inch drill pipe is relative to wellbore fluid pressure.
Minimum closing time is approximately 5 seconds when maximum closing pressure of 1000 p.s.i.
is used. Figure 4 shows how closing time increases as closing pressure is decreased.
CHAPTER 1
1-2
Closing pressure should never be applied to the outer packer unless the packer insert is installed, as
this could rupture the outer packer and cause injury to personnel. As a safety precaution, a pilot
operated check valve should be installed in the packer insert closing circuit. The pilot signal required
to open the check valve and allow hydraulic fluid flow to the outer packer would be provided from the
lock side of the packer insert lockdown dogs. This ensures that the outer packer can only receive fluid
pressure while the packer insert lockdown dogs are in the locked position.
A diverter ball joint or flex joint is required to provide a flexible link between the marine riser
telescopic joint and the fixed diverter housing. The ball/flex joint prevents bending loads being
exerted on the diverter housing and telescopic joint inner barrel, while permitting lateral movement of the vessel from directly over the well. The ball/flex joint has to have the same internal
wellbore pressure rating as the diverter system and must be capable of retaining this pressure at
its maximum design angle. Figure 5 shows the Hughes D R I ball joint.
DIVERTER SYSTEM
CHAPTER 1
1-3
The internal pressure rating of the marine riser system should be at least equal to the working pressure of the diverter system, plus the maximum difference in hydrostatic pressure of the drilling fluid
and sea water at the ocean floor. In deep water drilling, riser collapse resistance has to be considered in the event of lost circulation or disconnection of the riser while full of drilling fluid.
Riser pipe connections must have the same strength and pressure integrity as the riser pipe
section and provide a means of quick reliable make up and break out.
Figures 11, 12, 13, and 14 show the Vetco and Cameron riser connectors which use the same
principles in make up. The actuator bolts force locking rings or dogs radially inwards, which engage
mating grooves in the pin end of the connector. By applying the appropriate torque to the actuator bolt,
the pin and box assembly are pre- loaded to the design load rating. By pre- loading the assembly
in this manner the risk of joint separation is minimised, even when the maximum design load is
reached.
A mechanical lock is provided for the actuator bolts to prevent loss of torque due to vibration etc.
The integral high pressure choke and kill lines which provide the high pressure communication
between the B.O.P. stack and the choke and kill manifold on board the vessel, are permanently
installed on the riser joints so that they are simultaneously made up when the riser connector is
made up. Provision is made through the use of test caps, to allow testing of the choke and kill
lines as the riser and B.O.P. are being run to the wellhead.
Lip type seals or chevron type packings are used in the box ends to seal the choke and kill line
connections. The pins of the choke and kill lines have a colmonoy or other hard wearing overlay
which provides high abrasion and corrosion resistance. Colmonoy is a nickel/chrome mixture
applied to the parent metal at approximately 1150 C.
Prior to running the marine riser, the riser pipe connections must be cleaned and inspected for
damage to the sealing surfaces and locking rings etc. The choke and kill line box and pins must
also be inspected for damage.
Periodic N.D.T. inspection should be carried out and results documented under the planned
maintenance program.
TELESCOPIC JOINTS
The telescopic joint is used at the top of the marine riser and has the following functions:
a)
b)
c)
d)
CHAPTER 1
1-4
The telescopic joint is comprised of an outer barrel which is attached to the top joint of marine
riser and an inner barrel which is attached to the diverter ball joint.
The outer barrel includes the support ring or fixed pad eyes for attaching the riser tensioner lines.
The effective stroke length of telescopic joints varies from 45 feet to 55 feet depending on manufacturer. Telescopic joints normally have the same load capabilities as the riser system in the
closed or fully extended position. Handling of the B.O.P. system, i.e. landing the B.O.P. and riser
string on the wellhead with the inner barrel fully extended, is not a recommended practise, as the
condition of the inner barrel load shoulder or shoe, is not always known.
The inner barrel can be mechanically locked in the closed position for B.O.P. handling, transportation and ease of handling on the rig.
The outer barrel houses pressure energised resilient packing elements which when energised
effect a seal around the inner barrel. These packing elements must have the same internal wellbore
pressure rating as the diverter system. Figures 15, 15A, and 16 show the Cameron and Vetco
telescopic joints.
Seal Failure:
Riser pipe connector seal failure causing loss of drilling fluid can have a serious effect
on well control. The resultant loss of hydrostatic head could reduce bottom hole pressure sufficiently to allow the well to flow. This is especially true where high mud weights
are required.
Choke and kill line sealing is also vital to well control. Failure in this area while circulating out a kick could have catastrophic effects on both the rig and personnel.
DIVERTER SYSTEM
CHAPTER 1
1-5
b)
2)
Weld failure.
3)
4)
Loss of pre-load.
5)
In deep water the riser pipe can be collapsed due to the outside hydrostatic pressure of
the sea water when the drilling fluid inside the riser is lost. Loss of drilling fluid can be
caused by:
1)
Lost circulation.
2)
Disconnecting the riser from the B.O.P. while full of drilling fluid.
