Sie sind auf Seite 1von 1

VFT Series Flash Tanks

"Featuring Exclusive Internal Separator for Enhanced Steam Quality"


Model
Sizes
Connections
Body Material
PMO Max. Operating Pressure
TMO Max. Operating Temperature
PMA Max. Allowable Pressure

VFT
6, 8, 12, 16

A
OUTLET

Carbon Steel
150 PSIG
366F
150 PSIG @ 450F

F
G

Note: 250 PSIG unit available. Consult factory.

1/2
NPT

J
NPT

T Y P I C A L A P P L I C AT I O N

The VFT flash recovery vessels are installed in


condensate return systems in order to capture
and utilize the flash steam coming off of the hot
condensate. This flash steam is typically piped
away for use on low pressure steam processes.

INLET

Use Table 1 to determine amount of Flash Steam that will


be generated by the hot pressurized condensate. The
percentage of Flash Steam formed is found where
Condensate Pressure and Flash Tank Pressure intersect.
Multiply your Condensate Load by the decimal equivalent
of the Flash Steam Percent to determine the amount of
Flash Steam in lbs/hr. Then, use Figure 1 to determine
Flash Tank Size required:

L
NPT
D

Note: All Thermaflo flash recovery vessels are supplied with


ASME Section VIII Code Stamp.

Example: Condensate Pressure: 100 PSIG


Flash Tank Pressure: 20 PSIG
Condensate Load:
8,000 lbs/hr
% Flash Steam:
8.7% from chart
Decimal Equivalent % Flash Steam = .087
.087 x 8000 = 696 lbs/hr of flash steam

Ta b l e 1 P E R C E N T ( % ) F L A S H S T E A M
Produced when condensate is discharged to atmosphere (0 PSIG) or into a
flash tank controlled at various pressures

Therefore Choose: 12 FLASH TANK


Figure 1 Recovery Vessel Capacities
20,000

Condensate (lbs/hr)

Size 16
10,000

Size 12

5,000

Size 8
2,000
0

Size 6
500

1000

2000

3000

696
Flash Steam (lbs/hr)

H
150#
FLANGE

HOW TO SIZE/ORDER

8,000

H
150#
FLANGE

DIMENSIONS & WEIGHTS

Condensate
Pressure
(PSIG)

5
10
15
20
30
40
60
80
100
125
150
200
250
300
350
400

1.6
2.9
3.9
4.9
6.5
7.8
10.0
11.8
13.3
14.9
16.3
18.7
20.8
22.5
24.1
25.6

0.0
1.3
2.4
3.3
5.0
6.3
8.5
10.3
11.8
13.5
14.9
17.3
19.4
21.2
22.8
24.2

Flash Tank Pressure (PSIG)


10
20
30
40
0.0
1.1
2.1
3.7
5.1
7.3
9.1
10.6
12.3
13.7
16.2
18.2
20.0
21.7
23.1

0.0
1.7
3.0
5.3
7.1
8.7
10.4
11.8
14.3
16.4
18.2
19.9
21.4

0.0
1.4
3.7
5.5
7.1
8.8
10.3
12.8
14.9
16.8
18.4
19.9

0.0
2.3
4.2
5.8
7.5
9.0
11.5
13.7
15.5
17.2
18.7

60

80

100

0.0
1.9
3.5
5.3
6.8
9.4
11.5
13.4
15.1
16.7

0.0
1.6
3.4
4.9
7.6
9.8
11.7
13.4
15.0

0.0
1.8
3.3
6.0
8.2
10.2
11.9
13.5

inches/pounds

Size

Weight
(lbs)

6
8
12
16

65/8
85/8
123/4
16

51
52
53
62

381/2
393/4
411/4
50

12
13
21
24

8
81/2
113/4
133/8

10
12
13
14

251/2
255/8
26
32

2
4
6
6

3/4
3/4
11/2
2

11/2
2
2
2

75
150
165
215

PO BOX 473639, Charlotte, NC 28247 Phone 704-940-1228

www.thermafloengineering.com

Fax 704-940-1227

8/11