CHAPTER 1
1-6
Figure 1
Vent/Flowline Installations
DIVERTER SYSTEM
CHAPTER 1
1-7
Figure 2
CONTROL SYSTEM
(ON RIG FLOOR)
DIVERTER
HOUSING
DIVERTER
FLOWLINE
BALL (FLEX)
JOINT
MARINE RISER
(BELOW SLIP JOINT)
SLIP
JOINT
Hughes KFDS
Diverter System
CHAPTER 1
1-8
Figure 3
400
200
0
0
200
400
600
800
1000
Figure 4
15
10
15
5
0
0
200
400
600
800
1000
1200
DIVERTER SYSTEM
CHAPTER 1
1-9
Figure 5
CHAPTER 1
1-10
Figure 6
DIVERTER SYSTEM
CHAPTER 1
1-11
Figure 7
HYDRIL DIVERTER
with integral valve
functions and
switchable target.
STARBOARD
VENT
SHALE
SHAKER
Always open
flow selector
DIVERTER
WITH INTEGRAL
VALVE
FUNCTIONS
PORT
VENT
SEQUENTIAL
DIVERTER
SYSTEM
SHALE
SHAKER
DIVERTER
STARBOARD
VENT
PORT VENT
FLOW
TARGET
Valve Function
1. Diverter valve
2. Flowline valve
3. Block valve
4. Port vent valve
5. Starboard vent valve
A Hydril diverter system significantly decreases risk of malfunction through its integral valve design, top. The upward
movement of one component, the piston, stops upward flow and opens the overboard vent simultaneously. Sequential diverters,
bottom, have remote valves and linkages with sequencing steps which create chances for malfunction.
FLOW SELECTOR
FS DIVERTER
FLEX JOINT
DRILL PIPE
Hydril FS 21-500
CHAPTER 1
1-12
Figure 8
HANDLING
TOOL
FS 21-500
MARINE RISER
DIVERTER
HOUSING
PACKING
UNIT
FLOW
LINE
VENT
LINE
DRILL
PIPE
U.S. PATENTS
4,444,401
4,456,062
4,456,063
DIVERTER SYSTEM
SIDE
SEAL
Hydril FS 21-500
CHAPTER 1
1-13
Figure 9
FLOW
SELECTOR
INSTALLATION
DATA
View C-C
Side Mount
Hydril FS 21-500
CHAPTER 1
1-14
View B-B
Bottom Mount
DIVERTER
Overboard
Overboard
Vent
Vent
TWO-POSITION
TARGET PLUG
DIVERTER
EXHAUST
U.S. PATENTS
4,566,494
Figure 10
TENSIONERS
WAVE
VELOCITY
CURRENT
VELOCITY
RIG FLOOR
TELESCOPIC JOINT
PULL OF
TENSIONERS
NET WEIGHT
OF WAVES
AND CURRENT
FORCES
NET WEIGHT OF
RISER IN WATER
NET WEIGHT OF
MUD IN WATER
NET WEIGHT
OF SUSPENDED
DRILL PIPE
CONNECTOR
BALL JOINT
BOP STACK
GUIDE BASE
DIVERTER SYSTEM
CHAPTER 1
1-15
Figure 11
CHAPTER 1
1-16
Figure 12
DIVERTER SYSTEM
CHAPTER 1
1-17
Figure 13
Riser Connector
CHAPTER 1
1-18
Figure 14
Riser Connector
DIVERTER SYSTEM
CHAPTER 1
1-19
Figure 15
RELEASED
LOCKED
VIEW A-A
DETAIL B
(INNER
BARREL
ENGAGED
IN END
CONNETOR
CHAPTER 1
1-20
Figure 15A
Packing Element
DIVERTER SYSTEM
CHAPTER 1
1-21
Figure 16
CHAPTER 1
1-22
Figure 17
DIVERTER SYSTEM
CHAPTER 1
1-23
Figure 18
Handling Tools
CHAPTER 1
1-24
Figure 19
DIVERTER SYSTEM
CHAPTER 1
1-25
Figure 20
CHAPTER 1
1-26
Figure 21
ANTI-ROTATION PINS
FLEXIBLE
URETHANE
SHIELD
ELEMENT RETAINER
FLANGE
STATIC O-RING SEAL
FLEX ELEMENT
WEAR BUSHING
DIVERTER SYSTEM
CHAPTER 1
1-27
Figure 21A
SHIELD
BACK
FLANGE
O-RINGS
RETAINER
FLANGE
NUTS
NIPPLE
FLEX ELEMENT
ASSEMBLY
ANTI-ROTATION
PIN
RETAINER
FLANGE
STUDS
BACK FLANGE
FLEX ELEMENT
SHIELD
SPACER
BOLTS
WEAR
RING
WEAR RING
ANTI-ROTATION
PIN
SHIELD
SPACER
GUIDES
BODY
RETAINER
FLANGE
CHAPTER 1
1-28
Figure 22
DIVERTER SYSTEM
CHAPTER 1
1-29